iglu Aleut Series User manual

INSTALLATION MANUAL
IGLU Aleut Series

2
Table of Contents
INTRODUCTION..........................................................................................................................4
PURPOSE....................................................................................................................................4
LIABILITY ....................................................................................................................................4
WARRANTY.................................................................................................................................4
SAFETY .......................................................................................................................................5
PRODUCT PACKAGING AND TRANSPORTATION...................................................................5
SELECTION OF THE INSTALLATION PLACE ...........................................................................6
PRELIMINARY PREPARATION OF THE PIPELINES.................................................................6
OUTDOOR CIRCUIT....................................................................................................................6
Installation and filling .............................................................................................................6
Filling and circulating unit......................................................................................................6
Automatic air release valves..................................................................................................7
Outdoor circuit pump..............................................................................................................7
INTERNAL CIRCUIT....................................................................................................................7
Heating system filling.............................................................................................................7
Flow through the heating system ..........................................................................................8
Heating system filter and valves............................................................................................8
Internal circuit circulation pump............................................................................................8
Heating system rinsing and filling.........................................................................................8
THERMAL INSULATION .............................................................................................................9
ELECTRICAL CONNECTION WORKS........................................................................................9
Temperature sensors............................................................................................................10
Characteristics of temperature sensors NTC 10K ..............................................................10
Phase sequence relay...........................................................................................................10
Control panel.........................................................................................................................11
START OF OPERATION............................................................................................................11
HEAT PUMP ELECTRICAL CONNECTION DIAGRAM.............................................................11
ARRANGEMENT OF CONTROLS.............................................................................................13
HEAT PUMP CLASSIC CONNECTION DIAGRAM ...................................................................14
CONNECTION DIAGRAM FOR HEAT PUMP WITH PASSIVE COOLING................................15
HEATING SYSTEM WITH BUFFER CAPACITY........................................................................16
HEATING SYSTEM WITH PASSIVE COOLING AND BUFFER CAPACITY .............................17
Technical data of IGLU Aleut fixed capacity heat pumps......................................................18
Technical data of IGLU Aleut WT fixed capacity heat pump with water heater....................19
Technical data of IGLU Aleut 18 WTI variable capacity heat pump with integrated water heater
...................................................................................................................................................20
Annex No 1................................................................................................................................21

3
Annex to the technical characteristics according to European Commission Regulation No 813/2013
...................................................................................................................................................21
Technical data of IGLU Aleut 5 fixed capacity heat pump..................................................21
Technical data of IGLU Aleut 7 fixed capacity heat pump..................................................22
Technical data of IGLU Aleut 9 fixed capacity heat pump..................................................23
Technical data of IGLU Aleut 11 fixed capacity heat pump................................................24
Technical data of IGLU Aleut 13 fixed capacity heat pump................................................25
Technical data of IGLU Aleut 5 WT fixed capacity heat pump with boiler ........................26
Technical data of IGLU Aleut 7 WT fixed capacity heat pump with boiler ........................27
Technical data of IGLU Aleut 9 WT fixed capacity heat pump with boiler ........................28
Technical data of IGLU Aleut 11 WT fixed capacity heat pump with boiler.......................29
Technical data of IGLU Aleut 13 WT fixed capacity heat pump with boiler.......................30
Technical data of IGLU Aleut 18 WTI heat pump with integrated boiler............................31
Annex No 2................................................................................................................................32
Use of outdoor and indoor circuit pumps according to heat pump models ..................................32
Annex No 3................................................................................................................................33
UPM3 K FLEX AS 25-75 180 characteristic................................................................................33
UPM3 K FLEX AS 25-75 180 electrical parameters, 1 x 230 V, 50/60 Hz...................................33
Annex No 4................................................................................................................................34
UPMXL GEO 25-125 180 PWM, 1 x 230 V, 50/60 Hz characteristics .........................................34
UPMXL GEO 25-125 180 PWM electrical parameters, 1 x 230 V, 50/60 Hz...............................34
Dimensions of the UPMXL circulation pump...............................................................................34
Annex No 5................................................................................................................................35
Heat pump dimensions and connection nozzles .........................................................................35
Annex No 6................................................................................................................................38
Design dimensions of the heat pump from the front ................................................................38
Design dimensions of the heat pump from the top...................................................................38

