Ideal Heating ECOMOD AHP60 50 kW User manual

INSTALLATION AND
SERVICING
ECOMOD AHP60
50 and 70 kW
Air/water monobloc heat pump
When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal.
For the very latest copy of literature for specification and maintenance practices visit our website www.idealcommercialboilers.com
where you can download the relevant information in PDF format.
September 2022
UIN 00U07352260-A


01.07.2022 3 / 78
AHP60-50/70 - Installation, Use and Maintenance
CONTENTS
1.
REGULATIONS, RECOMMENDATIONS AND WARNINGS..............................................................5
1.1. Applicable regulations and standards ........................................................................................................... 5
1.2. Recommendations and warnings................................................................................................................. 5
2. DESCRIPTION OF THE EQUIPMENT ..............................................................................15
2.1. Designations and scope.............................................................................................................................. 15
2.2. Packaging ................................................................................................................................................... 15
2.3.Denitions ................................................................................................................................................... 15
2.4. Technical data ............................................................................................................................................. 16
2.5. Description .................................................................................................................................................. 20
2.6. Operating principle ...................................................................................................................................... 22
3. INSTALLATION ...................................................................................................................24
3.1. Lifting and handling ..................................................................................................................................... 24
3.2. Installation ................................................................................................................................................... 25
3.3. Installing the outdoor unit ............................................................................................................................ 25
3.4. Installing the control unit ............................................................................................................................. 32
3.5. Position of the centre of gravity and the vibration shock absorbers............................................................ 32
3.6. Hydraulic connections ................................................................................................................................. 33
3.7. Electrical connections ................................................................................................................................. 39
4. PRE-REQUISITES BEFORE COMMISSIONING .............................................................44
4.1.Vericationbeforeswitchingon................................................................................................................... 44
4.2. Switching On ............................................................................................................................................... 45
4.3. Commissioning ........................................................................................................................................... 45
4.4.Primaryloopowrate/cascadebalanceadjustment................................................................................... 45
4.5. Operating
diagram .......................................................................................................................................46
4.6. ECOMOD user interface navigation............................................................................................................ 48
5. CONTROL INTERFACE .....................................................................................................49
5.1. User interface.............................................................................................................................................. 49
5.2. “SET” setpoint menu (For manual operation only) ................................................................50
5.3. Sensor menu [TP] ....................................................................................................................................... 51
5.4. Error menu [Err] .......................................................................................................................................... 51
5.5. Operating hours menu [OHR] ..................................................................................................................... 51
5.6. Parameter menu [Par]................................................................................................................................. 51
6. TROUBLESHOOTING .......................................................................................................52
6.1. Troubleshooting of failures without error code ............................................................................................ 52
6.2. Error codes and diagnostic assistance ....................................................................................................... 52
6.3. Inverter board errors ................................................................................................................................... 59
6.4. Ohmic values of the various sensors .......................................................................................................... 61
7. MAINTENANCE OF THE OUTDOOR UNIT......................................................................62
7.1. Drainage of the outdoor unit on the water side ........................................................................................... 62
7.2. Filling the outdoor unit................................................................................................................................. 62
7.3. Prolonged shutdown ................................................................................................................................... 62
7.4. Periodic checks ........................................................................................................................................... 62

4 / 78 00U07352260-A_EN 01.07.2022 5 / 78
7.5. Cleaning the external surfaces.................................................................................................................... 65
7.6. Maintenance of the outdoor unit.................................................................................................................. 65
7.7. Residual safety risks ................................................................................................................................... 66
7.8. Heavy maintenance work............................................................................................................................ 67
7.9. “Maintenance” check list ............................................................................................................................. 68
8. END OF PRODUCT LIFE- ..................................................................................................74
9. ANNEX A - DATA FOR PRODUCTS ≤ 70KW .........................................................76
■Symbols used in this document
INFORMATION: This symbol draws attention to comments.
CAUTION: Failure to comply with these instructions may cause damage to the
installationortootherobjects.
WARNING: Failure to comply with these instructions may cause electrocution.
WARNING: Failuretocomplywiththeseinstructionsmaycauseinjuryandserious
damage to property.

