Inepro 4PU Series User manual

4PU and 4PS Series MID
Three phase energy meter
User manual
Version: 1.00
© 2021 Inepro B.V. All rights reserved


Inepro Metering - 4PU & 4PS - 3
1 Index
Index
1 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 Certicates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.1 Performance criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
5.2 Basic errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
5.3 Bluetooth specication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
5.4 M-bus communication specications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
5.5 RS485 communication specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.6 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.7 Wire connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.8 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.1 Display part 1 (MID relevant). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
7.2 Display part 2 (MID relevant) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
7.3 Display part 3 (non-relevant) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
7.4 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
7.5 Bluetooth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
7.6 Button settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
7.6.1 Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
7.6.2 Tari . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
7.6.3 S0 output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
7.6.4 Pulse type setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
7.6.6 Modbus ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
7.6.7 Modbus baud rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
7.6.8 Modbus parity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
7.6.9 M-bus ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
7.6.10 M-bus baud rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
7.6.11 Backlight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
7.6.12 Powerdown counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
7.6.13 Trip counter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
7.6.14 OBIS codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
7.6.15 Combination code (Modbus, M-bus & Bluetooth setting only). . . . . . . . . . . . . . . . . . .21
8 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.1 Errors / Diagnostics display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
8.2 Technical support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Appendix 1 - Multi tari function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
A1.1 How to switch between T1 and T2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
A1.2 How to switch between T3 and T4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Appendix 2 - M-bus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
A2.1 Communicating via the M-bus output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
A2.2 M-bus register map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Appendix 3 - Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
A3.1 Communicating via the Modbus output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
A3.2 Modbus register map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Appendix 4 - Bluetooth. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

4 - Inepro Metering - 4PU & 4PS
2 Safety instructions
Information for your own safety
This manual does not contain all of the safety measures for operation of this meter because special operating conditions,
local code requirements or local regulations may necessitate further measures. However, it does contain information
which must be adhered to for your own personal safety and to avoid material damage. This information is highlighted by
a warning triangle with an exclamation mark or a lightning bolt depending on the degree of actual or potential danger:
Warning
This means that failure to observe the instruction can result in death, serious injury or considerable
material damage.
Caution
This means hazard of electric shock and failure to take the necessary safety precautions will result in
death, serious injury or considerable material damage.
Qualied personnel
Installation and operation of the device described in this manual may only be performed by qualied personnel. Only
people that are authorized to install, connect and use this device, who have the proper knowledge about labeling and
grounding electrical equipment and circuits and can do so in accordance with local (safety)regulations, are considered
qualied personnel in this manual.
Use for the intended purpose
This device may only be used for the application cases specied in the catalog and the user manual and only in
connection with devices and components recommended and approved by Inepro Metering B.V.
Proper handling
The prerequisites for perfect, reliable operation of the product are proper transport, storage, installation and connection,
as well as proper operation and maintenance. During its operation certain parts of the meter might carry dangerous
voltages.
• Only use insulated tools suitable for the voltages this meter is used for.
• Do not connect while the circuit is connected to a power or current source.
• Only place the meter in a dry environment.
• The meter is intended to be installed in a Mechanical Environment ‘M1’, with Shock and Vibrations of low signican-
ce and Electromagnetic Environment ‘E2’, as per 2014/32/EC Directive. The meter is intended for indoor use. The
meter shall be installed inside a suitable IP rated enclosure, in accordance with local codes and regulations.
• Do not mount the meter in an explosive area or exposed to dust, mildew and/or insects.
• Make sure the used wires are suitable for the maximum current of this meter.
• Make sure the AC wires are connected correctly before activating the current/voltage to the meter.
• Do not touch the meter’s connection clamps directly with your bare hands, with metal, blank wire or other
conducting material as you will risk an electric shock that could cause possible injury, serious injury or death.
• Make sure the protection covers are replaced after installation.
• Maintenance and repair of the meter should only be carried out by qualied personnel.
• Never break any seals (if present on this meter) to open the front cover as this might inuence the functionality or
accuracy of the meter, and will void all warranty.
• Do not drop, or allow physical impact to the meter as there are high precision components inside that may break
and aect the meter measurement negatively.
• All clamps should be properly tightened.
• Make sure the wires t properly in the connection clamps.
• If the wires are too thin it will cause a bad contact which can spark causing damage to the meter and its
surroundings.

Inepro Metering - 4PU & 4PS - 5
Exclusion of liability
We have checked the contents of this manual and every eort has been made to ensure that the descriptions are as
accurate as possible. However, deviations from the description cannot be completely ruled out, so that no liability can
be accepted for any errors or omissions in the information given. The data in this manual are checked regularly and the
necessary corrections will be included in subsequent editions. If you have any suggestions, please do not hesitate to
contact us.
Subject to technical modications without notice.
Copyright
Copyright Inepro Metering February 2021.
It is prohibited to pass on or copy this document or to use or disclose its contents without express permission of
Inepro Metering BV. Any duplication is a violation of the law and subject to criminal and civil penalties. All rights reserved,
particularly for pending or approved patent awards or registered trademarks.