4
INTRODUCTION
This installation manual provides information on the installation of the IGLU heat pump. It is an
integral part of the product and must be easily accessible to the installer. The manual must be
available throughout the life of the device. In the event of a change in the owners of the device, the
manual must be passed on to the new owners or users.
Read the instructions before installing the heat pump. Follow all instructions as specified by
the manufacturer.
If you have any questions, please contact the company that performs installation of heat
pumps or your local manufacturer’s representative.
This installation manual was written for several types of devices; you must always follow the
parameters applicable to the respective type of equipment
PURPOSE
The manual is intended only for persons who install the devices. Treat all constituents
responsibly. The heat pump may only be used for its intended purpose, which means:
•heating;
•domestic hot water preparation;
•coolinstr.
The device can only be operated according to its technical parameters.
LIABILITY
The manufacturer shall not be liable for damage caused by improper use or installation of the
heat pump. The manufacturer’s liability shall also not apply:
•if work has been performed that differs from the specifications in these operating
instructions;
•if work has been carried out on the equipment which is not described in this manual or
which has not been approved in writing by the manufacturer;
•if the equipment or its components have been modified, altered or removed without a
written consent of the manufacturer.
WARRANTY
The product has a 24-month warranty upon submission of the purchase documents.
The product warranty can be extended up to 60 months with annual heat pump maintenance.
Warranty and post-warranty provisions are available in the purchase documents.

5
SAFETY
The device is safe to use as intended. The construction and design of the device comply with
all safety regulations. Prior to starting work, any person involved must read and understand the
operating instructions. This also applies if the person concerned has already worked on such or
similar equipment or has been trained by the manufacturer. Any person carrying out installation work
must meet the health and safety requirements that apply everywhere. This is especially true when
using personal protective equipment.
DANGER!
Danger of fatal injuries due to electric shock!
The electrical connection may only be installed by a qualified electrician.
Prior to opening the device, disconnect the system from the power supply and prevent it from
being switched on again!
WARNING!
Work on the device and its components may only be carried out by qualified specialists
(heating, refrigeration, coolant technicians and electricians).
WARNING!
Observe the safety signs on and inside the device.
WARNING!
The unit contains coolant!
If the coolant leaks, it poses risk to people and the environment, therefore, you must:
–
turn off the system;
–
make sure the installation room is well ventilated;
–
inform the manufacturer’s customer service.
ATTENTION
For safety reasons, never disconnect the device from the power supply unless the device is open.
Do not use pure water in the outdoor circuit.
PRODUCT PACKAGING AND TRANSPORTATION
After purchasing a heat pump:
Inspect the delivered product for external damage during delivery;
In the event of delivery defects, submit a claim to the company that sold the device immediately.
The heat pump may only be transported and stored in an upright position. The device
can only be temporarily tilted, not laid down. The device can be stored at a temperature no lower
than 10 oC.

6
SELECTION OF THE INSTALLATION PLACE
When choosing the installation place of the heat pump, keep in mind that the heat pump
produces a certain level of noise (see table “Heat pump technical data”).
The device must be mounted on a flat and stationary surface with a permissible load of at least
500 kstr. Minor surface irregularities can be compensated by adjusting the feet of the device.
The ambient temperature near the heat pump must be between 10°C and 35°C, and the relative
humidity must not exceed 80%.
There must be no aggressive chemicals in the environment.
The heat pump should not be installed close to walls; the front of the unit should always be
accessible (see, Annex No 6).
A drainage system must be provided in the room where the unit is installed. In this case, leaking
water can be drained.
Do not use extra platforms.
PRELIMINARY PREPARATION OF THE PIPELINES
The connecting pipes for the outdoor circuit, the heating circuit and, if provided, the hot water
circuit must be laid up to the intended location of the heat pump. Install an expansion vessel, safety
valves, coarse suction filters and pressure gauges for the outdoor, heating circuit and boiler. The
circuits must have a provided filling point.
OUTDOOR CIRCUIT
Installation and filling
The outdoor circuit can be vertical (boreholes) or horizontal. The horizontal circuit must be
installed below the freezing zone, depending on the ground of the installation site. Fill the outdoor
circuit with glycol, which ensures that it does not freeze in temperatures up to -15oC. Do not use the
salt-based solution. The following fluids are approved for the outdoor circuit:
• monoethylene glycol;
• propylene glycol.
It is recommended to use a mixture of water and monoethylene glycol concentrate in a ratio of
3:1. The applicable rules and regulations must be observed when installing and filling the outdoor
circuit. There must be no stones or sharp objects in the ground where the outdoor circuit is installed
that could damage the pipes. Prior to filling the system, make sure that the system is tightly sealed.
When installing the outdoor circuit, it is necessary to protect the pipes from penetration of dirt
or gravel. If the system is dirty, the heat pump may become clogged and individual components of
the device may be damaged or corrupted.
Filling and circulating unit
The outdoor system refiller must be installed next to the circuit inlet so that the system can be
replenished when the system pressure drops and the external and glycol mixing procedure can be
performed when filling the outdoor circuit. The filling unit is not included in the heat pump
package.

