www.sn-promet.pl
Spółdzielnia Niewidomych PROMET 41-200Sosnowiec,ul.Lipowa11
Centrala:tel+48222698100,Sekretariat:tel.+48 32 269 81 02, Dział Obsługi Klienta: tel. +48 32 269 81 81,
Strona|5
−in the lower part - scaled measured value displayed in digital form (white colour) with units
(cyan colour).
note:
1. The display colour of the measured value may change from white to red when the upper
overflow alarm is activated or to blue when the lower alarm is activated (see p. 5.2.4 to 5.2.7).
2. In current loop mode, if the input current is below 4 mA or its total absence (open circuit),
instead of the measured value, "Err" is displayed in blue.
At the same time, the lower overflow alarm activates if it was set to "ON" during programming
(see section 5.2.4).
3. The position of the decimal point for all three values is the same and corresponds to the setting
according to p. 5.2.1.
5. Settings up - programming of the MD22-TFT-IU indicator.
Reprogramming is carried out by means of three buttons of the membrane keyboard
on the front panel, marked as ↵, +, -.
Entering the programming mode follows by pressing and holding the "↵" button for approx. 5s.
Immediately after pressing the "↵" button, the screen backlight goes off, after about 5s the first
setting screen appears with the SET 1 header.
If the button is released earlier - the indicator returns to normal operation.
The programming process is quite intuitive. The parameter found to change is highlighted by
displaying black characters on a white background. The function of the "+" and "-" buttons is displayed
on each of the setting screens in the magenta colour at the bottom of the screen.
Pressing the "↵" button takes you to the next parameter settings or to the next settings screen.
5.1. Notes on setting numerical values.
All set numerical values should be in the range -999 ÷ 1000. The method of setting individual digits
was adopted by incrementing with the "+" button. The digit to be changed is displayed in the yellow
box, the selection is made by the "-" button.
note:
The first digit can take the values “-“, 0 or 1. In the last case, other three digits must remain zeros
(1000 - maximum value). Therefore, when setting this item to 1 other digits will automatically reset,
setting other values will be possible only after changing the first position to 0 or “-“.
We operate with integer values, omitting the decimal point, which after returning to the normal mode
will be displayed in accordance with the setting according to p. 5.2.1.