Hubbell Building Automation, Inc.
9601 Dessau Road • Austin, Texas 78754
512-450-1100 • 512-450-1215 Fax
www.hubbell-automation.com
72-00400
Assigning Switch Station Network Address
The Switch Station network address is set via three rotary dials lo-
cated under the Switch Station face plate as shown in figure 2, Keyed
Switch Station Controls Diagram. Each Switch Station is factory set
to address 001 prior to shipping.
To set the Switch Station Address, rotate the dial(s) with the small,
blade screwdriver till the indicator points to the appropriate number.
Assign each Switch Station its address as delineated in the project
plans as applicable. Dial “A” sets the most significant digit of the
network address and Dial “C” sets the least significant digit of the
network address. For example, address 001 is set by Dial A = “0”,
Dial B = “0” and Dial C = “1”.
Note: For the purposes of addressing, an LX Keyed Switch Station
should be considered the same as a standard LX Switch Station
and numbered within that sequence without duplication.
Programming Switch Station Functions
Refer to the LX Lighting Controls User’s Manual to assign the Switch
Station button(s) to the lighting circuit(s) and setup schedules and
system functionality using the Touch Tablet Graphical User Interface.
Note: As of March 1, 2008 all HBA programming interfaces will
recognize the Keyed Switch Station and provide a unique interface.
Prior versions of programming interfaces will recognize the Keyed
Switch as a standard LX Switch Station and the Button Programming
options will be ignored. All other programming functions (mapping,
naming, active/inactive times) will function normally.
Note: If another device or schedule is programmed to control the
same relay or group as the key switch, it is possible that the state
of the relay will become out of sync with the position of the key switch.
In this case, the key switch will need to be turned through an ON/OFF
cycle to re-align the state of the key switch to that of the relay.
This simple action will restore the normal action of the key switch.
Resetting the Switch Station
If needed, the Switch Station can be reset to factory default settings
(except network address) by holding down the service switch until the
switch state LED turns green. When changing the station address it is
also necessary to cycle power to reset the station to the new address
number.