7
Automatic air release valves
In order to ensure that no air clogs occur in the outdoor circuit system and that the heat pump
does not signal an alarm as a result, it is necessary to install automatic air release valves on the
outdoor circuit. The air release valves must be installed at the highest points of the circuit.
Outdoor circuit pump
The outdoor circuit pump is included in the heat pump set and is installed in the device at the
factory. The Grundfos UPM3 pump (see, Annex No 2) is the most commonly used for the outdoor
circuit, and the UPMXL heat pumps with a capacity of more than 11 kW (see, Annex No 2). The
circulation pump is controlled by the central processor while maintaining optimal flow. The control
system monitors the operation of the circulation pumps and a warning is received in the event of a
deviation.
INTERNAL CIRCUIT
To avoid gas formation, it is recommended not to use galvanised pipe systems.
WARNING!
The area of the domestic hot water tank heat exchanger must correspond to the capacity of
the heat pump. The water capacity must be such that the heat output of the heat pump is
transmitted as efficiently as possible.
NOTE
Integrate the hot water tank into the heat pump system to match the heating system scheme
you have selected (see, pages 14-17).
Heating system filling
Set the pressure of the heating circuit in the expansion vessel to 1.5 bar. Usually the
replenishment of the heating circuit is stationary, pre-connected to the water inlet, in which case the
replenishment takes place individually according to the system. If the filler in the heating circuit is not
water, then the system is filled with the appropriate liquid. As an additional protection against
freezing, in some cases the water in the heating system may be mixed with glycol, however, this
concentration should not exceed 15%. In this case, the efficiency of the heat pump decreases.

8
Flow through the heating system
A bypass is required in the mixing circuit, if an adjustable circulation pump is used, which is
controlled by differential pressure. Bypass is not included with the heat pump. If a buffer tank
bypass is installed in parallel with the heating system, no bypass is required.
Heating system filter and valves
The heat pump does not include a filter and a safety valve. These components must be
installed on the pre-prepared heating system return line. The safety valve shall be installed vertically.
WARNING!
Do not leave the safety valve closed.
Internal circuit circulation pump
The internal circuit pump is included in the heat pump set and is installed in the device at the
factory. The Grundfos UPM3 pump (see, Annex No 2) is the most commonly used for the internal
circuit, and the UPMXL heat pumps with a capacity of more than 9 kW (see, Annex No 2). The
circulation pump is controlled by the central processor while maintaining optimal flow. The control
system monitors the operation of the circulation pumps and a warning is received in the event of a
deviation.
Heating system rinsing and filling
The heat pump is an integral part of the heating system. Heat pump failures are usually caused
by poor water quality in the heating system, or by presence of air in the system. The presence of air
in the system produces corrosive products such as magnetite or sediment. Magnetite has an
abrasive effect that is especially enhanced in pumps, valves, or eddy-flow components, such as a
condenser. Prior to installing a heat pump in a heating system that needs to be filled or uses water
that is not pure, auxiliary measures such as the installation of filters and automatic outlets must be
taken. Filling with untreated drinking water will inevitably result in formation of a sediment. Effect:
formation of limescale deposits on the heat transfer surfaces. Decreased efficiency and energy
consumption increases. 1 millimetre of lime deposits causes an energy loss of 10%. In extreme
cases, this can even damage the heat exchangers.
Do not use water treatment additives in the heating system. Additives can be used to adjust the
pH of the water, the recommended pH of the water is 7.5-9. The safest and most efficient operation
of the system is achieved by using low-salt water.
When combining a heat pump with a boiler, it may be necessary to fill the system with
desalinated water to protect the boiler from corrosion. This reduces electrical conductivity and risk of
corrosion.
WARNING!
Sediment in the piping can damage the heat pump. To prevent this, make sure to flush the
pipes.
Damage to sediment and corrosion heating systems is low if:
- planning and start-up are carried out properly;
- the system is closed in terms of corrosion;
- pressure in the heating system is adequate;

