manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ICP DAS USA
  6. •
  7. I/O System
  8. •
  9. ICP DAS USA tM-R5 User manual

ICP DAS USA tM-R5 User manual

Other manuals for tM-R5

1

Other ICP DAS USA I/O System manuals

ICP DAS USA PISO-P64 Series User manual

ICP DAS USA

ICP DAS USA PISO-P64 Series User manual

ICP DAS USA WF-2000 Series User manual

ICP DAS USA

ICP DAS USA WF-2000 Series User manual

ICP DAS USA A-8111 Series User manual

ICP DAS USA

ICP DAS USA A-8111 Series User manual

ICP DAS USA PIO-D144U User manual

ICP DAS USA

ICP DAS USA PIO-D144U User manual

ICP DAS USA WF-2000 Series User manual

ICP DAS USA

ICP DAS USA WF-2000 Series User manual

ICP DAS USA PROFI-8455 Setup guide

ICP DAS USA

ICP DAS USA PROFI-8455 Setup guide

ICP DAS USA P8R8-DIO User manual

ICP DAS USA

ICP DAS USA P8R8-DIO User manual

ICP DAS USA DN-8K32R User manual

ICP DAS USA

ICP DAS USA DN-8K32R User manual

ICP DAS USA I-9018W User manual

ICP DAS USA

ICP DAS USA I-9018W User manual

ICP DAS USA I-7021 User manual

ICP DAS USA

ICP DAS USA I-7021 User manual

ICP DAS USA A-821PGH Series User manual

ICP DAS USA

ICP DAS USA A-821PGH Series User manual

ICP DAS USA M-7011 User manual

ICP DAS USA

ICP DAS USA M-7011 User manual

ICP DAS USA CAN-2018C User manual

ICP DAS USA

ICP DAS USA CAN-2018C User manual

ICP DAS USA WF-2055 User manual

ICP DAS USA

ICP DAS USA WF-2055 User manual

ICP DAS USA CAN-2060C User manual

ICP DAS USA

ICP DAS USA CAN-2060C User manual

ICP DAS USA tET Series User manual

ICP DAS USA

ICP DAS USA tET Series User manual

ICP DAS USA ET-2242 User manual

ICP DAS USA

ICP DAS USA ET-2242 User manual

ICP DAS USA tM-P8 User manual

ICP DAS USA

ICP DAS USA tM-P8 User manual

ICP DAS USA tM-AD8 User manual

ICP DAS USA

ICP DAS USA tM-AD8 User manual

ICP DAS USA CAN-2054C User manual

ICP DAS USA

ICP DAS USA CAN-2054C User manual

ICP DAS USA ET-2254 User manual

ICP DAS USA

ICP DAS USA ET-2254 User manual

ICP DAS USA WP-5238-CE7 User manual

ICP DAS USA

ICP DAS USA WP-5238-CE7 User manual

ICP DAS USA ET-8KP4-MTCP User manual

ICP DAS USA

ICP DAS USA ET-8KP4-MTCP User manual

ICP DAS USA PIO-DA4 User manual

ICP DAS USA

ICP DAS USA PIO-DA4 User manual

Popular I/O System manuals by other brands

SMC Networks EX600-AXA Installation & maintenance manual

SMC Networks

SMC Networks EX600-AXA Installation & maintenance manual

Siemens SIMATIC ET 200SP HA Equipment manual

Siemens

Siemens SIMATIC ET 200SP HA Equipment manual

Advantech PCM-27J3AU Startup manual

Advantech

Advantech PCM-27J3AU Startup manual

Hitachi HX-RIO3 Series user manual

Hitachi

Hitachi HX-RIO3 Series user manual

IFM AL1200 operating instructions

IFM

IFM AL1200 operating instructions

Allen-Bradley D Series installation instructions

Allen-Bradley

Allen-Bradley D Series installation instructions

Allen-Bradley 1794-OF8IH installation instructions

Allen-Bradley

Allen-Bradley 1794-OF8IH installation instructions

Allen-Bradley SLC 500 1746-FIO4I user manual

Allen-Bradley

Allen-Bradley SLC 500 1746-FIO4I user manual

WAGO I/O-SYSTEM 750 manual

WAGO

WAGO I/O-SYSTEM 750 manual

System Sensor M201E installation instructions

System Sensor

System Sensor M201E installation instructions

M-system R7D-YV2A instruction manual

M-system

M-system R7D-YV2A instruction manual

NTP Technology Penta 721 digital I/O installation guide

NTP Technology

NTP Technology Penta 721 digital I/O installation guide

Bosch B208 user manual

Bosch

Bosch B208 user manual

