ICS Lifeline M95-600 Series User manual

INSTRUMENTATION AND CONTROL SYSTEMS, INC.
UNINTERRUPTIBLE POWER SYSTEM
MODEL M95-600 SERIES
PART NO. 9300057
DRAWING NO. 8060180
ISSUED: 5- 1-07
REV B: RELEASED
INSTRUMENTATION AND CONTROL SYSTEMS INC.
5 0 WEST INTERSTATE ROAD ADDISON, ILLINOIS 60101 USA
TEL (630) 543-6 00 FAX 630-543-6 44
1

1. INTRODUCTION
1.1 System Description
Thank you for purchasing one of the LIFELINE series of Uninterruptible Power
Systems manufactured by Instrumentation Control Systems Inc., Electropac
Division. The particular UPS described by this manual, part number 9300057,
represents the latest in efficient, clean and highly reliable source of AC power.
In the line regulated mode, the system provides regulated AC output with a
maximum of efficiency and minimum of noise. Coupled with the battery, the
UPS gives the user protection from disruption of power to the critical
equipment.
1. Manual Description
The purpose of this manual is to provide the user with installation, operation
and maintenance of the LIFELINE Uninterruptible Power System, part number
9300057. This manual should be read thoroughly to familiarize personnel
before the system is operating. If any situation develops that is different from
what is described herein, contact the factory for further assistance.
1.3 Proprietary Notice
This equipment was designed and manufactured under several patents owned
by ICS, Inc. The user of these patented circuits or reproductions of the
drawings, schematics, etc. may not occur except by written permission from
ICS, Inc.
1.4 HAZARD CAUTION
The normal operating voltages contained within the cabinet are as much as
600 volts. It is extremely important that caution be exercised when working on
this equipment.
When connecting DC terminals to the external batteries, it is very important that
correct polarity be observed.
. Standard Installation
.1 Unpacking
Carefully unpack the unit and remove any packing materials. Inspect the
cabinet and the front panel controls. Remove the two screws near the right
edge of the front panel and open the door of the unit . Inspect the interior of the
unit for possible damage or dislodging of components. Retain packing
materials to return unit if operational problems occur.
2

. Mounting
This unit is designed for either shelf or wall mounting. A minimum of 6” per side
and 2” above the cabinet is necessary for the cooling and mounting purposes.
Consideration should be given to the proximity of the incoming and output
power.
Caution: Due to the weight of this system (up to 150 lb.) , mounting securely is
extremely important. Standard drywall or bookshelf mounting is not
acceptable. Mounting to the wall studs is required.
External batteries (on a rack or in a cabinet) should be located in an equipment
room per local requirements.
.3 Wiring
Open the door of the unit after removing the two fastening screws near the right
edge of the door. Four dual concentric knockouts are located on the left side of
the cabinet to install 1/2” or 3/4” conduit to the unit. Run 18 gauge (minimum)
wires through the conduit and connect per Installation Wiring Diagram No.
8022072 at the rear of this manual. The input/output terminal strip TS3 is
located on the left side of the cabinet above the knockouts.
This UPS is provided with external batteries which must be connected to the
unit. Confirm that all sources of power are off and that the battery circuit
breaker on the left side of the cabinet is off ( handle in the down position).
Loosen the outside caps on the plastic feedthroughs located on the left side of
the cabinet and pass the two battery wires (marked POS+ and NEG-) through
the feedthroughs. Connect the wires to the terminal board on the inside rear of
the cabinet, matching the wire markings to the terminals. Close the cabinet
door and replace the two screws near the right hand edge of the front panel.
With the battery system wired ( four batteries in series mounted on an open
rack, or in a prewired battery cabinet), connect the two battery wires from the
UPS to the battery system observing the proper polarities.
WARNING: The battery system is a hazardous source of power. Make all
connections first before connecting the equipment to the batteries. Connect the
wires at the battery terminal last. Improper polarities will damage the UPS
and/or batteries.
.4 Startup Procedure
2.4.1 With the battery circuit breaker off ( handle in the down position) and
the load(s) disconnected, apply AC input power.
3