9
- regular maintenance and prevention.
It is recommended that a system log be kept containing the relevant maintenance data.
Damage that may occur due to a malfunctioning system
Component failures (e.str., pumps, valves)
Internal and external leaks (e.str., from heat exchangers)
Reduction in cross-section and flow blockage (e.str., heat exchanger, pipes, pumps can
become clogged due to limescale or corrosion)
Faster wear
Gas cushion formation (cavitation)
Adverse effects due to heat transfer (coatings, sedimentation) and associated noise
(e.str., roaring, flow noise)
THERMAL INSULATION
All heat and cold conductive parts of the piping must be insulated with special means of thermal
insulation in accordance with current standards. The main normative document, which defines the
requirements for thermal insulation, is Order No 1-245 of the Minister of Energy of the Republic of
Lithuania “ON THE APPROVAL OF RULES FOR INSTALLATION OF THERMAL INSULATION OF
EQUIPMENT AND HEAT TRANSMISSION NETWORKS” of 20 September 2017.
ELECTRICAL CONNECTION WORKS
DANGER!
Risk of electric shock! Always disconnect the device from the power supply prior to work on
the electrical system parts.
Remove the top cover of the heat pump by unscrewing the screws on the top of the device.
Connect the power cable to the marked heat pump relay terminals 1, 3, 5, respectively L1, L2, L3
(see, Section: “Heat pump electrical connection diagram”) and connect N and PE conductors to the
marked electrical connection diagram contacts, respectively.

10
Temperature sensors
The temperature sensors for the outdoor and water heater are connected to the terminal blocks,
which are shown in the layout diagram of the control elements (see, Section: “Heat pump electrical
connection diagram”). A two-core 0.5 ÷ 1mm2cable must be routed from the heat pump to the
outdoor temperature installation location.
It is recommended that the outdoor sensor be installed on the north side or in a place that is not
exposed to direct sunlight.
In models without integrated water heater, a two-core 0.5 ÷ 1.0 mm2cable must be routed from
the heat pump to the hot water tank.
Next: Heat pump electrical connection diagram.
Characteristics of temperature sensors NTC 10K
T [°C]
R [Ω]
T [°C]
R [Ω]
T [°C]
R [Ω]
-30.0
175203
50.0
3605
130.0
298
-25.0
129289
55.0
2989
135.0
262
-20.0
96360
60.0
2490
140.0
232
-15.0
72502
65.0
2084
145.0
206
-10.0
55047
70.0
1753
150.0
183
-5.0
42158
75.0
1481
155.0
163
0.0
32555
80.0
1256
160.0
145
5.0
25339
85.0
1070
165.0
130
10.0
19873
90.0
915
170.0
117
15.0
15699
95.0
786
175.0
105
20.0
12488
100.0
677
180.0
95
25.0
10000
105.0
586
185.0
85
30.0
8059
110.0
508
190.0
77
35.0
6535
115.0
443
195.0
70
40.0
5330
120.0
387
200.0
64
45.0
4372
125.0
339
Phase sequence relay
The heat pump features a built-in phase sequence relay that ensures that the compressor is
running in the correct phase sequence. The relay is equipped with PWR and OUT indicator lights.
When the heat pump is switched on and the phases are in the correct sequence, the PWR display
lights up yellow and OUT lights up green. If it is not connected properly, the PWR indicator lights up
in yellow and the OUT indicator does not light up. In this case, reset the correct phase sequence so
that the OUT indicator lights up in green.