4 / 78 00U07352260-A_EN 01.07.2022 5 / 78
1. REGULATIONS, RECOMMENDATIONS AND WARNINGS
1.1. Applicable regulations and standards
This outdoor heat pump has been designed in accordance with current regulations and
must be used accordingly. See the list of standards on the back cover.
This device must be transported in compliance with the Local Laws.
This device and its refrigerant R32 must be handled in compliance with the application
ordersoftheFGasregulations.SpecicguidelinesrelatedtothepresenceofFluorine
inthecompositionoftheR32uid arespecied intheEuropeanUnionregulationn°
517/2014.
It must be installed in compliance with local or national regulations such as the RSD (Local
sanitary Regulations), and in accordance with standard EN 378-3: 2016 concerning the
installation of heat pumps.
The electrical connection must be made in compliance with the Current I.E.E. (BS7671)
Wiring Regulations standard.
The hydraulic connection must be made in compliance with the Local Laws
Regulations covering Maintenance
The appliance must be installed and maintained by an approved professional in
accordance with the prevailing regulations and code of practice, in particular:
- The legislation on the handling of refrigerants
- Current I.E.E. (BS7671) Wiring Regulations
CAUTION:
This device must be maintained by qualied personnel with a certicate of capacity
for the handling of refrigerants.
1.2. Recommendations and warnings
1.2.1. Transport and storage
The outdoor appliance and the hydraulic station:
- must be stored in a place where the temperature is between -10°Cand+50°Cwith
a relative humidity between 5 and 95%.
- must not be stacked,
- must be protected from humidity.
Transport and storage must comply with the national standards in force. In particular,
according to the provisions of the ADR (see below), the maximum total quantity per
transportunitforammablegasesis333kg(netmass).
Handling
The outdoor unit must not be in a horizontal position during transport.
Transport in a horizontal position may damage the appliance by moving the refrigerant
and damaging the compressor's suspensions.
Damage caused by transportation in a horizontal position is not covered by the warranty.
If necessary, the outdoor unit may be tilted during manual handling (to go through a door
or use a staircase). This operation must be conducted very carefully and the appliance
must be immediately restored to the upright position.

6 / 78 00U07352260-A_EN 01.07.2022 7 / 78
1.2.2. Unpacking the appliance
Acceptance
With the carrier present, carefully check the general appearance of the packaging and the
appliances. Check that the outdoor appliance has not been placed in a horizontal position.
In the event of disagreement, write to the carrier within 48 hours mentioning all reserves
and send a copy of this letter to the After Sales Department.
Before unpacking the appliance, check that there are no refrigerant leaks using a suitable
detector. Check that there are no ignition sources near the unit.
Smoking is forbidden near to the unit.
1.2.3. Safety recommendations related to the presence of the R32 refrigerant
The handling and installation of this outdoor appliance must only be performed by
personnelthatare duly trained, qualiedandauthorised to carry outtheseoperations,
according to the laws, directives and standards applicable in each country.
TheEN378:2016standarddenestheframeworkofrequirementstobemettomanage
each potential risk at each stage of the machine's life cycle. This standard was also used
to design this machine.
In the absence of local building codes or safety standards, the installation and maintenance
of the machine may follow the elements outlined in this standard; in particular, it is the
responsibility of the installer and personnel performing operations on this machine to
perform a risk analysis prior to any installation and work on the machine.
The elements indicated below are not exhaustive given the diversity of the possible
installations and interventions; they cannot be considered as an undertaking as
to the responsibility of the Ideal Heating. These elements cannot replace a risk
analysis, which remains the responsibility of the installer and the personnel working
on the machines.
Designation R32.
INDICATION OF DANGERS
Main dangers: Asphyxia.
Specicdangers: The rapidity of evaporation can cause burns.
EMERGENCY MEASURES
General information Do not give anything to persons who have fainted.
Inhalation:
Take the person to fresh air.
Useoxygenorarticialrespirationifrequired.
Do not administer adrenaline or similar substances.
Contact with the eyes: Rinse thoroughly with water for at least 15 minutes and seek
medical attention.
Contact with the skin:
Rinse thoroughly with water for at least 15 minutes. Apply a sterile
gauze.
Remove contaminated clothing immediately.
FIRE PREVENTION MEASURES
Extinguishers: Water spray, dry powder.
Specicdangers: Rupture or explosion of the recipient.
Specicmethods:
Cool down the recipients by spraying with water from a safe
position. If possible, stop the product from leaking. If possible, use
a water spray to hose down the smoke. Move the recipients well
clearoftherezoneifpossiblewithouttakingrisks.

