Page 6
TROUBLESHOOTING
A blinking“green” Relay board status LED indicates that communication has not been properly established for this card.Contact
Hubbell ControlsTechnical Service at (800) 888-8006 for assistance and replacement as required.A complete Troubleshooting
Guide is contained in the “CX Panel User Manual” provided as a downloadable document at
www.hubbell-automation.com.
CX PANEL SPECIFICATIONS
• Panel Input Power Requirements:
o Input Voltage “2” designator – 100VA, 120-277VAC universal
o Input Voltage “3” designator – 100VA, 347-480VAC universal
• Overall Dimensions:
o Surface mount, 20” W x 24” H x 3.5” D.
• Relay Load Ratings:
o CXR2N – 120/277VAC, Electrically Held, N/O, 20Amps, HID and Fluorescent Ballast 15Amps, Fluorescent
Electronic Ballast 16 Amps, Tungsten (120V only) 15 Amps, 3/4HP at 120V and 277V,
o CXR3L – 120/277/347VAC, Latching, 30Amps, HID and Fluorescent Ballast at 120/277 VAC, Fluorescent
Electronic Ballast 16 Amps, and 20A mps Tungsten at 120VAC, 1HP at 120V, and 20Amps, HID and
Fluorescent Ballast at 347V
o CXRTN – 208/240/480VAC, Electrically Held, N/O, 20Amps, HID, Ballast, 2HP
o CXR2C – 120/277VAC, Electrically Held, N/C, 20Amps, HID and Fluorescent Ballast 15Amps Fluorescent
Electronic Ballast 16 Amps, Tungsten (120V only) 15 Amps, 3/4HP at 120V and 277V,
o CXRTC – 208/240/480VAC, Electrically Held, N/C, 20Amps, HID, Ballast, 2HP
• Low Voltage Inputs:
o CX 16-Relay Panel – 20 available inputs
o CX 24-Relay panel – 30 available inputs.
o LowVoltage Switches – 2 or 3 wire momentary or maintained style, with or without LED indication. LED
indication support is LED – “ON” when switch is active and LED – “OFF” when switch is inactive. Green
“ON” with Red “OFF” indication is not supported.
o Motion Sensor Input – Three wire 24VDC
o Photocell – Three wire 24VDC power, 0-10V DC control input.
• Output Relay Contacts
o Two each for 16-Relay panel only – Dry Contact Output, NO/NC, 24V AC/DC, 50mA
o Three each for 24-Relay panel only – Dry Contact Output, NO/NC, 24V AC/DC, 50mA
• Operating Environment:
o Indoor Use Only; 0 to 50°C; Relative Humidity: 0 – 90% non-condensing.
PANEL LOAD SCHEDULE FORM
A Panel Load Schedule Form is supplied in the clear plastic pocket inside the Panel Door to record the lighting circuit relay
assignments while connecting the relays. Low voltage input types and assignments should also be recorded on the form.
72-00517 Rev.A