11
WARNING!
Do not connect anything to the terminals that are dark grey
The phase sequence relay also responds to voltage that is too low or too high. If the
voltage is too low or too high, the compressor operation will stop. When the voltage is
within tolerance again, the compressor operation is resumed.
Control panel
The control panel is installed in the room according to which you want to control the heating
temperature. The panel must be easily accessible in a point about 1.5 m above the floor. An online
5cat network cable must be routed from the heat pump to the control panel mounting location.
START OF OPERATION
Prior to start of operation of the heat pump, be sure to check that:
•the heat pump has been installed in accordance with the requirements of this operating manual;
•the electrical installation works have been properly performed;
•the heating circuit has been flushed and properly filled;
•all valves and shut-off devices in the heating system are open;
•all piping systems and components are leakproof;
•the pressures in outdoor and indoor circuits meet the requirements;
•the cables have been laid in accordance with the requirements up to the outdoor and hot water
tank and control panel;
•Wi-Fi or wired internet connection is available to be able to monitor and control the heat pump
remotely.
The heat pump must be started by the customer service personnel authorised by the manufacturer.
Start-up and adjustment work is performed against remuneration! Once the work is completed,
the person responsible for the start-up shall fill our and sign the heat pump start-up report.
HEAT PUMP ELECTRICAL CONNECTION DIAGRAM
Input voltage
Power
source
Relay
output

12
MCX061V
Šilumos siurblio įvadas
išatskiro automatinio jungiklio
F1
KM1
L3
L2
L1
KU1
WVU
N PE
F2
AI1
ST1
AI2
AI3
AI4
AI5
AI6
AI7
5V+
PS
PS
Atsiurbimo temperatūra, NTC-10K
Įeinančio glikolio temperatūra, NTC-10K
Išeinančio glikolio temperatūra, NTC-10K
Lauko temperatūra, NTC-10K
Kondensacijos slėgis, 0-5V
Gryžtančio termofikato temp. NTC-10K
Atsiurbimo slėgis, 0-5V
General Alarm
EEV vožtuvas
EXV1
ST2
ST3
ST4
M
L
N
GND
CANL
CANH
R120
RD
BL
OR
YE
MŠ1
EXC06D AI1
DI1
AI2
AI3
AI4
Boilerio temperatūra, NTC-10K
Kambario temperatūra, NTC-10K
Paduodamo termofikato temp., NTC-10K
Kompresoriaus variklio šil. apsauga
Fazių kontrolės kontaktas
L1
N1
GND
CANL
CANH
R120
DI3
DI2
DI4
DI5 Vyksta vesinimas (fankoilas)
COM
COM
COM
NO1
NO4
C1
NO2
C2
Kompresorius
Vidaus kontūro siurblys
Lauko kontūro siurblys
Karšto vandens vožtuvas
Vėsinimo vožtuvas
NO5
C4
C5
C3
NO3
Boilerio teno relė
NO5
C5
NC5
COM
DI1
A1
13
KU1
13
14
Operatoriaus
panelėCAN-
RJ
COM
P1
P2
X1:1 X1:2
X1:6X1:5
X1:4X1:3
M
M2
M
M3
KM1 A2
F1 14
X2:2X2:1
X2:4X2:3
WH
GN
BL
WH
GN
BL
24AC
230VAC
I>
1 3 5
L3L2L1
62 4
62 4
51 3
M1
3~
X1 X2
TE1
TE2
TE3
TE4
TE5
TE6
TE7
TE8
X1 X2
KB
Heat pump inlet
from separate automatic switch
Suction temperature, NTC-10K
Incoming glycol temperature, NTC-10K
Outgoing glycol temperature, NTC-10K
Outdoor temperature, NTC-10K
Condensation pressure, 0-5V
Return heating water temperature, NTC-
10K
Offset pressure, 0-5V
EEV valve
Boiler temperature, NTC-10K
Room temperature, NTC-10K
Supply heating water temperature, NTC-
10K
Boiler temperature, NTC-10K
Room temperature, NTC-10K
Supply heating water temperature, NTC-
10K
Compressor motor thermal protection
Phase control contact
Cooling (fan coil)
Compressor
Outdoor circuit pump
Internal circuit pump
Hot water valve
Cooling valve
Boiler heating element relay

