IGD TOC-625-MCP User manual

Auto Setup Table 1
Relay 1 and Relay 2 on the TOC-625-Micro are set to be normally energised, de-energising on alarm or
power failure.
The TOC-625-Micro can FIND up to 10 devices. These can be any mix of gas detectors and up to 2 output
nodes
The TOC-625-Micro can FIND up to 4 addressable relays on 2 output nodes. Relay nodes supplied with
TOC-625-Micro need to be addressed as follows and will operate according to the following table.
Node Relay Address
Relay 1 Relay 2
Mutable
4201 4202
Relay 1 Relay 2
Mutable
4203 4204
Output Node 1 Output Node 2
Relays Active on
First Alarm
Note that mutable relays re-energise on second alarm.
Use the Setup Wizard at Startup
TOC-625-MCP Automatically Finds Connected Devices
Detected Devices are Automatically Installed
Alarm Levels and Outputs are Automatically Set
TOC-625 MICRO SERIES
GAS DETECTION SYSTEM International Gas Detectors
The control panel should be located outside the
area where the detectors are located so that it is
not necessary to enter to the area with a gas alarm
to reset or check the controller.
For detector locations refer to IGD document
BS023 Siting Gas Detectors. This is available from
the downloads area of our website.
Detectors are supplied pre-calibrated. If it is
required to check or demonstrate operation, test
gas kits are available from IGD
Note Alarms Levels and Types Are Fixed and Cannot be Adjusted
TOC-625-MCP is a multi-channel detector controller in an easily installed and implemented small
format package using pre-made plug and socket cables. The system can be used with the Tocsin
Addressable range of detectors or I/O modules listed in the auto setup table. The use of pre-made
cables means there is very little installation required, reducing cost and enhancing safety.625
Micro has a unique Auto Setup Function.
OLIVER I G D
Triton House Tel: +44 (0)161 483 1415
CO
H S
2CO2
SO2
NO NO2
CH4
International Gas Detectors Crosby St
Stockport
SK2 6SH
England
Fax: +44 (0) 161 484 2345
Email: [email protected]
Website: www.internationalgasdetectors.com
Ref T625M-3
Flammables
Carbon Monoxide
Carbon Dioxide
Carbon Dioxide
Chlorine
Oxygen
Type
Rising - Latching
Rising - Latching
Rising - Latching
Rising - Latching
Rising - Latching
Falling - Latching
Range
0-100% LEL
0-100ppm
0-5000ppm
0-5%
0-5ppm
0-25%
Alarm 1 / Relay 1
10% LEL
30ppm
1500ppm
0.5%
0.5ppm
19.5%
Alarm 2 / Relay 2
20% LEL
75ppm
5000ppm
1.5%
1ppm
18.5%
Gas Outputs
Hydrogen Sulphide 0-50ppm Rising - Latching 5ppm 10ppm

Electrical Details Figure 1 24V DC Operation
Rear View Front View Cover Open TOC-625 Micro
Power Connection Detail
Note System can also be
powered via 3.5mm Jack
Plug Mounted on the PCB
when using IGD Supplied
PSU Part ID TOC-PSU
Electrical Power: 18-28V DC
Power Requirements For 8 Detectors and 2 Nodes From Above Table = 1.5A
Important Note:
If you are using a floating output DC supply that does not have a grounded output then with the case open
high voltages could be present. Power down equipment before opening the housing and ensure installation is
by a competent person.
External Mains PSU Via Fused Spur
Cable Order Codes
1M Male -Female Cable M16
3M Male - Female Cable M16
6M Male - Female Cable M16
+24V DC
0V DC
NC
NC
NC RL
1
RL
2
+Ve
Electrical Load: TOC-625 Micro Controller in Alarm State 0.3A @ 24 V DC
TOC-30 Series Addressable Gas Detector 0.1A @ 24 V DC
TOC-30 Series Relay Node Activated 0.2A @ 24 V DC
Detectors, Nodes and Beacon
Sounders Connect Together Using
Pre-Made Cable Assemblies.
These Can be Inter-Connected to
Make Longer Runs
T30-1M-CBL
T30-3M-CBL
T30-10M-CBL
There can be up to 8 Gas detectors on
the system, these can be any mix of gas
detector types on the highway. For
example Flammable Gas Detectors,
Carbon Monoxide, Oxygen etc. This
example shows 2
There can be up to 2 Addressable Relay
Nodes on a system. These provide 2
single pole relays and if fitted then when
the FIND function is run they will set up
to the table on page 1
Normally Open
Common
Normally Closed
Connections common to each of the
two relay outputs. Note relays are
normally energised for fail safe
operation in service. Diagram shows
de-energised state.
Relays are 4A Non Inductive @ 24V DC
-Ve
NOTE
Detectors and Nodes MUST have
unique addresses. These will be
indicated on the cover on the
detector or node. Detectors or Nodes
with duplicate addresses will not
function correctly
Field Device Connector
Comm
Comm
NO
NO
NC
NC
Relays Energised
Relays De-Energised
Relay Action
Page 2
International Gas Detectors