6 - Inepro Metering - 4PU & 4PS
Thank you for purchasing this energy meter. Inepro has a wide product range of devices. We have introduced a large
number of energy meters on the market suitable for 110V AC to 400V AC (50 or 60Hz). Besides the normal energy
meters we also developed our own pre-paid meters with chip card, chip card re-loaders and a complete PC management
control system. For more information on other products please contact our sales department at sales@ineprometering.
com or visit our website at www.ineprometering.com.
Although we produce this device according to international standards and our quality inspection is very accurate it’s
still possible that this device shows a defect or failure for which we do apologize. Under normal conditions your product
should give you years of trouble free operation. In case there is a problem with the energy meter you should contact
your distributor immediately. Most of our energy meters are sealed with a special seal. Once this seal is broken there is
no possibility to claim any warranty. Therefore NEVER open an energy meter or break the seal of the device. The limited
warranty is 5 years after production date, divided into various periods., after production, and only valid for production
faults.
3 Foreword

Inepro Metering - 4PU & 4PS - 7
4 Certicates
We,
Inepro Metering BV
(supplier’s name)
Pondweg 7
2153 PK Nieuw-Vennep
The Netherlands
(supplier’s address)
declare under our sole responsibility that the product:
4PU and 4PS
Three phase DIN rail Watt Hour meter
(Name, type or model, batch or serial number, possibly source and number of items)
to which this declaration relates in conformity with the following European
harmonized and published standards at date of this declaration:
EN 50470-1:2006
EN 50470-3:2006
EN 61326-1:2020
ETSI EN 301 489-1: V2.2.3 (2019-11)
ETSI EN 301 489-17: V3.2.4 (2020-09)
ETSI EN 300 328: V2.2.2 (2019-07)
EN 62311:2020
(Title and or number and date of issue of the applied standard(s))
Following the provisions of the Directives (if applicable):
2014/32/EU (MID)
2011/65/EU (RoHS)
1907/2006 (REACH)
2014/53/EU (RED)
Nieuw-Vennep, 08-03-2021
Place and date of issue
D. van der Vaart
Name of responsible for CE-marking
This declaration of
Conformity is suitable
to the European
Standard EN 45014
General Criteria for
Supplier’s Declaration
of Conformity. The
basis for the criteria
has been found in
international
documentation,
particularly in
ISO / IEC, Guide 22,
1982, Information on
manufacturer’s
Declaration of
Conformity with
standards or other
technical
specifications

8 - Inepro Metering - 4PU & 4PS
Casing PC ame resistant plastic
Nominal voltage (Un) 230/400V AC (3~)
Operational voltage 3*230/400V ±20%
Insulation capabilities:
- AC voltage withstand 4KV for 1 minute
- Impulse voltage withstand 6KV – 1,2μS waveform
Basic current (Ib) 5A
Maximum rated current (Imax) 65A
Operational current range 0,4%Ib-Imax
Overcurrent withstand 30Imax for 0,01s
Operational frequency range 45-60Hz
Internal power consumption ≤2W/Phase - ≤10VA/Phase (active - reactive)
Test output ash rate (RED LED) 10.000 imp/kWh
Pulse output rate 10.000/2.000/1.000/100/10/1/0,1/0,01 imp/kWh
Pulse width Selectable 2-99ms (depending on pulse output rate setting)
Data store The data can be stored for more than 10 years
without power
5.1 Performance criteria
Operating humidity ≤ 75%
Storage humidity ≤ 95%
International standard EN50470-1/3
Accuracy class B (=1% accuracy)
Protection against penetration
of dust and water IP51
Insulating encased meter of
protective class II
Operating temperature range -40°C - +70°C
5 Specications

Inepro Metering - 4PU & 4PS - 9
Do not exceed the following limits for ambient temperature in combination with conductor cross-section and rated
current:
5.2 Basic errors
0,05Ib Cosφ = 1 ±1,5%
0,1Ib Cosφ = 0,5L ±1,5%
Cosφ= 0,8C ±1,5%
0,1Ib - Imax Cosφ = 1 ±1,0%
0,2Ib - Imax Cosφ = 0,5L ±1,0%
Cosφ = 0,8C ±1,0%
5.3 Bluetooth specication
Protocol BLE 4.2
Frequency range Bluetooth 4.0: 2402 - 2480 MHz (40 CH)
5.4 M-bus communication specications
Bus type M-bus
Baud rate 300, 600, 1200, 2400 (default), 4800 and 9600
Range ≤1000m
Downlink signal Master to slave. Voltage modulation
Uplink signal Slave to master. Current modulation
Cable JYSTY (nx2x0,8)
Protocol EN13757-3
Unit loads 1
Max. number of meters 64 per bus*