13
ARRANGEMENT OF CONTROLS
Kompresoriaus
magnetinis paleidiklis
Kabelinis latakas
Centrinis procesorius
Anga kabelių įvedimui
Įžeminimo gnybtynas
Neutralės gnybtynas
Kompresoriaus šiluminė apsauga
Valdymo grandinių automatinis
išjungiklis .
Lauko temp. daviklio gnybtų rinklės
Programuojamo loginio valdiklio
išplėtimo modulis .
Fazių kontrolės relė
24V DC maitinimo šaltinis
Šilumos siurblio įvadas
išatskiro automatinio
jungiklio
Kambario temp. daviklio gnybtų rinklės
Boilerio temp. daviklio gnybtų rinklės
Kabelinis latakas
Elementų tvirtinimo plokštė
Heat pump inlet from a
separate circuit breaker
Neutral terminal
Ground terminal
Element mounting
plate
Cable duct
Compressor magnetic
starter
CPU
Hole for cable entry
Compressor thermal
protection
Automatic circuit breaker for control
circuits
Outdoor temperature sensor terminal
set
Room temperature sensor terminal
set
Boiler temperature sensor terminal set
Cable duct
Programmable logic controller
expansion module
Phase control relay
24V DC power supply

14
HEAT PUMP CLASSIC CONNECTION DIAGRAM
The most popular heating system connection diagram, which is the most cost-effective in
terms of cost and installation. When the hot water is heated to the set temperature, a three-way
valve inside the heat pump switches to home heating, where the heat is transferred to the home in a
low-temperature medium. The manufacturer recommends the use of underfloor heating for this
connection method.
Each heat pump has the ability to connect to the Internet, so you can see the heat pump
settings and control the system remotely.
Čia: - paduodamas termofikatas;
- grįžtantis termofikatas;
- išeinantis glikolis;
- įeinantis glikolis.
Šildymo
kontūras
Lauko kontūras
Karšto
vandens
boileris
Šilumos
siurblys
Outdoor circuit
Hot
water
boiler
Where:
Supply heating water
Return heating water
Outgoing glycol
Incoming glycol
Heat pump
Heating circuit
Heating circuit

15
CONNECTION DIAGRAM FOR HEAT PUMP WITH PASSIVE COOLING
This diagram shows the hydraulic diagram of the heating system when passive cooling is
used. This connection method ensures comfort all year round. The heating system is similar to the
classic one, but in this case it is necessary to lay the pipes to the fan radiators (fan coils). In
addition, a three-way valve is installed on the outdoor circuit, which regulates the direction of glycol
flowing from the outdoor circuit during the warm season. The outdoor circuit cannot be used for
cooling and heating at the same time.
Each heat pump has the ability to connect to the Internet, so you can see the heat pump
settings and control the system remotely.
Čia: - paduodamas termofikatas;
- grįžtantis termofikatas;
- išeinantis glikolis;
- įeinantis glikolis.
Lauko kontūras
Karšto
vandens
boileris
Pasyvus vėsinimas
Fankoilas
Šilumos
siurblys
Fankoilas
A B
AB
Šildymo
kontūras
Outdoor circuit
Fancoil Fancoil
Hot
water
boiler
Heat pump
Heating circuit
Passive cooling
Where:
Supply heating water
Return heating water
Outgoing glycol
Incoming glycol
Fancoil Fancoil

16
HEATING SYSTEM WITH BUFFER CAPACITY
This diagram provides a hydraulic diagram of the heating system, when the temperature
control of individual room circuits by actuators is provided in the object. It is recommended to install
a buffer tank for fixed capacity heat pumps when planning to regulate the temperature for individual
rooms. Otherwise, without installing the buffer tank, up to 30% of the heating circuit can be closed at
the same time. Variable capacity heat pumps do not require buffer capacity.
Each heat pump has the ability to connect to the Internet, so you can see the heat pump
settings and control the system remotely.
Čia: - paduodamas termofikatas;
- grįžtantis termofikatas;
- išeinantis glikolis;
- įeinantis glikolis.
Šildymo
kontūras
Karšto
vandens
boileris
Buferinė
talpa
Šilumos
siurblys
Lauko kontūras
Where:
Supply heating water
Return heating water
Outgoing glycol
Incoming glycol
Heat pump
Heating circuit
Hot
water
boiler
Outdoor circuit
Buffer
tank

