manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ICM Controls
  6. •
  7. Measuring Instrument
  8. •
  9. ICM Controls ICM450A General instructions

ICM Controls ICM450A General instructions

1. Press the SETUP button to enter Setup mode. Setup LED will light.
2. Use the and arrows to change user parameters.
3. Scroll through setup by pressing and releasing the SETUP button.
4. When the last parameter has been set, the phase average will be displayed and the
Setup LED will automatically turn OFF.
Setting the Parameters
Button Functions
Press arrows to scroll
through and select user
parameter settings in
Setup mode. HOLD
down for fast edit.
Press to
enter Setup
mode and
select user
parameters.
Hold for
voltage display
a b, b c,
a c
(simultaneously).
Press to read
faults. Hold for 5
seconds to clear
faults and reset
memory.
Installation
1. Using (2) #8 screws, mount the ICM450A and ICM450A plus+ in a cool, dry, easily
accessible location in the control panel.
2. Connect voltage as shown in Figure 1 (below). Leave existing line and load side
connections intact on the contactor.
3. Load side monitoring is optional (unit may be used to monitor line side only). Wire the
contactor and optional control voltage monitoring as in Figures 2 and 3 (below).
Note: Load/line wire must be rated for 3-phase voltage rating, 20 AWG minimum.
4. Upon application of power, the CM450A and ICM450A plus+ will be on line and will
begin to monitor the system.
• Terminals 4 and 5 are the control signal input terminals
• “Control Mode” is turned ON or OFF in setup
• With “Control Mode” set to “ON,” there must be a voltage present on terminals 4 and
5 for the relay output terminals 1 and 2 to close; this voltage can be supplied from a
thermostat, pressure switch, etc.
• When the voltage on these terminals is re-applied,
the unit will not re-energize until the delay on break
(0-10 minutes) time has elapsed
• Use of terminals 4 and 5 is optional; they will be ignored if the “Control Mode” is
set to “OFF”
• Terminals 1 and 2 are “dry,” normally open contacts
• Terminals1and2areclosedwhenpoweriswithinspecications
• Terminals 1 and 2 open when there is a fault condition
• Terminals 1 and 2 open when there is a loss of the control signal with “Control Mode” set
to “ON”
Note: Terminals 6, 7 and 8 used for ModBus communication on ICM450A and
ICM450A plus+.
Figure 3
Contactor Voltage
(18-240 VAC)
Optional Control Voltage
Contactor
Coil
COM NO NC
Figure 2
Contactor Voltage
(18-240 VAC)
Optional Control Voltage
Contactor
Coil
COM NO NC
Figure 1
Incoming 3-phase
voltage from load
or “back” side of
contactor (optional)
Incoming 3-phase voltage from
line or “front” side of contactor
The incoming 3-phase voltage
is used to power up the
ICM450A as well (190-600)
ICM450A and ICM450A plus+ Wiring Diagrams
Load 3
Load 2
Load 1
LOAD
L1 L2
3-Pole Contactor
Load 2
Load 1
L1 L2
2-Pole Contactor
Load
3
LOAD
L3 L3
6 87432 51
Optional Control
Voltage
18-240 VAC
6 87432 51
Optional Control
Voltage
18-240 VAC
ICM450A &
ICM450A plus+
Programmable 3-Phase
Line Voltage Monitors
Installation of the ICM450A and ICM450A plus+ shall be performed by trained
technicians only. Adhere to all local and national electric codes.
Disconnect all power to the system before making any connections.
Caution
Specification
Input:
• Line Voltage: Universal, 190-600 VAC
• Frequency: 50-60 Hz
• Load Side Monitoring: Optional
• Control Voltage: 18-240 VAC
• Frequency: 50-60 Hz
Output:
• Type: Relay, SPDT
• Voltage Range: 277 VAC @ 10A maximum
• Frequency: 50-60 Hz
Control Operating Temperature
• Operating Temperature: -40ºF to +167ºF (-40ºC to +75ºC)
• Storage Temperature: -40ºF to +185ºF (-40ºC to +80ºC)
LCD Operating Temperature :-4ºF to +167ºF (-20ºC to +75ºC)
Mechanical:
• Mounting: Surface mount using (2) #8 screws
• Terminations: 1/4” quick connects
• Weight: 12 ounces (341 grams)
ModBus: RS485 Communication (ICM450A plus+)
Dimensions: 6.5”L x 4.75”W x 1.09”D
Parameters
Line Voltage: Universal 190-600 VAC
Phase Unbalance Protection
• Voltage Unbalance: 2-20% adjustable
Over/Under Voltage Protection
• Under Voltage: 2-25% adjustable
• Over Voltage: 2-25% adjustable
Phase Loss Protection
• Phase Loss Condition: Equals 25% of nominal for any given phase; system will shut
down and a fault will be recorded should this occur
Delay on Break Timer
• Time Delay: 0 to 10 minutes adjustable
Control Voltage: 18-240 VAC
• Control Mode: ON/OFF
Fault Interrogation Delay
• Time Delay: 0 to 15 seconds adjustable
• Provides a delay between fault detection and system shutdown - helps to eliminate
nuisance trips or unnecessary shutdowns
Reset Mode: 0 (auto) or 1-10 retries
Set Date and Time: Provides real time clock for date and time stamp (ICM450A plus+)
Language: Set to English or Spanish language for display
Parameters
Parameter Description Range Default Recommended
Line Voltage Average phase to phase line voltage 190-600 208 Nameplate Voltage
Delay on Break Amount of time between the load de-energizing and re-energizing 0-10 minutes .1
minute
4 minutes**
Delay on Fault Amount of time before the load de-energizes due to a non-critical fault* 0-15 seconds 15
seconds
7-8 seconds**
% Over/Under
Voltage
Maximum/minimum phase to phase average voltage, respectively 2-25% 20% 12-15%**
% Phase Unbalance Amount of allowable voltage unbalance 2-20% 20% 4-5%**
Reset Mode 0 (auto) or number of times the load can be re-energized after a load side fault before a manual reset is
necessary
Note: When monitoring line side only, the reset mode will always be 0 (auto)
0 (auto)
, 1-10
0 (auto) 0 (auto)
Control Mode With control mode set to OFF, the load will energize if no 3- phase fault conditions exist; with control mode ON,
the load will energize if no fault conditions exist and control voltage is present at terminals 4 and 5 of the ICM450A
ON or OFF ON Based on wiring
