
Copyright
©
2023,
Ideal
V
acuum
Products,
LLC
|
(505)
872-0037
| [email protected] | www.idealvac.comSVSC-04102023 - V 1.0.26
3. ANALOG USAGE
The Signal Converter’s factory default setting is to use analog input signals and supply analog output
signals from 0.5 to 4.5 volts. This voltage range denes a linear scale between a CommandValve
buttery angle of 0° and 90°. Values below the low end of the range are mapped to 0°, values
higher than the high end of the range are mapped to 90° (for any voltage range conguration).
There are four possible analog voltage range congurations which are shared by both the input and
output signals. The voltage conguration selection is set through the Modbus Holding Registers
(“
Analog Range Mode
”, Table 5, p. 7), using an analog voltage range selection (Table 6, p. 8).
Analog input can be disabled (and should be disabled) if one wants to utilize the Modbus interface
to control the valve (see Modbus Usage, below).
4. MODBUS USAGE
Modbus is utilized to congure the Signal Converter. Modbus RDU protocol on RS-485 is followed.
Modbus can control the valve on a Modbus network and can also be used to monitor and debug
the analog system.
Modbus registration tables are found on page 7. Modbus conguration tables are found on page 8.
As delivered, Modbus is NOT congured to control the valve directly. Setting the “
Analog Input
” coil
(Coils, Table 3, p. 7) to it’s off state and then modifying the “
Desired Angle
” (Holding Registers,
Table 5, p. 7) provides the necessary ability to control the valve.
To monitor the progress of the valve, “
Angle Position
” provides an interface to read the valve’s real
buttery angle value (Input Registers, Table 4, p. 7).
The “
Valve Model ID
” identies which command valve has been identied on the controller, if any
(Input Register, Table 4, p. 7, and Valve Models, Table 7, p. 8).
The Modbus interface provides a “
Control On
” coil to stop the Converter from controlling the
CommandValve through ANY input (Coils, Table 3, p. 7). This allows the user to use the push
buttons on the side of the CommandValve without them ghting the Signal Converter.
By default, Modbus serial settings are baud rate 9600, data bits 8, stop bits 1, no parity, and no
ow control. The baud rate is changed in the “
Baudrate Mode
” (Holding Registers, Table 5, p. 7)
and by setting the baud rate mode (Table 8, p. 8).
By default, the Modbus slave address is 1, but the Signal Converter also reacts to broadcasted
messages on slave address 0. The “
Modbus Slave Address
” is changed in the Holding Registers
(Table 5, p. 7).
Per the Modbus standard, it is recommended to have a minimum 2ms pause between transactions
on the RS 485 line.