17
HEATING SYSTEM WITH PASSIVE COOLING AND BUFFER CAPACITY
This connection method allows to take full advantage of the heating and cooling functions.
The diagram shows the hydraulic diagram of the heating system, when the temperature control of
individual room circuits by actuators and cooling function using fan radiators is provided in the
object. It is recommended to install a buffer tank for fixed capacity heat pumps when planning to
regulate the temperature for individual rooms. Otherwise, without installing the buffer tank, up to
30% of the heating circuit can be closed at the same time. Variable capacity heat pumps do not
require buffer capacity. For fan radiators, additional pipes must be laid from the outdoor circuit to
which they will be connected via a three-way valve. The outdoor circuit cannot be used for cooling
and heating at the same time.
Each heat pump has the ability to connect to the Internet, so you can see the heat pump
settings and control the system remotely.
Čia: - paduodamas termofikatas;
- grįžtantis termofikatas;
- išeinantis glikolis;
- įeinantis glikolis.
Šildymo
kontūras
Lauko kontūras
Karšto
vandens
boileris
Buferinė
talpa
Pasyvus vėsinimas
Fankoilas
Šilumos
siurblys
Fankoilas
A B
AB
Where:
Supply heating water
Return heating water
Outgoing glycol
Incoming glycol
Heat pump
Heating
circuit
Hot
water
boiler
Outdoor circuit
Buffer
tank
Fancoil Fancoil
Passive cooling

18
Technical data of IGLU Aleut fixed capacity heat pumps
Units
5 kW
7 kW
9 kW
11 kW
13 kW
Brine/water used
Thermal power (B0/W35)1)
kW
5.24
7.25
9.22
10.95
13.07
Thermal power (B0/W45)1)
kW
4.89
6.85
8.67
9.98
12.30
COP (B0/W35)1)
-
4.37
4.42
4.45
4.52
4.54
COP (B0/W45)1)
-
3.37
3.42
3.47
3.41
3.47
SCOP (B0/W35)
-
5.55
5.66
5.72
5.86
5.77
SCOP (B0/W45)
-
4.14
4.22
4.26
4.37
4.3
Brine circuit
Rated flow (DT = 3K)2)
m3/h
1.50
2.0
2.50
3.00
3.50
Permissible external pressure drop2)
kPa
45
80
91
90
85
Maximum pressure
bar
4
Volume (internal)
l
5
Operating temperature
°C
from -10 to +20
Connection (Cu)
mm
28
Compressor
Type
Spiral “Scroll”
Mass of refrigerant R 407C3)
kg
1.20
1.30
1.35
1.40
1.50
Maximum pressure
bar
45
Heating system
Rated flow (DT = 7K)
m3/h
1.00
1.50
2.00
2.00
2.20
Min. flow temperature
°C
15
Max. flow temperature
°C
60
Max. permissible operating pressure
bar
4.0
Connection (Cu)
mm
28
Power network connection values
Electrical connections
400 V 3 N~50 Hz
Inertial fuse; with electric heater 3 kW
A
10-16-20
16/16/20
16/20/25
16/25/25
20/25/32
Compressor rated power (B0/W35)
kW
1.19
1.64
2.06
2.56
3.06
Max. current with inrush current limiter4)
A
4.10
5.20
6.80
8.23
10.10
Type of protection
IP
X1
General information
Permissible ambient temperatures
°C
from +10 to +35
Sound power level5)
dBA
42
Dimensions (width x depth x height)
mm
620 x 620 x 1200
Weight (without packaging)
kg
102
110
115
130
135
1) With internal pump according to EN 14511
2) With ethylene glycol
3) Greenhouse potential, GWP100 = 1774
4) WPS 6-1: Max. current without inrush current limiter
5) According to EN 3743-1