6 / 78 00U07352260-A_EN 01.07.2022 7 / 78
MEASURES IN THE EVENT OF AN ACCIDENTAL LEAK
Individual precautions:
Use personal protection equipment.
Evacuate the personnel to safe areas.
Eliminate ignition sources.
Ensure there is adequate ventilation.
Environmental precautions: Try to stop the leak.
Cleaning methods: Ventilate the area.
HANDLING AND STORAGE
Handling:
Technical measures/precautions: Ensure that the premises have adequate air renewal/extraction .
Recommendations for safe use: Do not breathe in the vapours or use aerosols.
Storage
Close tightly and store in a cool, dry, well-ventilated place.
Keep in original recipients. Incompatible products: explosives,
ammablematerials,organicperoxide.
CONTROLLED EXPOSURE/INDIVIDUAL PROTECTION
Control parameters:
DNEL:DerivedNo-Eect-Level(workers)
longterm,systemiceects,inhalation=7035mg/m3.
PNEC:PredictedNoEectConcentration
Water(freshwater)=0.142mg/l
Aquatic,intermittentemissions=1.42mg/l
Sediments,freshwater=0.534mg/kgdryweight
Respiratory protection:
Protection of the eyes:
Not necessary.
Safety glasses.
Protection of the hands: Rubber gloves.
Hygiene measures: Do not smoke!
PHYSICAL AND CHEMICAL PROPERTIES
Colour Colourless.
Smell: Ethereal. Hardly perceptible in low concentrations.
Boiling point: -51.7°Catatm.press.
Flash point: 648°C
Lowerammabilitylevel 13%
Upperammabilitylevel 32%
Relativedensityofgas(air=1) 1.8
Relativedensityofliquid(water=1) 1.1
Solubility in water: 280000 mg/l.
STABILITY AND REACTIVITY
Stability: Stable in normal conditions.
Materials to be avoided:
Hazardous decomposition products
Hazardous:
Air, oxidising agents, humidity.
In normal conditions of storage and use, no hazardous
decomposition product should be generated.

8 / 78 00U07352260-A_EN 01.07.2022 9 / 78
TOXICOLOGICAL INFORMATION
High toxicity:
Localeects:
Long term toxicity:
LD/LC50/inhalation/4hours/rattest=1107000mg/m3.
Noknowneects.
Noknowneects.
ENVIRONMENTAL INFORMATION
Global warming potential
GWP(R744=1): 675
Ozone damage potential ODP
(R11=1):
OftheozoneODP(R11=1):
0
Disposal Considerations: Comply with the supplier’s gas collection programme. Avoid direct
emission into the atmosphere.
■ Specic warnings on the R32 refrigerant
The R32 refrigerant:
- is odourless;
-isslightlyinammable(A2L),butonlyinthepresenceofames;
-Riskofexplosionatairconcentrationsbetweenthelowerandupperammabilitylevelsofthe
uid,seerefrigerantdatasheetabove.
It is essential to follow the following guidelines:
- do not smoke near to the appliance ;
- put up no smoking signs near to the appliance ;
- ensure that it is installed in a well-ventilated area
- do not pierce or burn the appliance ;
-donotpositiontheapplianceneartoignitionsources,suchasnakedames,electricheaters,
etc.;
- any special work or repairs to the appliance must be carried out by specialised technicians or
qualiedpersonnel;
■ R32 refrigerant load
The procedures described below must only be performed by specialised technicians or
qualied personnel:
- ensure that other types de refrigerant do not contaminate the R32;
- keep the gas bottle in a vertical position when loading it;
- put a suitable label on the unit after loading it;
- do not load more refrigerant gas than needed;
- before loading, search for leaks before carrying out an operating test. This operation has two
purposes, to control the quantity of refrigerant loaded and to check the circuit for leaks,
- after the operating test, we recommend carrying out another leak test,
■ Eliminating the R32 refrigerant
Follow the standardised procedures for collecting refrigerants, which may only be carried
out by specialised technicians or qualied personnel, and return it to the supplier.
■ Installation precaution related to the refrigerant
If local construction codes or safety standards don’t exist, the information shown below are
taken from the standard EN378: 2016 may be used for information; they may be used as a guide
for the safe use of machines that use R32 as a refrigerant.
This outdoor unit must not be installed in a place that can the general public or untrained,
qualiedorapprovedpersonscanaccess.
It is designed to be installed outdoors, in open air. A shelter or alcove in which at least one of
the longest walls is open to the outside air by louvers having a free area of 75% and covering