Acces I/O products MPCIE-ISODIO-16 Hardware manual

Acces I/O products

Acces I/O products MPCIE-ISODIO-16 Hardware manual

ExpertDAQ EX-9017F Operation manual

ExpertDAQ

ExpertDAQ EX-9017F Operation manual

SeaLevel SeaI/O-580E user manual

SeaLevel

SeaLevel SeaI/O-580E user manual

Technosoft iPOS360x MX Technical reference

Technosoft

Technosoft iPOS360x MX Technical reference

National Instruments 776570-00 user manual

National Instruments

National Instruments 776570-00 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Copyright © 2009 ICP DAS Co., Ltd.All Rights Reserved. E-mail: service@icpdas.com
tM-R5 Quick Start
1
Quick Start
for tM-R5
September 2014, Version 1.1
Congratulations on purchasing the tM-R5 the most popular automation solution for
remote monitoring and control applications. This Quick Start will provide information
needed to get started with the tM-R5. Please also consult the User Manual for
detailed information on the setup and use of the tM-R5.
In addition to this guide, the shipping box includes the following items:
tM-R5
ICP DAS Website
http://www.icpdas.com/
All manuals and user guides at all-guides.com
Copyright © 2009 ICP DAS Co., Ltd.All Rights Reserved. E-mail: service@icpdas.com
tM-R5 Quick Start
2
1
----------------------------------------------------------------------------------
Understanding the Hardware Specifications
and Wiring Diagrams
Before installing the hardware, you should have a basic understanding of hardware
specification and the wiring diagrams.
System Specifications:
All manuals and user guides at all-guides.com
Copyright © 2009 ICP DAS Co., Ltd.All Rights Reserved. E-mail: service@icpdas.com
tM-R5 Quick Start
3
I/O Specifications:
Wire Connection:
All manuals and user guides at all-guides.com
Copyright © 2009 ICP DAS Co., Ltd.All Rights Reserved. E-mail: service@icpdas.com
tM-R5 Quick Start
4
Pin Assignment:
Make sure the switch placed in the
“Init” position.
2
--------------------------------------------
Booting the tM-R5 in Init
Mode
All manuals and user guides at all-guides.com
Copyright © 2009 ICP DAS Co., Ltd.All Rights Reserved. E-mail: service@icpdas.com
tM-R5 Quick Start
5
3
----------------------------------------------------------------------------------
Connecting to the PC and the Power Supply
The tM-Series series is equipped with an RS-485 port
for connection to a 232/USB converter to PC
Connect to the PC
using an RS-485 Converter
Connect to PC
using a USB Converter
I
-
7520
Power Supply
RS
-
232
RS
-
485
PC
t
M
-
Series
Power Supply
USB
RS
-
485
I
-
7561
PC
tM
-
Series
All manuals and user guides at all-guides.com
Copyright © 2009 ICP DAS Co., Ltd.All Rights Reserved. E-mail: service@icpdas.com
tM-R5 Quick Start
6
The DCON Utility is an easy-to-use tool designed to enable simple configuration of I/O
modules that use the DCON protocol.
The DCON Utility can be obtained from the companion from the ICPDAS
FTP site:http://ftp.icpdas.com/pub/cd/8000cd/napdos/driver/dcon_utility/
After the installation has
been completed, there will be a
new shortcut to the DCON Utility on
the desktop.
The tM-Series is an I/O module based on the DCON protocol, meaning that you can use
the DCON Utility to easily initialize it.
4
---------------------------------------------------------------------------------
Installing the DCON Utility
5
----------------------------------------------------------------------------------
Using the DCON Utility to Initialize the
tM-Series Module
Step 1: Locate the DCON Utility