2.4.2 After the UPS starts up, verify that all three LED indicators on the front
panel are illuminated.
2.4.3 Turn on the battery circuit breaker (handle in the up position). The
characteristic sound of the main transformer in the UPS may change somewhat
due to charging of the battery system.
2.4.4 Connect the load(s) to the UPS output.
.5 Continuous Operation
It is recommended that the unit be left on all the time. This will insure that the
battery remain charged to it full capacity. The unit is designed to operate 24
hours per day and is not required that it be turned off during the week-ends
.6 Shut Down Procedure
2.6.1 Disconnect the load from the UPS.
2.6.2 Disconnect the commercial AC source from the UPS.
2.6.3 Press the BATTERY OFF push-button switch on the front panel to turn off
the UPS.
2.6.4 Turn off the BATTERY CIRCUIT BREAKER (handle in the down
position) to prevent further discharge of the battery.
2.6.5 If servicing of the UPS or the battery is required, disconnect the battery
cable at the battery before performing any maintenance.
3. DESCRIPTION OF OPERATION
3.1 General Operation
Figures 3.1 and 3.2 illustrate the operation of this system. Please note that
under normal operation (Figure 3.1), the AC input operates through the inverter
and is then further regulated and filtered. The output of the unit is a very clean
sinewave with an output voltage that is regulated to within + 3% with an input
voltage swing of + 10% and -15%. During this operation, a special inverter
circuit provides trickle charge to the battery.
During standby operation when the commercial line is not present, the inverter
is switched totally to the battery which converts the battery’s DC voltage to AC
and supplies power to the regulator/filter. The output is then the same as if the
line were present. Transfer from a charger to inverter is done within
microseconds and no power interruption occurs at the output.
4

3. Operation From AC Input
When the line power is normal, the static switch connects the line to the load
through an inverter which filters and regulates the power to the load. The
inverter also charges the battery.
It is also possible to operate the system without the use of the battery. In this
case, the unit provides excellent regulation and filtering of the incoming AC line
but without battery backup capability.
COMMERCIAL
AC LINE TRANSFORMER LOAD
PRESENT
STATIC SWITCH
CLOSED
BATTERY CHARGER
Figure 3.1 Commercial Power On
3.3 Operation From Battery
During the loss of commercial AC power, the battery provides DC current to
the inverter which then converts it to reliable, accurate AC power. A precision
frequency standard provides a highly stable frequency which is closely
regulated to the nominal output frequency.
In the event of a power interruption, the static switch disconnects the
commercial line from the inverter. The battery supplies power to the load via
the inverter.
COMMERCIAL
AC LINE TRANSFORMER LOAD
ABSENT
STATIC SWITCH
OPEN
BATTERY INVERTER
Figure 3.2 Commercial Power Off
5

4. Maintenance
CAUTION: Disconnect AC DC power before performing any maintenance.
The unit is basically free from any maintenance except for keeping it clean and dirt-
free. If the unit is mounted in a dirty environment it may well be necessary to vacuum
it occasionally to keep it free from lint and dirt particles. The equipment is not
designed to be mounted in an area of highly corrosive fumes or conductive particles.
Conductive dirt particles in the atmosphere will definitely cause malfunction of the unit.
4.1 Adjustments
The equipment is properly adjusted and fully tested by the factory. However, if
any adjustments need to be made, it is probably due to component changes in
the field over a long period of time. Under those circumstances it is important
that the user contact the factory for further instructions. The attached table can
be used as a basic trouble shooting guide. It is important to note however that
this equipment is fairly sophisticated and service should not be attempted by
inexperienced personnel. It is important that accurate DC and AC meters be
available to properly measure DC operating battery voltage and AC input and
output voltage.
4. Troubleshooting
Table 4.1 presents a basic trouble shooting guide. Replacement of fuses must
only be accomplished after removing the input power to the unit and pressing
the battery OFF button.
6

TABLE 4.1: BASIC TROUBLESHOOTING GUIDE
PROBLEM
CHECK OR
REPLACE F1
CHECK BATTERY
CIRCUIT BREAKER
REPLACE PRINTED
CIRCUIT BOARD OTHER
No AC output when
commercial power
is present
X
No AC output when
commercial power
is not present
X Check Battery
Battery does not
charge X X Check Battery
Output voltage low X Reduce Load
Output frequency
low or high X
“AC Input” light off X
“Battery” light off X
“AC Output” light off X
“Battery ON/RESET”
pushbutton does not
start inverter
X X Check Battery
7