8 / 78 00U07352260-A_EN 01.07.2022 9 / 78
at least 80% of the wall (or the equivalent if more than one wall is open to the outside
air), is considered to be open to the outside air.
It must be located so that no refrigerant leaks can enter the building and/or endanger
people and property. Therefore:
It must not be possible for the refrigerant to spill into a ventilation duct, under
a door, hatch or similar opening in case of a leak. For this reason, the installer
must ensure that there is a distance of at least 1m between the unit and any such
opening. When a shelter is provided for the refrigerant appliance in the open air,
this shelter must be equipped with a natural or forced ventilation device.
For refrigerant appliances which are installed outdoors at a location where a
refrigerant release may stagnate, for example, below ground level, the installation
must meet the requirements relative to gas detection and machine room ventilation.
1.2.4. Recommendations for hydraulic and electrical circuits
■Hydraulic connections
The connection must comply with good engineering practices according to the regulations
in force.
Reminder: Make the assembly seals according to good engineering practices in force
for plumbing work:
- Usesuitablesealsorgaskets(breseals,Orings).
- UseTeonorhemptape.
- Use sealant (synthetic as required).
■ Characteristics of the water for the appliance
To ensure thattheappliance is workingcorrectly, thewatermust be lteredcorrectly
(see the indications at the beginning of this section) and the quantity of dissolved must
be minimised.
Refer to chapter 3.6.4. For further recommendations.
The maximum authorised values are as follows:
Use glycol water if the room where the primary/secondary storage tank(s) is/are installed
is not frost-free; we recommend that this situation be temporary so as not to alter the
system’s
MAXIMUM AUTHORISED PHYSICAL-CHEMICAL CHARACTERISTICS AUTHORISED FOR THE INSTALLATION
WATER
PH 7.5 - 9
Electrical conductivity 100-500μS/cm
Total hardness 8.0-15.1°f
Temperature ˂65°C
Oxygen content ˂0.1ppm
Max. quantity of glycol 40%
Iron (Fe) < 0.3 ppm
Chlorine ions (Cl-) < 50 ppm