Date and Time Provides real time clock for date and time stamp (ICM450A plus+ models)
ON or OFF
ON
ON
Language Set to English or Spanish language for display
EN or SP EN English
* Non-critical faults are faults such as High/Low Voltage and Phase Unbalance. Critical faults, such as Phase Loss and Phase Reversal, have a fault interrogation and typical response time
of under 4 seconds and it is not user adjustable.
** For best recommendations, consult manufacturer of equipment.
Troubleshooting
Problem LCD
Readout LED Status Corrective Action
Load will not energize Phase Average All LEDs Off Conrmthatthecontrolinput(terminals4&5)isproperlyconnectedandcongured
Load will not energize Phase Average Load LED Off,
Fault LED blinking
Press FAULToncetoobservethecurrentfault;correcttheconditionoftherstfaultthatappears
(see Fault Conditions above, for a list of corrective actions)
Fault LED blinks repeatedly
while load is energized
Phase Average Fault LED Blinking,
Load LED On
Indicates there are faults saved in the memory, press FAULT rapidly to scroll through saved faults; to clear
the faults, press and hold FAULT for more than 5 seconds
Load will not de-energize
when control voltage is OFF
Phase Average Load LED On,
Control LED Off
The control mode setting is OFF; press SETUP to get to the control mode. Press to set the control
mode ON
Setup LED is on while load
is being energized
Anything Other Than
Phase Average
Setup LED On,
Load LED On
To exit the setup mode, press either READ or FAULT
Load will not energize Reset Fault LED Blinking Unit in lockout; maximum number of retries in manual reset mode has been reached; to reset unit, press
FAULT and hold for more than 5 seconds
Load turns ON and OFF
repeatedly
Readout is Irrelevant Fault LED Blinking Fix load side fault; press FAULT to observe condition; the delay on break period may be too short; press
SETUP to enter the delay on break mode; press to lengthen the delay
ONE-YEAR LIMITED WARRANTY
The Seller warrants its products against defects in material or workmanship for a period of one (1) year from
the date of manufacture. The liability of the Seller is limited, at its option, to repair, replace or issue a non-case
credit for the purchase prices of the goods which are provided to be defective. The warranty and remedies set
forth herein do not apply to any goods or parts thereof which have been subjected to misuse including any use or
applicationinviolationoftheSeller’sinstructions,neglect,tampering,improperstorage,incorrectinstallationor
servicing not performed by the Seller. In order to permit the Seller to properly administer the warranty, the Buyer
shall: 1) Notify the Seller promptly of any claim, submitting date code information or any other pertinent data as
requested by the Seller. 2) Permit the Seller to inspect and test the product claimed to be defective. Items claimed
to be defective and are determined by Seller to be non-defective are subject to a $30.00 per hour inspection
fee.ThiswarrantyconstitutestheSeller’ssoleliabilityhereunderandisinlieuofanyotherwarrantyexpressed,
implied or statutory. Unless otherwise stated in writing, Seller makes no warranty that the goods depicted or
describedhereinaretforanyparticularpurpose.
Patent No. 424,953
7313 William Barry Blvd., North Syracuse, NY 13212
(Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276
www.icmcontrols.com
LIAF290
Press and release fault button to scroll through all saved faults.
Note: For initial setup, press and hold FAULT for 5 seconds to remove any previously stored faults.
Fault Problem Corrective Action
Back Phase Loss Not all three of the phases on the load side
are present
1. Re-energize the contactor.
2. If the fault reappears after the load energizes:
a. Turn all power OFF
b. Check all load side connections
c. Check the contacts of the contactor for debris or excess carbon.
Back Phase Rev Loads 1, 2, or 3 are not in sequence
(not 120º phase shifted)
1. Turn OFF all power.
2. Swap any 2 phases on the load side of the ICM450A and ICM450A plus+ only (example: swap load 1 and
load 2) *
3. Re-apply power.
Back Phase Unbalance A voltage unbalance between the three load
phases exceeds the unbalance setpoint
1. Press the READ button to observe the present load voltages. Check system for unbalance cause.
2. Increase the fault interrogation time if necessary.
3. Increase the percent unbalance setting if necessary.
Front Over Voltage Average phase-phase voltage exceeds the
maximum percentage
1. Check system for over-voltage cause.
2. Increase the percent over-voltage setting if necessary.
3. Increase the fault interrogation time if necessary.
Front Phase Loss Not all three of the phases on the line side
are present
1. Press and hold the READ button on the phase monitor or use an AC voltmeter to carefully measure all three
phase-phase line voltages (example: Line 1
Line 2, Line 2
Line 3, Line 3
Line 1).
2. Repair the missing phase.
Front Phase Reversal Lines 1, 2, or 3 are not in sequence
(not 120º phase shifted)
1. Turn OFF all power.
2. Swap any 2 phases on the line side of the ICM450A and ICM450A plus+ (example: swap Line 1 and Line 2)*
3. Re-apply power.
Front Phase Unbalance A voltage unbalance between the three line
phases exceeds the unbalance setpoint
1. Press the READ button to observe the present load voltages. Check system for unbalance cause.
2. Increase the fault interrogation time if necessary.
3. Increase the percent unbalance setting if necessary.
Front Under Voltage Average phase-phase voltage is below the
minimum percentage
1. Check system for under-voltage cause.
2. Increase the percent under-voltage setting if necessary.
3. Increase the fault interrogation time if necessary.
Fault Conditions
* Only swap phases during initial setup, not after the ICM450A and ICM450A plus+ has been in operation without errors.