Front View
Start up
Detector Order Codes With M16 Connectors
6 Entries 20.5mm
172mm
158mm
97.5mm
SETUP
WIZARD
Side View
76mm
18mm
RUN
10 s
Accessory Order Codes
Gas Collector Cone*
Remote Gassing Kit*
Cal Gas Adaptor
Splashguard
Output Relay Node
(Use With Beacons)
Beacon Sounder
With Signage
5A PSU With Battery
Backup 110/230V AC
2.5A 24V DC PSU
110/230V AC
*Collector Cones and remote gassing kits
also require the splash guard to be fitted
-5 to To 55 Deg C
0-95% RH Non-Condensing
IP54
Temp Rating
Humidity Rating
Sealing
5 Way M16
Connector
For Detector/Node
Connection
5210101
5110150
5925701
TOC-30-GD
TOC-30P-NDE
TOC-30P-BCN
TOC-PSU-B
TOC-PSU
Page 3
International Gas Detectors
0-100% LEL
0-100ppm
0-30% Vol
0-20ppm
0-5%
0-5000ppm
TOC-30P-PHC
TOC-30P-CO
TOC-30P-O2
TOC-30P-CL2
TOC-30P-CO2
TOC-30P-LCO2
>3 Years
>5 Years
>5 Years
>2 Years
>5 Years
>5 Years
Gas Standard Range Order Code Typical Cell Life
Flammable Gases
Carbon Monoxide
Oxygen
Chlorine
Carbon Dioxide
Carbon Dioxide
0-50ppm TOC-30A-H2S >3 YearsHydrogen Sulphide
After the start up cycle the Setup Wizard is displayed and RUN option will be available for 10
seconds. Press the button during this period and the TOC-625 Micro will search for connected
detectors and relay nodes. Based on the devices found the controller will set itself up based on
table 1. No operator intervention is required. Gas channels will be automatically configured based
on the devices found. Need to add or remove a detector or node? Just make the physical changes
and select the RUN option again on power up

User Actions....Day to Day Operation
FLT COM
FLT SEN
FLT OVR
FLT UND
Once fully installed the TOC-625 controller will continuously monitor connected
gas detectors and sensors and compare current values with any set alarm
thresholds. The display will cycle to display each channel in turn.
Channel Number Gas Type
Current Channel Reading
and Measurement Units
Power LED
In Alarm Condition
The back light will flash red and the display will indicate which alarm level and which
channel is in alarm. The sounder will also activate. Pressing the button will silence
the sounder and mute the relay nodes if connected as indicated in table 1. If the gas
is still breaching the alarm threshold it will not be possible to reset the alarm
1=FLAM
ALARM 1
In alarm mode the RED
alarm led will either be
flashing for alarm level 1 or
solid for alarm level 2. The
bottom line of the display will
indicate:
Alarm 1
Alarm 2
Alarm 1&2
In Fault Condition
1=FLAM
FLT UND
In FAULT mode the Yellow fault led
will be on. The bottom line of the
display will indicate as follows:
communication
error to sensors
Sensor Error
Sensor Over Range
Sensor Under Range
Reset Button
Alarm Sounder
Fault LED
Alarm LED
Flashing = Alarm 1
Continuous = Alarm 2
Page 4
OLIVER I G D
Triton House Tel: +44 (0)161 483 1415
CO
H S
2CO2
SO2
NO NO2
CH4
International Gas Detectors Crosby St
Stockport
SK2 6SH
England
Fax: +44 (0) 161 484 2345
Email: [email protected]
Website: www.internationalgasdetectors.com
Ref T625M-3
International Gas Detectors
This manual suits for next models
1
Popular Measuring Instrument manuals by other brands

Christ Elektronik
Christ Elektronik CLM1000 Professional instruction manual

THORLABS
THORLABS HTPS operating manual

Hanna Instruments
Hanna Instruments HI 701 manual

GASTRON
GASTRON GTC-520A instruction manual

AquaLabo
AquaLabo NEON pH-RedOx Operation manual

Powerfix
Powerfix Profi+ 94500 Operation and safety notes