10 / 78 00U07352260-A_EN 01.07.2022 11 / 78
Percentage of
glycol Freezing point [°C] Eciency cor-
recon factor
Absorbed power
correcon factor
Water ow rate
correcon factor
Loss of head cor-
recon factor
10% -3.2 0.985 1 1.02 1.08
20% -7.8 0.98 0.99 1.05 1.12
30% -14.1 0.97 0.98 1.10 1.22
40% -22.3 0.965 0.97 1.14 1.25
performancepermanently.Donotforgettoushthesystemoncetheroomisfrost-free.
If glycol water is used, plan an annual control of the glycol quality. Use monopropylene
type glycol only. The recommended concentration should not exceed 40%.
If glycol is not used, trace the pipes electrically outside.
• In certain installations, the presence of dierent metals can cause corrosion
problems; in this case, the formation of metal particles and sludge in the
hydraulic circuit is seen.
- Please refer to the chapter “Treatment of domestic and heating water” in our price
catalogue
• It is also necessary to ensure that the treated water does not become aggressive
for the circuit.
■Electrical connections
Ensure that the general electrical power supply has been cut o before starting any
repair work.
Characteristics of the electrical power supply
Theelectricalinstallationmustbeconductedinaccordancewiththeregulationsineect
and in particular to current I.E.E. (BS7671) Wiring Regulations
Theelectricalinstallationmustbeequippedwithadierentialprotection.
Thisapplianceisdesignedtooperateunderanominalvoltageof400V+/-10%,50Hz.
For installations without neutral, a galvanic isolating transformer must be used that is
earthed on the secondary side.
The electrical connections will only be made when all of the other assembly operations
(attachment, assembly,...) have been carried out.
Never use a socket for the power supply.
CAUTION:
The contract with the energy supplier must cover the maximum electrical requirement of
the installation.
The outdoor unit must be supplied directly (without external switch) by a dedicated line
protected at the start by a dedicated isolator switch. (Seer “Current source” paragraph).

10 / 78 00U07352260-A_EN 01.07.2022 11 / 78
Example of recommended connection diagram (non exhaustive)
TO THE EXPANSION
SYSTEM
COMMAND TO
ELECT. CABINET

12 / 78 00U07352260-A_EN 01.07.2022 13 / 78
1.2.5. General safety rules
Before starting any operation on the units, each operator must be fully familiar with
the operation of the machine and its controls and have read and understood all the
information contained in this manual.
The removal and/or handling of any safety device is strictly prohibited.
Children and unaccompanied disabled people are not allowed to use the device.
It is forbidden to touch the device barefoot and with wet or wet parts of the body.
Any cleaning operation is prohibited when the main switch is in position « ON ».
It is forbidden to pull, unplug or twist the electrical cables coming out of the device, even if it is
disconnected from the power supply.
Itisforbiddentostandonthedevice,tositonitand/ortoputobjectsofanykindonit.
Itisforbiddentosplashthedeviceorprojectwateronit.
It is forbidden to disperse, deposit or leave within the reach of children the packaging material
(cardboard, staples, plastic bags ... etc.) because it can be a potential source of danger.
Any ordinary or extraordinary maintenance operation must be carried out at a standstill, without
power supply.
Do not put your hands or introduce screwdrivers, wrenches or other tools into moving parts.
The machine manager and the maintenance technician must receive the appropriate training
and instruction for their tasks in safe conditions.
Operators should be familiar with personal protective equipment and accident prevention rules
prescribed by national and international laws and standards.
1.2.6. Worker safety
Anywhere the unit is installed, the applicable local laws regarding worker safety and
health must be accurately respected and enforced by each employer. We therefore
recall that:
It is forbidden to handle or replace parts of the machine without the express permission of the
manufacturer. These interventions release the manufacturer from any civil or criminal liability..
The use of components, consumables or spare parts other than those recommended by the
manufacturer and/or mentioned in this manual may constitute a danger to operators and/or
damage the machine.
Theoperator’sworkstationmustbekeptclean,tidyandfreeofobjectswhichmayrestricthis
freedomofmovement.Theworkstationmustbesucientlyilluminatedfortheperformanceof
theplannedoperations.Insucientorexcessivelightingcanpresentrisks.
Ensure the appropriate ventilation of the work zone is always guaranteed. Ensure the air suction
systems are operating correctly, in optimal conditions, and comply with the legal measures..
During the design phase, the indications contained in UNI EN ISO 14738 were followed with
regard to workstations on machines and the lifting limits imposed by UNI ISO 11228-1 were
evaluated.

