6
1-3
INSTALLATORUSER
MAINTENANCE TECHNICIAN
partitions with limited static properties, or in any
case walls other than those indicated, a static test
must be carried out to ensure adequate support.
N.B.: the hex head screws supplied in the blister
pack are to be used exclusively to x the relative
mounting bracket to the wall.
ese boilers are used to heat water to below
boiling temperature in atmospheric pressure.
ey must be connected to a central heating
system and hot water circuit suited to their
performance and capacity.
1.3 GAS CONNECTION APPLIANCE
CATEGORY II2H3+.
Our boilers are designed to operate with methane
gas (G20) and LPG. Supply pipes must be the
same as or larger than the 3/4”G boiler tting.
Before connecting the gas line, carefully clean
inside all the fuel feed system pipes to remove any
residue that could impair boiler eciency. Also
make sure the gas corresponds to that for which
the boiler is prepared (see boiler data-plate). If
dierent, the appliance must be converted for op-
eration with the other type of gas (see converting
appliance for other gas types). e dynamic gas
supply (methane or LPG) pressure must also be
checked according to the type used in the boiler,
as insucient levels can reduce generator output
and cause malfunctions.
Ensure correct gas cock connection by follow-
ing the mounting instructions illustrated in
the gure. e gas supply pipe must be suitably
dimensioned according to current regulations in
order to guarantee correct gas ow to the burner
even in conditions of maximum generator output
and to guarantee appliance eciency (technical
specications). e coupling system must con-
form to standards.
Fuel gas quality. e appliance has been de-
signed to operate with gas free of impurities; oth-
erwise it is advisable to t special lters upstream
from the appliance to restore the purity of the gas.
Storage tanks (in case of supply from LPG
depot).
- New LPG storage tanks may contain residual
inert gases (nitrogen) that degrade the mixture
delivered to the appliance casing functioning
anomalies.
- Due to the composition of the LPG mixture,
layering of the mixture components may occur
during the period of storage in the tanks. is
can cause a variation in the heating power of
the mixture delivered to the appliance, with
subsequent change in its performance.
1.4 HYDRAULIC CONNECTION.
Important: In order not to void the warranty
before making the boiler connections, carefully
clean the heating system on the primary heat
exchanger (pipes, radiators, etc.) with special
pickling or de-scaling products to remove any
deposits that could compromise correct boiler
operation.
In compliance with Standards in force it is man-
datory to treat the water in the heating system
chemically in order to protect the system and
appliance from deposits of lime scale.
Hydraulic connections must be made in a
rational way using the couplings on the boiler
template. e boiler safety valve outlet must be
connected to an appropriate drain. Otherwise,
the manufacturer declines any responsibility in
case of ooding if the drain valve cuts in.
Attention: Immergas declines all liability in
the event of damage caused by the inclusion of
automatic lling that is not of its own brand.
Important: to preserve the duration of appliance
eciency features, in the presence of water whose
features can lead to the deposit of lime scale,
installation of the “polyphosphate dispenser” kit
is recommended. On the basis of the Standards in
force, it is mandatory to treat the water with over
25 French degrees in the heating circuit and over
15 French degrees for DHW using conditioning
chemicals for powers < 100 kW or with soeners
for powers > 100 kW.
1.5 ELECTRICAL CONNECTION.
e Mini Nike X 24 3 E boiler has an IPX4D
protection rating for the entire appliance. Elec-
trical safety of the unit is reached when it is cor-
rectly connected to an ecient earthing system
as specied by current safety standards.
Important: Immergas S.p.A. declines any re-
sponsibility for damage or physical injury caused
by failure to connect the boiler to an ecient
earth system or failure to comply with the refer-
ence standards.
Also ensure that the electrical installation
corresponds to maximum absorbed power
specications as shown on the boiler data-plate.
Boilers are supplied complete with an “X” type
power cable without plug. e power supply
cable must be connected to a 230V ±10% /
50Hz mains supply respecting L-N polarity and
earth connection . is network must also
have an omnipolar circuit breaker with class III
over-voltage category. When replacing the power
supply cable, contact an authorised company (e.g.
Authorised Technical Aer-Sales Service). e
power cable must be laid as shown. In the event
of mains fuse replacement on the P.C.B., use a
2A quick-blow fuse. For the main power supply
to the appliance, never use adapters, multiple
sockets or extension leads.
1.6 REMOTE CONTROLS AND
ROOM CHRONOTHERMOSTATS
OPTIONAL.
e boiler is prepared for the application of room
chronothermostats or remote controls, which are
available as optional kits. (Fig. 1-3)
All Immergas chronothermostats can be con-
nected with 2 wires only. Carefully read the
user and assembly instructions contained in the
accessory kit.
•On/OImmergasdigitalchrono-thermostat.
e chronothermostat allows:
- to set two room temperature values: one for
day (comfort temperature) and one for night
(lower temperature);
- to set up to four on/o dierential weekly
programs;
- to select the required operating mode from
the various possible alternatives:
•permanentfunctioningincomforttemp;
•permanentfunctioninginreducedtemp;
•permanentfunctioning in adjustableanti-
freeze temp.
e chronothermostat is powered by two 1.5V
LR 6 type alkaline batteries.
•“ComandoAmico Remoto” remoteControl
DeviceV2 (CARV2) with climate chronother-
mostat function. In addition to the functions
described in the previous point, the CAR
panelV2 enables the user to control all the
important information regarding operation
of the appliance and the heating system with
the opportunity of easily intervening on the
previously set parameters without having to
go to the place where the appliance is installed.
e panel is provided with self-diagnosis to
display any boiler functioning anomalies.
e climate chronothermostat incorporated
into the remote panel enables the system ow
temperature to be adjusted to the actual needs
of the room being heated, in order to obtain
the desired room temperature with extreme
precision and therefore with evident saving in
running costs. CARV2 is powered directly by
the boiler via the same 2 wires that are used
for data transmission between the boiler and
the device.
Important: If the system is subdivided into zones
using the relevant kit. the CARV2 must be used
with its climate thermostat function disabled, i.e.
it must be set to On/O mode.
“Comando Amico Remoto” Remote control
DeviceV2 or On/O chronothermostat elec-
trical connections (Optional). e operations
described below must be performed aer having
removed the voltage from the appliance. Any
thermostat or On/Off environment chrono-
thermostat must be connected to clamps 40
and 41 eliminating jumper X40 (Fig. 3-2). Make
sure that the On/O thermostat contact is of
the “clean” type, i.e. independent of the mains
supply, otherwise the electronic adjustment
card would be damaged. Any Comando Amico
Remoto remote controlV2 must be connected to
clamps 40 and 41 eliminating jumper X40 on the
circuit board, paying attention not to invert the
connections (Fig. 3-2).
Important: if the “Comando Amico Remoto”
remote controlV2 or any other On/O chrono-
thermostat is used arrange two separate lines in
compliance with current regulations regarding
electrical systems. No boiler pipes must ever be
used to earth the electric system or telephone
lines. Ensure elimination of this risk before mak-
ing the boiler electrical connections.
On/O digital chronothermostat
Comando Amico Remoto remote controlV2 (CARV2)