Step 2: Follow the prompts to complete the installation
All manuals and user guides at all-guides.com
Copyright © 2009 ICP DAS Co., Ltd.All Rights Reserved. E-mail: service@icpdas.com
tM-R5 Quick Start
7
Double-click the DCON Utility
shortcut on your desktop.
Click the “COM Port” option from the menu and a dialog box will be displayed that will allow
you to set the communication parameters as described in the table below.
Communication
parameter INIT Mode
Address 00
Baud Rate 9600
Protocol DCON
Checksum Disabled
Parity N,8,1
Step 1: Run the DCON Utility
Step 2: Use the COM1 port to communicate with the tM-Series
All manuals and user guides at all-guides.com
Copyright © 2009 ICP DAS Co., Ltd.All Rights Reserved. E-mail: service@icpdas.com
tM-R5 Quick Start
8
Click “Start Search” button from the toolbox to search for the tM-Series module.
After the tM-Series module is displayed in the list, click “Stop Search” button.
After clicking on the name of the module in the list, a dialog box will be displayed.
Start Search
Stop Search
Step 3: Search for the tM-Series module
Step 4: Connect to the tM-Series
All manuals and user guides at all-guides.com
Copyright © 2009 ICP DAS Co., Ltd.All Rights Reserved. E-mail: service@icpdas.com
tM-R5 Quick Start
9
Set the “Address” field in the dialog box to 1 and then click “Setting” button to save the
settings.
Make sure the INIT switch is placed in the“RUN” position.
7
----------------------------------------------------------------------------------
Starting the Module Operation
After rebooting the tM-Series module, search for the module to make sure the settings
have been changed. You can double click on the name of the module in the list to open
the configuration dialog box.
6
--------------------------------------------
--------------------------------------
Rebooting the tM-Series Module in RUN Mode
Step 5: Initialize the tM-Series module
All manuals and user guides at all-guides.com
Copyright © 2009 ICP DAS Co., Ltd.All Rights Reserved. E-mail: service@icpdas.com
tM-R5 Quick Start
10
Address Description Attribute
40481 Firmware version (low word) R
40482 Firmware version (high word) R
40483 Module name (low word) R
40484 Module name (high word) R
40485 Module address, valid range: 1 ~ 247 R/W
40486 Bits 5:0
Baud rate, valid range: 3 ~ 10
Bits 7:6
00: no parity, 1 stop bit
01: no parity, 2 stop bit
10: even parity, 1 stop bit
11: odd parity, 1 stop bit
R/W
40488 Modbus response delay time in ms, valid range: 0 ~ 30
R/W
40489 Host watchdog timeout value, 0 ~ 255, in 0.1s R/W
40492 Host watchdog timeout count, write 0 to clear R/W
10073 ~ 10077 High latched values of DO R
10105 ~ 10109 Low latched values of DO R
00001 ~ 00005 Digital output value of channel 0 ~ 4 R/W
00129 ~ 00133 Safe value of digital output channel 0 ~ 4 R/W
00161 ~ 00165 Power on value of digital output channel 0 ~ 4 R/W
00257 Protocol selection, 0: DCON, 1: Modbus R/W
00258 1: Modbus ASCII, 0: Modbus RTU R/W
00260 Modbus host watchdog mode
0: same as I-7000
1: can use AO and DO command to clear host
watchdog timeout status
R/W
00261 1: enable, 0: disable host watchdog R/W
00264 Write 1 to clear latched DIO W
00266 DO active state, 0: normal, 1:inverse R/W
00270 Host watchdog timeout status, write 1 to clear host
watchdog timeout status R/W
00273 Reset status, 1: first read after powered on, 0: not the
first read after powered on R
8
---------------------------------------------------------------------------------
Modbus Address Mapping
All manuals and user guides at all-guides.com