12 / 78 00U07352260-A_EN 01.07.2022 13 / 78
Be sure to maintain a posture that does not cause fatigue when installing and maintaining the
unit. Also check the weight of any component before handling it.
The unit works with the refrigerant R32, included in the list of greenhouse gases (GWP
675) that meet the requirements of EU Regulation No. 517/2014 known as “F-GAS”
(mandatory in the European area). One of the provisions of this Regulation requires
operatorsworkingininstallationsusinggreenhousegasestoholdacerticateissuedor
recognised by the competent authority attesting that they have passed an examination
authorising them to carry out such work. In detail :
-Upto3kgoftotalrefrigerantcontainedintheappliance:Category2certicate.
-Morethan3kgoftotalrefrigerantcontainedintheappliance:category1certicate.
Refrigerant R32 in gaseous form is heavier than air, if it is dispersed in the environment,
it tends to concentrate strongly in poorly ventilated areas. Inhalation can cause dizziness
andsuocationand,incaseofcontactwithopenamesorhotobjects,lethalgasesmay
be emitted (see Refrigerant Material Safety Data Sheet).
You should know that refrigerants may not develop an odor.
For any intervention on the heat pump system:
Wear appropriate PPE (especially gloves and goggles).
Ensure that the workplace is well ventilated. Do not work in closed rooms or ditches with low
air recirculation.
Donothandlecoolantnearhotcomponentsoropenames.
Avoid any dispersion of the refrigerant in the environment and pay particular attention to
accidentalleaksofpipesand/orttings,evenafterdrainingthesystem.
Makesurethereisareextinguisherneartheunit.
1.2.7. Personal protective equipment
When using and maintaining units, it is necessary to provide for the use of personal
protective equipment such as:
Clothing: People who perform maintenance or work on the system must wear clothing that
does not leave parts of the body uncovered, because during maintenance it is possible to come
into contact with hot or sharp surfaces. Avoid clothing that can cling to or be sucked in by the
airow.
Safetyshoeswithnon-slipsoles,especiallyinenvironmentswheretheoorisslippery.
Gloves: Protective gloves must be worn during cleaning and maintenance interventions.
Mask and goggles: Goggles and a respiratory protective mask should be used during cleaning
operations.

14 / 78 00U07352260-A_EN
AHP60-50/70 - Installation, Use and Maintenance
?

2. DESCRIPTION OF THE EQUIPMENT
2.1. Designations and scope
ECOMOD AHP60:
Heat pump comprising a close-coupled heat pump
Hot water production system for heating networks or thermodynamic production of
domestic hot water.
2.2. Packaging
Outdoor unit
Model Code
ECOMOD 50 AH090921
ECOMOD 70 AH090924
ECOMOD 50 AC* AH090922
ECOMOD 70 AC* AH090925
ECOMOD 50 D** AH090923
ECOMOD 70 D** AH090926
*AC: Anti-corrosion treated
** D: Ducted version
Outdoor unit accessories
Model Code
Set of anti-vibration supports (pack of 4) 092040
Other accessories according to connection - see Ecomod Heat Control manual, heating application
or DHW application.
The evaporator for the AC version is treated against corrosion. The heat pump's performance may
beaectedbythisbyupto2%inrelationtothevaluescommunicatedinchapter2.4.1
2.3. Denitions
Change to monobloc heat pump : to be installed outdoors only for heating and/or domestic hot
water application .
air/water : The outdoor air is the energysource. This energy is transmitted to the primary water
circuit by the heat pump.
inverter : The fan and compressor speeds are modulated to suit the heat requirements which
allows the noise level to be reduced. This technology makes it possible to save energy by avoiding
highstartingcurrentsandbyadjustingthepowertotheload.
COP(coecientofperformance) : instantaneously, this is the ratio between the energy transmitted
to the heating circuit and the electrical energy consumed.
DHW : Domestic hot water
CAUTION: The minimum admissible temperature for the storage of the units is 5°C.