This manual suits for next models

1

Other ICM Controls Measuring Instrument manuals

ICM Controls ICM493-60A General instructions

ICM Controls

ICM Controls ICM493-60A General instructions

ICM Controls ICM493-60A General instructions

ICM Controls

ICM Controls ICM493-60A General instructions

ICM Controls ICM400 General instructions

ICM Controls

ICM Controls ICM400 General instructions

ICM Controls ICM450 General instructions

ICM Controls

ICM Controls ICM450 General instructions

Popular Measuring Instrument manuals by other brands

DeWalt DW0165 user manual

DeWalt

DeWalt DW0165 user manual

Knick Portavo 902 COND user manual

Knick

Knick Portavo 902 COND user manual

Bosch GIM 60 L Professional Original instructions

Bosch

Bosch GIM 60 L Professional Original instructions

SensorLink 8-182 Operator's manual

SensorLink

SensorLink 8-182 Operator's manual

SIGLENT SSA3000X Plus user manual

SIGLENT

SIGLENT SSA3000X Plus user manual

TA DHR Series Getting started guide

TA

TA DHR Series Getting started guide

EUTECH INSTRUMENTS Oakton 450 Series Operation instructions

EUTECH INSTRUMENTS

EUTECH INSTRUMENTS Oakton 450 Series Operation instructions

Vibration Research ObserVR1000 quick start guide

Vibration Research

Vibration Research ObserVR1000 quick start guide

Stabila LD 520 user manual

Stabila

Stabila LD 520 user manual

ELEKON BATLOGGER WE X manual

ELEKON

ELEKON BATLOGGER WE X manual

SUTO S418-V Instruction and operation manual

SUTO

SUTO S418-V Instruction and operation manual

Badger Meter Blancett B220-880 user manual

Badger Meter

Badger Meter Blancett B220-880 user manual

ETM DeltaBlue user guide

ETM

ETM DeltaBlue user guide

Emerson mobrey MSP-USTD1 Quick Start Booklet

Emerson

Emerson mobrey MSP-USTD1 Quick Start Booklet

OJ Electronics EFRP-900 instructions

OJ Electronics

OJ Electronics EFRP-900 instructions

Dresser D Series Installation supplement

Dresser

Dresser D Series Installation supplement

FASTLITE MOZZA operating manual

FASTLITE

FASTLITE MOZZA operating manual

DYNAPAR NorthStar WIND 56 instruction manual

DYNAPAR

DYNAPAR NorthStar WIND 56 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.