5. Warranty
Except as hereinafter in this Section set forth, all new apparatus sold by ICS Inc. is
warranted for a period of one year from the date of shipment to the Buyer, to be free
from defect in material and workmanship. If the buyer within this period gives ICS Inc.
written notice of any alleged defect in any such apparatus and provides an opportunity
to perform any appropriate test thereon ( the time and place to be mutually agreed
upon and ICS Inc. at its option, to be present thereat) and if the apparatus is found not
to be in conformity with this warranty, ICS Inc. will, at its option, and expense either
repair the same or supply a replacement therefore. The Buyer will pay all return
transportation charges in connection with same.
The return of equipment to ICS Inc. must be authorized in advance by ICS Customer
Service personnel. Contact the Service Department for assignment of an RMA
(Return Material Authorization) number which must be marked on the outside of the
shipping container. Users of equipment returned to ICS Inc. which is found to be
operating properly will be assessed recalibration and inspection charges as well as all
shipping cost.
On repaired apparatus, the warranty shall be as for new apparatus except that it shall
only apply to the parts repaired or replaced by ICS Inc. No separate warranty shall
apply to repaired apparatus as a whole or to parts not repaired by ICS Inc.
ICS Inc. reserves the right to make changes, additions and / or improvements in its
product previously sold.
Due to nature of certain equipment installation, it could be impractical to remove ICS
Inc.’s portion of the equipment from the customer ‘s premises to ICS Inc.’s facility. In
such case and at the request of the Buyer, ICS Inc. will perform such services as can
be satisfactorily rendered at the Buyer’s facility. The Buyer will be charged for travel
and living expenses incidental to the service call.
However, no charges will be made for actual service time or any parts that may be
required if this warranty is applicable.
The warranties of ICS Inc. on all apparatus do not cover, and ICS Inc. makes no
warranty with respect to:
a) Failures not reported to ICS Ins. within the warranty period above specified.
b) Failure or damage due to misapplication, abuse, improper installation or abnormal
conditions to temperature, dirt or corrosive matter.
c) Failure due to operation, either intentional or otherwise above rated capacities or in
an otherwise improper matter.
8

d) Apparatus which has been in any way tampered with or altered by anyone other
that an authorized representative of ICS, Inc..
e) Apparatus damaged in shipment or otherwise without the fault of ICS, Inc.
f) Losses, costs, expenses, liabilities and damages (including loss of use or profits, all
liabilities of the Buyer to its customers or third persons and other consequential
damages), whether direct or indirect, and whether or not resulting from or contributed
to by the default or negligence of ICS, Inc. its agent , employees and sub-contractors,
which might be claimed as a result of the use or failure of the apparatus delivered.
There is no further warranty, either express or implied, in connection with the design,
sale or use of any ICS, Inc.’s products except as to title; and ICS, Inc.’s liability to its
warranty shall in no event exceed the cost of correcting defects in the apparatus sold.
9

6. TECHNICAL INFORMATION FOR MODEL 9300057 UPS
6.1 Specifications
Input Power DC: 48VDC nominal, 55AH sealed lead-acid battery
Charging Current: 2ADC
Input Power AC: 120VAC, +10/-15%, 60Hz, 8AAC nominal, single phase
Rated Output Power: 120VAC, 60Hz, 5.0AAC (600VA/W), single phase
Load Power Factor: 0.8 to 1.0
Output Voltage Regulation: +/-3%
Output Waveform: Sinusoidal with 5% maximum total harmonic distortion
Efficiency: Up to 85% at nominal line, battery voltage and full load
Battery Backup Times:
4 Hours at 2.5AAC Output
2 Hours at 5.0AAC Output
Operating Temperature: 10 to 40 degrees C
Operating Humidity: 0 to 85% non-condensing
Storage Temperature: 0 to 65 degrees C
Input/Output Connections: Terminal strip with provisions for conduit entry
6. Controls
Battery Circuit Breaker: Connects/disconnects battery to/from UPS.
Battery On/Reset Switch: Starts UPS from battery or restarts UPS after
low battery shutdown when AC input power not present.
Battery Off Switch: Shuts down UPS while operating from battery.
6.3 Indicators
AC Input LED: Indicates AC input power is present.
Battery LED: Indicates DC power is present.
AC Output LED: Indicates AC output power is available.
6.4 UL Certifications
Product Name: Fire Alarm Power Supply Unit
Category Control Number: UTRZ
Standard: UL1481Listing Mark Control No.: 2N09
10

BATTERY WIRES 8GA AWG MIN. ALL OTHER WIRES 18GA AWG MIN.
* TOTAL UPS LOAD WITH BATTERY BACKUP: 5AAC MAX.
HOURS BACKUP TIME AT 5.0 AAC OUTPUT
4 HOURS BACKUP TIME AT .5AAC OUTPUT
** CONNECT TO EARTH GROUND
11