16 / 78 00U07352260-A_EN
AHP60-50/70 - Installation, Use and Maintenance
TECHNICAL CHARACTERISTICS Measurement
units
AHP 60
50 kW 70 kW
Heating
Heat output (1)
min./nom. kW 24.1 / 50.2 32.9 / 66.8
Absorbed power (1) kW 12.2 16.3
C.O.P. (1) W/W 4.11 4.10
Heat output (2) kW 48.3 62
Absorbed power (2) kW 18.02 23.75
C.O.P. (2) W/W 2.68 2.61
SCOP (3) W/W 4.16 3.94
Waterowrate(1) m3/h 8.6 11.5
Useful head (1) kPa 108 122
Energyeciency
Water35°C/55°C Class A++/A+ A++/A+
Compressor
Type Scroll DC Inverter
Oil (type) FW68S
Number of compressors 2 2
Quantity of oil L 3.8 3.8
Refrigerating circuits 1 1
Refrigerant
Type R32
Refrigerant load (4) kg 8.5 12
Cooling quantity in tons of CO2 equivalent
(4) ton 5.7 8.1
Operating pressure (upper/lower) in heat
pump mode bar 46 / 1.3
Internal
exchanger Water capacity L 3.54 5.12
2.4. Technical data
2.4.1. Data sheet for standard units
This product is designed to be installed at a maximum altitude of 2000m

01.07.2022 17 / 78
AHP60-50/70 - Installation, Use and Maintenance
TECHNICAL CHARACTERISTICS Measurement
units
AHP 60
50 kW 70 kW
Hydraulic
circuit
Hydraulic circuit water capacity L 7 9
Max. pressure on water side bar 6 6
Hydraulic connections Ø 1 1/2” (DN 40)
Minimum volume of water for bottle L 389 522
Maximum power of circulator kW 1.04 1.35
Max absorbed current of the circulator A 1.86 2.45
EnergyEciencyIndex(IEE)ofthe
circulator
≤0.23 ≤0.23
Acoustic level
Noise level Lw (5) dB (A) 82 83
Audio power LW (6) under partial load dB (A) 75 81
Acoustic pressure at a distance of 1 m Lp1
(7) dB (A) 64.4 65.4
Acoustic pressure at a distance of 10 m
Lp1 (7) dB (A) 50.2 51.2
Electrical data
Power supply 400V/3P+N+
T/50Hz
400V/3P+N+
T/50Hz
Maximum absorbed power kW 34 43
Maximum absorbed current A 54 70
Dimensions
and weight
A - Length mm 1920
B - Width mm 1110
C - Height mm 1920 (1980 for ducted version)
A - Length packed mm 2100
B - Width packed mm 1110
C - Height packed mm 2015 (2075 for ductable version)
Weight for shipping kg 545 605
Weight in service kg 535 595
The above performances are given for the following operating conditions, as per the standard
14511:2018:
(1) Heating: external air temperature 7°dry C temperature (Ts) 6°C humid temperature (Th); in/out water
temp..30/35°C.
(2) Heating: external air temperature 7°dry C temperature (Ts) 6°C humid bulb (Th).; in/out water temp.
47/55°C.
(3)Heating:averageclimaticconditions:Tbiv=-7°C;in/outwatertemp.30/35°C.
(4)Indicativedataandsubjecttovariation.Forthecorrectdata,alwaysrefertothedatalabelontheunit.
(5) Noise level: heating mode condition (1); as per EN 12102-1:2013; value calculated based on the
measurements made as per UNI EN ISO 9614-1.
(6) Noise level: heating mode under partial load as per Appendix A of EN 12102:2017; value determined
based on measurements made as per UNI EN ISO 9614-1, in accordance with the requirements of HP
Keymarkcertication.
(7) Acoustic pressure: value calculated from the original acoustic pressure level as per ISO 3744:2010
N.B. : the performance date is indicative data and subject to variation. Furthermore, the outputs provided
in points (1) and (2) are given in relation to the instantaneous power as per standard EN 14511. The gure
provided in point (3) is determined based on the standard EN 14825.

