Husky Corporation • 2325 Husky Way • Pacic, MO 63069 • Phone: (800) 325-3558 • Fax: (636) 825-7300 • www.husky.com
Page 4 009310-7 7/2019
007 SPDT POWER RELAY
007 REMOTE STROBE LIGHT
007 REMOTE SIREN
Model 007655, 007656 Leak Guards
007742,007743OverllGuards
1. Remove eyelet connector from end of chain
and save.
2. Determine tank depth in inches.
3. Stand oat on end on a at work surface
alongside a measuring tape and pull chain
taut to desired measurement.
4. Cut chain on mark and feed chain through
bottom center hole in shaft and back out of
either hole on sides of shaft.
5. Secure chain with eyelet by crimping eyelet
closed.
6. Loosen thumbscrews on sensor.
7. Slide sensor, positioning arrow just inside top
of clear window.
8. Connect an ohmmeter to sensor leads.
9. Using chain, pull orange indicator to bottom
of gauge and conrm circuit is closed.
10. Slowly release chain tension allowing spring
to raise orange indicator to its full extension.
11. Conrm circuit is now open.
12. Tighten thumbscrews rmly, approximately 1
to 2 turns past hand tight - do no overtighten.
13. Apply appropriate sealant to male threads of
bung adaptor.
14. Slowly lower weighted oat into tank and
tighten gauge, approximately 1 to 2 turns past
hand tight. Do not overtighten.
15. Conrm orange indicator is at proper level
- if tank is empty it should not be visible.
(If visible, remove sight glass and depress
orange indicator. Reinstall sight glass. If
orange indicator is still visible, recheck
measurements in steps 2 - 4 and shorten
chain as required.)
16. Solder (or wire nut) sensor leads then tape
the connections.
17. Seal hole with silicone or appropriate sealant.
18. Connect wire to printed circuit board
terminals marked "N/C SENSOR IN".
Model 007645
1. Install power relay in proper enclosure for
application.
2. Connect terminals marked 1 & 2 on the power
relay to terminals marked "TO SOLENOID
VALVE" on the printed circuit board.
Observation of polarity is not necessary.
Model 007695
1. Connect strobe leads to terminals marked
"POWER OUT ON ALARM" on the printed
circuit board.
2. Connect red lead to (+) terminal and black lead
to (-) terminal.
3. Polarity must be observed.
NOTE: For indoor or outdoor use.
Model 007690
1. Connect siren leads to terminals marked
"MUTED OUT ON ALARM" on the printed
circuit board.
2. Connect red lead to (+) terminal and black lead
to (-) terminal.
3. Polarity must be observed.
NOTE: If mounting outdoors, angle siren down to shed water.
007SV / 007SVT SOLENOID VALVE
007 REMOTE LEAK / OVERFILL GUARDS
Model 007580, 007570
1. Mount solenoid valve and plumb air supply
observing airow direction and assuring air line
is free of debris. Caution - use backup wrench.
2. Connect terminals marked "From 007" on
the solenoid valve to terminals marked "TO
SOLENOID VALVE" on the printed circuit
board.
3. Connect supplied transformer to terminals
marked "12VDC POWER IN" on the solenoid
valve. Observation of polarity is not necessary.
4. Plug transformer into a non-switched 24-hour
hot 115v outlet and secure transformer using
outlet plate screw.
5. Test solenoid valve for proper air shut o.