CABINET DIMENSIONS
12

NOTES:
1. DIMENSIONS ARE FOR REFERENCE ONLY
2. DESCRIPTION: UNINTERRUPTIBLE POWER SUPPLY – LIFELINE SERIES
3. SPECIFICATIONS:
WEIGHT: 120 LBS. PLUS EXTERNAL BATTERIES AND RACK
INPUT POWER DC: 48VDC NOMINAL, 55AH BATTERY
INPUT POWER AC, 60HZ, 8AAC, NOMINAL
REGULATED OUTPUT POWER: 120VAC, 60HZ, 5.0AAC
OUTPUT WAVE FORM: SINUSOIDAL 5% MAX TOTAL HARMONIC DISTORTION
CHARGING CURRENT: 2ADC
EFFICIENCY: UP TO 85% NOMINAL LINE, BATTERY VOLTAGE AND FULL LOAD
INPUT/OUTPUT CONNECTIONS: NUMBERED 18 POSITION TERMINAL STRIP
INPUT/OUTPUT CONNECTION ACCESS: 4 DUAL-CONCENTRIC CONDUIT HOLES
OPERATING TEMPERATURE: 10 – 40 DEGREES C
OPERATING HUMIDITY: 0 – 85% NON-CONDENSING
STORAGE TEMPERATURE: 0 – 65 DEGREES C
4. CONTROLS:
BATTERY CIRCUIT BREAKER
INVERTER ON PUSHBUTTON SWITCH
INVERTER OFF PUSHBUTTON SWITCH
INVERTER CAN BE SWITCHED ON AND OFF WHEN INPUT 120VAC POWER IS NOT PRESENT.
WHEN INPUT 120VAC POWER IS PRESENT, OUTPUT 120VAC POWER IS ALWAYS PRESENT.
5. INDICATORS (ALL GREEN):
AC INPUT – INDICATES AC INPUT POWER IS PRESENT
BATTERY – INDICATES DC POWER IS PRESENT (FROM BATTERY OR CHARGER)
AC OUTPUT – INDICATES AC OUTPUT POWER IS AVAILABLE
6. BATTERY BACKUP TIMES:
4 HOURS AT 2.5AAC POWER OUTPUT
2 HOURS AT 5.AAC POWER OUTPUT
13

OPERATING INSTRUCTIONS FOR UPS PART NO. 9300057
DRAWING N0. 8060181
ISSUED 06/16/94
REV. A: RELEASED
Mount this sheet in a frame and locate it adjacent to the unit. Refer to Drawing/Manual No. 8060180, issued
06/16/94 for complete information.
1. Ratings:
Input AC Power: 120VAC, 60Hz., 8AAC nominal
Input DC Power: 48VDC, 55AH Battery
Output AC Power:120VAC, 60Hz., 5AAC
Charging Current: 2ADC
2. Intended Load: Fire Protection Signaling Systems
3. Startup Procedure
3.1 With the battery circuit breaker off (handle in down position) and the load(s) disconnected, apply AC
input power.
3.2 After UPS starts up, verify that all three LED indicators on front panel are illuminated.
3.3 Turn on battery circuit breaker (handle up). The characteristic sound of the main transformer in the
UPS may change somewhat due to charging of the battery system.
3.4 Connect the load(s) to the UPS output.
4. Shutdown Procedure
4.1 Disconnect the load(s) from the UPS.
4.2 Disconnect the commercial AC power source from the unit.
4.3 Press the BATTERY OFF pushbutton switch on the front panel to turn off the UPS.
4.4 Turn off the battery circuit breaker (handle in the down position) to prevent further discharge of the
battery.
4.5 If further servicing of the UPS or battery system is required, disconnect the battery cables at the
battery before performing any maintenance.
5. Local Service Representative:
Name:
Address:
TEL: FAX:
INSTRUMENTATION & CONTROL SYSTEMS INC.
5 0 WEST INTERSTATE ROAD ADDISON, ILLINOIS 60101 USA
TEL (630) 543-6 00 FAX (630) 543-6 44
14
This manual suits for next models
1
Table of contents
Popular UPS manuals by other brands

Eaton
Eaton Powerware 9395 550 kVA MBM Installation and operation manual

PowerShield
PowerShield PSDCMin12 quick guide

Emerson
Emerson Liebert NX Product specification/installation sheet

CertaUPS
CertaUPS C200-1500 user manual

Best Power
Best Power Fortress LI520 user guide

CyberPower
CyberPower OL6000ERT3UDM user manual

PowerStar
PowerStar PS502-8 user guide

CyberPower
CyberPower CyberShield CSN30U12V user manual

Vertiv
Vertiv Liebert ITA2-08KRT208 user manual

Middle Atlantic Products
Middle Atlantic Products UPS-S1500R user manual

socomec
socomec Green Power 2.0 60 Installation and operating manual

GE
GE Digital Energy LP 33 Series operating manual