18 / 78 00U07352260-A_EN
AHP60-50/70 - Installation, Use and Maintenance
2.4.2. 2.4.2. Electrical data for the unit and auxiliariesElectrical data for the unit and auxiliaries
*Acceptablevariations+/-10%.
REMARK: The electrical data may be modied for an update. You must consequently refer to the data label
on the RH side panel of the appliance.
2.4.3. Noise emissions
The acoustic pressure datas are calculated from the acoustic power level in compliance with
normISO3744:2010regardingheatpumpseldoperation.
2.4.3.1. Full load
Noise levels refer to units at full load under standard nominal conditions (1) and under normal
test conditions in heating mode, in accordance with the provisions of EU Regulation 813/2013.
The tolerance on the value of the total acoustic power level is 2 dB (A). The value is determined
in compliance with EN 12102-1: 2017, used together with EN ISO 9614-1 which describes the
test methods with the intensimetric method.
Unit power supply V/~/Hz 3N~400V-50Hz* Remote control circuit V/~/Hz 12/01/1950
Integrated control circuit V/~/Hz 12/01/1950 Power supply to fans V/~/Hz 3N~400V-50Hz*
Models
in kW Acoustic power level per octave band dB(A) Acoustic
power level
[LW(A)]
dB(A)
Acoustic
power
level at 1m
dB(A)
Acoustic
power level
at 10m
dB(A)
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz
50 59.2 66.3 69.6 73.7 76.8 78.5 69.6 82 64.4 50.2
70 61.1 67.3 70.8 74.9 78.1 79.8 70.8 83 65.4 51.2

01.07.2022 19 / 78
AHP60-50/70 - Installation, Use and Maintenance
2.4.3.2. Partial load
Sound levels refer to units at full load and in conditions guaranteeing a thermal capacity equal
tothatdeclaredatatemperatureof7°Cforanaverageclimate,inaccordancewithstandardEN
14825, in accordance with the provisions of EU regulation 813/2013(dry bulb temperature (wet
bulbtemperature)oftheoutsideair=7°C(6°C),watertemperatureinlet-outlet=47-55°C).The
tolerance on the value of the total sound power level is of 2dB(A). Value is determined according
toEN12102-1:2017,usedinconjunctionwithENISO9614-1whichdescribesthetestmethods
with the intensimetric method
Models
in kW Acoustic power level per octave band dB(A)
Acoustic
power
level
[LW(A)]
dB(A)
Acoustic
power level
at 1m dB
dB(A)
Acoustic
power level
at 10m dB
dB(A)
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz
50 48.9 57.9 63.0 66.3 69.9 70.6 68.3 75 57.4 43.2
70 41.4 64.0 70.1 72.6 75.5 75.8 71.2 81 63.4 49.2

20 / 78 00U07352260-A_EN
AHP60-50/70 - Installation, Use and Maintenance
2.5. Description
2.5.1. Models AHP60 50 - 70 kW
Front viewRight hand side view Left hand side view
Dimensions and weight
Models AHP60 50 kW AHP60 70 kW
Length mm 1920
Width mm 1110
Height mm 1920
Height (ducted version) mm 1980
IN / OUT (water in/out) 1 1/2” grooved tube
EElectrical power supply input
Figure 1 - Dimensions of the models AHP60 50 - 70 kW
2.5.2. Access to internal components
2.5.2.1. Access to the refrigeration circuit
1110
E
1920
1754100
1635
1920
Sor�e
d’eau
470198,5
296
Entrée
d’eau
1980 (version gainable)
Figure 2 - Access to the refrigeration component
This manual suits for next models
1
Table of contents
Other Ideal Heating Heat Pump manuals
Popular Heat Pump manuals by other brands

Nibe
Nibe Fighter 200P Installation and maintenance instructions

Aquacal
Aquacal 100 Owner's manual and installation guide

Weil-McLain
Weil-McLain WM2AC13018 Installer's information manual

ratiotherm
ratiotherm WP Max-Air Technical document

Danfoss
Danfoss HHP Series Application guidelines

Nibe
Nibe FIGHTER 1310 Installation and maintenance instructions

Dimplex
Dimplex LA 9TU Installation and operating instructions

Hayward
Hayward HeatPro HP50TA troubleshooting guide

Trane Technologies
Trane Technologies 4TWA4036A3000A Installer's guide

York
York YAP026 installation manual

Lennox
Lennox HP25 Series installation instructions

Heat Siphon
Heat Siphon Z Series owner's manual