19
Technical data of IGLU Aleut WT fixed capacity heat pump with water
heater
Units
5 kW
7 kW
9 kW
11 kW
13 kW
Brine/water used
Thermal power (B0/W35)1)
kW
5.24
7.25
9.22
10.95
13.07
Thermal power (B0/W45)1)
kW
4.89
6.85
8.67
9.98
12.30
COP (B0/W35)1)
-
4.37
4.42
4.45
4.52
4.54
COP (B0/W45)1)
-
3.37
3.42
3.47
3.41
3.47
SCOP (B0/W35)
-
5.55
5.66
5.72
5.86
5.77
SCOP (B0/W45)
-
4.14
4.22
4.26
4.37
4.3
Brine circuit
Rated flow (DT = 3K)2)
m3/h
1.50
2.0
2.50
3.00
3.50
Permissible external pressure drop2)
kPa
45
80
91
90
85
Maximum pressure
bar
4
Volume (internal)
l
5
Operating temperature
°C
from -10 to +20
Connection (Cu)
mm
28
Compressor
Type
“Scroll”
Mass of refrigerant R 407C3)
kg
1.20
1.30
1.35
1.40
1.50
Maximum pressure
bar
45
Heating system
Rated flow (DT = 7K)
m3/h
1.00
1.50
2.00
2.00
2.20
Min. flow temperature
°C
15
Max. flow temperature
°C
60
Max. permissible operating pressure
bar
4.0
Hot water tank volume
l
200
Capacity material
-
Stainless steel 1,4404
Connection (Cu)
mm
28
Power network connection values
Electrical connections
400 V 3 N~50 Hz
Inertial fuse; with electric heater 3 kW
A
10-16-20
16/16/20
16/20/25
16/25/25
20/25/32
Compressor rated power (B0/W35)
kW
1.19
1.64
2.06
2.56
3.06
Max. current with inrush current limiter4)
A
4.10
5.20
6.80
8.23
10.10
Type of protection
IP
X1
General information
Permissible ambient temperatures
°C
from +10 to +35
Sound power level5)
dBA
42
Dimensions (width x depth x height)
mm
700 x 700 x 1750
Weight (without packaging)
kg
187
195
200
215
220
1) With internal pump according to EN 14511
2) With ethylene glycol
3) Greenhouse potential, GWP100 = 1774
4) WPS 6-1: Max. current without inrush current limiter
5) According to EN 3743-1

20
Technical data of IGLU Aleut 18 WTI variable capacity heat pump with
integrated water heater
Units
Power network connection values
Electrical connections
400 V 3 N~50 Hz
Inertial fuse; with electric heater 3 kW
A
16-20-25
Compressor rated power consumption
(B0/W35) @ 60 rps
kW
2.84
Max. current
A
10.70
Type of protection
IP
X1
Heat (electric) power of a heat pump / COP (B0/W35)
Compressor power @ 30 rps
kW
5.85 (1.32) / 4,43
Compressor power @ 60 rps
kW
13.00 (2.84) / 4.58
Compressor power @ 85 rps
kW
18.60 (4.32) / 4.31
Compressor
Type
“Scroll”
Mass of refrigerant R410A
kg
2.20
Maximum pressure
bar
45
Heating system
Hot water tank volume
l
200
Max. permissible operating pressure
bar
4.00
Max. supply temperature
°C
60
Nominal flow (DT = 6K)
m3/h
2.17
Min. flow temperature
°C
15
Boiler tank material
-
Stainless steel 1,4404
Connection (Cu)
mm
28
General information
Permissible ambient temperatures
°C
from +10 to +35
Sound power level5)
dBA
35-42
Dimensions (width x depth x height)
mm
700 x 700 x 1750
Weight (without packaging)
kg
235
200
215
220
This manual suits for next models
11
Table of contents
Other iglu Heat Pump manuals
Popular Heat Pump manuals by other brands

Kospel
Kospel HPMI2 - 8 Installation and operating instructions

Carrier
Carrier Performance 50VT Product data

alphainnoTec
alphainnoTec LWP operating manual

VERSATEC
VERSATEC V036W installation manual

Mitsubishi Electric
Mitsubishi Electric Ecodan installation manual

Carrier
Carrier Infinity 25VNA4 owner's manual