Husky BJE 007 Installation instructions

1. Locate the most visible location to install control panel.
2. Securely (not permanently) mount control panel to wall.
3. Assemble gauge (do not install to tank).
4. Loosen thumbscrews on sensor.
5. Slide sensor to desired depth (high or low).
6. Connect an ohmmeter to sensor leads.
approximately 1 to 2 turns past hand tight, but do not overtighten.
9. Remove glass jar and linkage assembly from bung adaptor - do not disturb sensor setting.
10. Use appropriate sealant on male threads of bung adaptor.
tight, but do not overtighten.
12. Install linkage assembly into bung adaptor. Float arm must travel freely and not contact any
overtighten.
14. Solder (or wire nut) sensor leads then tape the connections.
15. Seal hole with silicone or appropriate sealant.
16. Connect wire to printed circuit board terminals marked "N/C SENSOR IN".
17. Select a non-switched 24-hour hot 115v outlet, preferably dedicated solely for use with the 007.
18. Connect transformer wires to printed circuit board terminal marked "12VDC POWER IN" .
19. Secure transformer to outlet using outlet plate screw.
DO NOT PLUG IN THE TRANSFORMER PRIOR TO CONNECTING WIRES TO CONTROL PANEL.
ONLY USE HUSKY®BRAND TRANSFORMER WITH 007 TANK MONITORS.
TESTING / MAINTENANCE / INSPECTION
007 JAR-
HEAD
WARNING
Page 1 009310-7 7/2019
INSTALLATION INSTRUCTIONS
Daily
position.
Quarterly
• Remove sensor from tank and manually
into alarm mode.
function.
to control panel and accessories.
• Follow all city, state, or federal wiring code
• Apply city, state, or federal testing regulations
as appropriate.
ANY TEST / INSPECTION FAILURE
REQUIRES IMMEDIATE EQUIPMENT
REPLACEMENT OR REMOVAL FROM
SERVICE.
MADE IN THE USA
007555, 008666 & 009919
and Inspection Instructions

CAUTION: DO NOT EXCEED THE MAXIMUM MILLIAMP LOAD!
Designed to drive up to 1000 milliamps of optional accessories.
ALWAYS ADHERE TO INSTALLATION / USAGE INSTRUCTIONS AND WARNINGS.
Improper use may result in injury, damage, or hazardous spill.
Husky Corporation will, at its option, repair, replace, or credit the purchase price of any BJE®product deemed to be defective
in material and/or workmanship for a period of one (1) year.
Buyer must return the products to Husky®, transportation charges prepaid. The warranty excludes damages due to
malfunction, failure to follow manufacturer's installation, operation or maintenance instructions and guidelines, unauthorized
The warranty provisions contained herein apply only to original purchasers who use the equipment for commercial or
Husky assumes no liability for labor charges or other costs incurred by Buyer incidental to the service, adjustment, repair,
incurred by the purchaser during the time necessary to repair the equipment. Husky assumes no liability for any incidental,
consequential, or other damages under any warranty, express or implied, and all such liability is hereby expressly excluded.
Husky reserves the right to change or improve the design of any Husky Oil Filter Crushers, Tank Monitors, Tank Gauges,
WARRANTY
• Use of equipment is at individuals’ own
risk.
and federal regulations regarding
use and installation of monitoring
equipment.
manufacturer’s installation and
maintenance instructions.
during maintenance activities.
damaged equipment immediately.
to appropriate authorities.
equipment during maintenance and
inspection activities.
extinguishing equipment within 5 ft /
1.5 m of tanks.
®tape or appropriate
thread sealant.
• The tank contents are the sole
responsibility of the tank owner.
• Never allow waste product to touch eyes
or skin.
• Never install monitors outdoors without
proper protection from the elements.
• Never use on below ground storage
tanks.
• Never exceed the maximum milliamps
and maintenance instructions.
• Never solely rely on this product; there is
no substitute for human supervision.
• Never to be used as a component of any
automatically controlled pump
transfer system.
GENERAL WARNINGS / INSTRUCTIONS PERTAINING TO A RISK OF FIRE, ELECTRIC
SHOCK OR INJURY TO PERSONS:

Audible alarm won't shut o... 1. Replace control panel.
System won't go into alarm mode... 1. Verify all wires are connected properly.
2. Conrm transformer is plugged in.
Audible alarm won't sound... 1. Conrm toggle switch is in "ON" position.
Strobe light won't stop ashing... 1. Replace control panel.
Bulk Product Sensor activates alarm prematurely... 1. Conrm oat is in the correct position.
2. Conrm pipe is not over 10 ft / 3 m long.
Applications Single or double walled above ground tanks.
Fluids Test and warranty for oil, waste oil, diesel fuel, antifreeze, water and other uids
with a low ash point
Milliamp load 750 mA maximum / 1000 mA maximum of optional accessories
Pipe ½" x 6" (12.7 mm x 152.4 mm) NPT PVC
Sensor Buna
Shipping Weight 8 - 11 lbs / 3.6 - 4.9 kg (depends on length of Jarhead)
Thread 2" / 50.8 mm NPT
Case Quantity 5 - 10 (depends on length of Jarhead)
TROUBLESHOOTING GUIDE
WIRING CONNECTIONS
GENERAL TECHNICAL DATA
Husky Corporation • 2325 Husky Way • Pacic, MO 63069 • Phone: (800) 325-3558 • Fax: (636) 825-7300 • www.husky.com
Page 3 009310-7 7/2019
12VDC POWER IN
12VDC POWER IN
NC SENSOR IN
NC SENSOR IN
-
MUTED OUT ON ALARM
+
-
POWER OUT ON ALARM
+
TO SOLENOID VALVE
TO SOLENOID VALVE
Use 18-gauge / 2 conductor wire up to 150 ft. or
14 gauge / 2 conductor wire up to 350 ft. to connect all components.

Husky Corporation • 2325 Husky Way • Pacic, MO 63069 • Phone: (800) 325-3558 • Fax: (636) 825-7300 • www.husky.com
Page 4 009310-7 7/2019
007 SPDT POWER RELAY
007 REMOTE STROBE LIGHT
007 REMOTE SIREN
Model 007655, 007656 Leak Guards
007742,007743OverllGuards
1. Remove eyelet connector from end of chain
and save.
2. Determine tank depth in inches.
3. Stand oat on end on a at work surface
alongside a measuring tape and pull chain
taut to desired measurement.
4. Cut chain on mark and feed chain through
bottom center hole in shaft and back out of
either hole on sides of shaft.
5. Secure chain with eyelet by crimping eyelet
closed.
6. Loosen thumbscrews on sensor.
7. Slide sensor, positioning arrow just inside top
of clear window.
8. Connect an ohmmeter to sensor leads.
9. Using chain, pull orange indicator to bottom
of gauge and conrm circuit is closed.
10. Slowly release chain tension allowing spring
to raise orange indicator to its full extension.
11. Conrm circuit is now open.
12. Tighten thumbscrews rmly, approximately 1
to 2 turns past hand tight - do no overtighten.
13. Apply appropriate sealant to male threads of
bung adaptor.
14. Slowly lower weighted oat into tank and
tighten gauge, approximately 1 to 2 turns past
hand tight. Do not overtighten.
15. Conrm orange indicator is at proper level
- if tank is empty it should not be visible.
(If visible, remove sight glass and depress
orange indicator. Reinstall sight glass. If
orange indicator is still visible, recheck
measurements in steps 2 - 4 and shorten
chain as required.)
16. Solder (or wire nut) sensor leads then tape
the connections.
17. Seal hole with silicone or appropriate sealant.
18. Connect wire to printed circuit board
terminals marked "N/C SENSOR IN".
Model 007645
1. Install power relay in proper enclosure for
application.
2. Connect terminals marked 1 & 2 on the power
relay to terminals marked "TO SOLENOID
VALVE" on the printed circuit board.
Observation of polarity is not necessary.
Model 007695
1. Connect strobe leads to terminals marked
"POWER OUT ON ALARM" on the printed
circuit board.
2. Connect red lead to (+) terminal and black lead
to (-) terminal.
3. Polarity must be observed.
NOTE: For indoor or outdoor use.
Model 007690
1. Connect siren leads to terminals marked
"MUTED OUT ON ALARM" on the printed
circuit board.
2. Connect red lead to (+) terminal and black lead
to (-) terminal.
3. Polarity must be observed.
NOTE: If mounting outdoors, angle siren down to shed water.
007SV / 007SVT SOLENOID VALVE
007 REMOTE LEAK / OVERFILL GUARDS
Model 007580, 007570
1. Mount solenoid valve and plumb air supply
observing airow direction and assuring air line
is free of debris. Caution - use backup wrench.
2. Connect terminals marked "From 007" on
the solenoid valve to terminals marked "TO
SOLENOID VALVE" on the printed circuit
board.
3. Connect supplied transformer to terminals
marked "12VDC POWER IN" on the solenoid
valve. Observation of polarity is not necessary.
4. Plug transformer into a non-switched 24-hour
hot 115v outlet and secure transformer using
outlet plate screw.
5. Test solenoid valve for proper air shut o.
Table of contents
Popular Security System manuals by other brands

Sirena
Sirena SMART-Q INSTALLATION AND APPLICATION INSTRUCTIONS

SANJIANG
SANJIANG JB-FSD-9082 quick start guide

Skil-Care
Skil-Care ChairPro 909370 quick start guide

GSL electronics
GSL electronics HB 12 operating instructions

Aico
Aico RadioLINK Ei450 instruction manual

Directed Electronics
Directed Electronics 554R installation guide