S Installation Instructions Combination Units I
Temperature Rise Check
NOTE: Air temperature rise is the temperature difference be-
tween supply and return air. With a properly designed distribution
system, the proper amount of temperature rise will normally be
obtained when the unit is operating at rated input with the recom-
mended blower speed.
2. The temperature rise must be within the specifica-
tions marked on the unit rating plate.
NOTE: The maximum outlet air setting for all models is 175°F.
4. Adjust the thermostat setting below room tempera-
ture.
Pilot and main burners and combustion air blower should
go OFF
The circulating air blower should continue to run for 60,
100, 140 or 180 seconds. This time is adjustable.
To check the temperature rise through the unit, place
thermometers in the supply and return air ducts as
close to the unit as possible,
Open ALL registers and duct dampers. Operate unit AT
LEAST 15 minutes before taking readings.
5. Set thermostat Heat-Cool selector to OFE
Cooling
1. Turn electric power OFF
2. Set thermostat Heat-Cool select to COOL.
Ifthe correct amount of temperature rise is not obtained when op-
erating on the recommended blower speed, it may be necessary
to change the blower speed. A faster blower speed will decrease
the temperature rise. A slower blower speed wil! increase the tem-
perature rise.
NOTE: The blower speed MUST be set to give the correct air tem-
perature rise through the furnace as marked on the rating plate.
3, After 15 minutes of operation check the limit control
function by blocking the return air grille(s),
After several minutes the main burners and pilot should go
OFF The circulating air blower should continue to run.
Remove air restrictions. Pilot and main burners should
relight after a cool down period of a few minutes.
3.
4.
Adjust thermostat setting to below room temperature.
Turn power ON, for approximately one minute, then OFF
During power application check the following:
a. Contactor - Contacts Closing
b. Compressor - ON
c. Condenser fan motor - ON
d. Circulating Air Blower - ON after a 30
second delay
Turn power OFF, check the following:
a. Contactor contacts opening.
b. Compressor - OFF
c. Condenser fan motor - OFF
d. Circulating blower - OFF after a 30 second
delay.
9. Operation
Electrical shock hazard.
Turn off electric power supply at disconnect switch or
service panel before removing any access or service
panel from unit.
Failure to follow this warning can result in property
damage, personal injury, and/or death.
Controls and Features
Cooling Time Delay Relay (Not All Models)
A cooling time delay relay is used on the evaporator blower motor
to increase efficiency (SEER). On a call for cooling, the blower
motor starting is delayed for 30 seconds. Also, after the thermo-
stat is satisfied, the blower motor continues to run for 30 seconds
after the condenser fan motor and compressor have shut off.
Scroll Anti-cycle Timer (Not All Models)
Single phase scroll compressor equipped units are equipped with
an anti-cycle device which delays start of the compressor in the
event of a power interruption. This feature is to allow pressure
equalization throughout the system and to prevent possible re-
verse rotation of the scroll compressor. Three phase units do not
require this device.
High and Low Pressure Switches (Not All Models)
High and low pressure switches are provided on these units which
will shut down the system when high pressures exceed 420 psi
and low system pressures fall below 27 psi. The switches auto-
matically reset after afault. They are accessed through the com-
pressor compartment access panel.
Fan Cycle Pressure Switch Port (optional)
If your unit will be operated in low ambient conditions (below 40 °
F) and you elect to install a low ambient fan cycle control, you can
find the low ambient pressure port located on the discharge line
just inside the compressor compartment panel opening.
Freeze Protection Thermostat (Not All Models)
The freeze protection thermostat is located on the evaporator coil
bends on the burner side ofthe unit. It is designed to shut down the
cooling circuit if the evaporator coil temperaturefalls below 35 ° R
Filter Drier
A liquid line filter drier is located inside the compressor compart-
ment access panel opening. Be certain to replace filter driers with
the correct size and type as found in the Technical Data Sheets
available from your dealer.
E_I 50901 110202