10 - Inepro Metering - 4PU & 4PS
5.5 RS485 communication specications
Bus type RS485
Protocol MODBUS RTU with 16 bit CRC
Baud rate 1200, 2400, 4800, 9600 (default), 19200, 38400, 57600 and 115200
Address range 1-247 user settable
Maximum bus load 60 meters per bus*
Range 1000m
*Note that the maximum number of meters is dependent on the converter, baudrate (the higher the baudrate, the
smaller the number of meters which can be used) and the circumstances under which the meters are installed.
5.6 Dimensions
Height without protection cover 92 mm
Height 140 mm
Width 72 mm
Depth 63 mm
Weight 0,34 Kg (net)
5.7 Wire connection
Connection technology Push-in CAGE CLAMP®
Actuation type Lever
WAGO serie 2616
Solid conductor 0.75 … 16 mm² / 18 … 4 AWG
Fine-stranded conductor 0.75 … 25 mm² / 18 … 4 AWG
Fine-stranded conductor; with insulated ferrule 0.75 … 16 mm²
WAGO serie 2604
Solid conductor 0.2 … 4 mm² / 24 … 12 AWG
Fine-stranded conductor 0.2 … 4 mm² / 24 … 12 AWG
Fine-stranded conductor; with insulated ferrule 0.25 … 2.5 mm²
Push-in technology can be used for Solid conductors and ne-stranded conductors with insulated ferrule.
Fine-stranded conductors require opening the levers for connection.
2616
2616 2604
2604

Inepro Metering - 4PU & 4PS - 11
5.8 Connection diagram
4PU - 3P 4W
4PU- 3P 3W Open Delta (Aron)
4PU- 3P 3W Delta
4PU - 1P 2W - Single phase
L1 (in) Phase 1 input - L1 (out) Phase 1 output
L2 (in) Phase 2 input - L2 (out) Phase 2 output
L3 (in) Phase 3 input - L3 (out) Phase 3 output
N Neutral input
4 S0 output 1 (+)
5 Ground (-)
6 S0 output 2 (+)
7 Modbus communication contact A
8 Modbus communication contact B / M-bus communication contact
9 M-bus communication contact
10, 11: Tari switching (230V AC)
L1 (in) Phase 1 input - L1 (out) Phase 1 output
L2 (in) Phase 2 input - L2 (out) Phase 2 output
L3 (in) Phase 3 input - L3 (out) Phase 3 output
N not used
4 S0 output 1 (+)
5 Ground (-)
6 S0 output 2 (+)
7 Modbus communication contact A
8 Modbus communication contact B / M-bus communication contact
9 M-bus communication contact
10, 11: Tari switching (230V AC)
L1 (in) Phase 1 input - L1 (out) Phase 1 output
L2 (in) Phase 2 input - L2 (out) Phase 2 output
L3 (in) Phase 3 input - L3 (out) Phase 3 output
N not used
4 S0 output 1 (+)
5 Ground (-)
6 S0 output 2 (+)
7 Modbus communication contact A
8 Modbus communication contact B / M-bus communication contact
9 M-bus communication contact
10, 11: Tari switching (230V AC)
L1 (in) Phase 1 input - L1 (out) Phase 1 output
L2 (in) not used - L2 (out) not used
L3 (in) not used - L3 (out) not used
N Neutral input
4 S0 output 1 (+)
5 Ground (-)
6 S0 output 2 (+)
7 Modbus communication contact A
8 Modbus communication contact B / M-bus communication contact
9 M-bus communication contact
10, 11: Tari switching (230V AC)
L1L 1 L2 L2 L3 L3
N
10
11
4
5
6789
S01
GND
S02
A
B/BUS2
BUS1
Tariff
IN
L1
OUT
L1
IN
L2
OUT
L2
IN
L3
OUT
L3

12 - Inepro Metering - 4PU & 4PS
4PS - 3P 4W
4PS - 3P 3W Open Delta (Aron)
4PS - 3P 3W Delta
4PS - 1P 2W - Single phase
L1 (in) Phase 1 input - L1 (out) Phase 1 output
L2 (in) Phase 2 input - L2 (out) Phase 2 output
L3 (in) Phase 3 input - L3 (out) Phase 3 output
N Neutral input
4 S0 output 1 (+)
5 Ground (-)
6 S0 output 2 (+)
7 Modbus communication contact A
8 Modbus communication contact B / M-bus communication contact
9 M-bus communication contact
10, 11: Tari switching (230V AC)
L1 (in) Phase 1 input - L1 (out) Phase 1 output
L2 (in) Phase 2 input - L2 (out) Phase 2 output
L3 (in) Phase 3 input - L3 (out) Phase 3 output
N not used
4 S0 output 1 (+)
5 Ground (-)
6 S0 output 2 (+)
7 Modbus communication contact A
8 Modbus communication contact B / M-bus communication contact
9 M-bus communication contact
10, 11: Tari switching (230V AC)
L1 (in) Phase 1 input - L1 (out) Phase 1 output
L2 (in) Phase 2 input - L2 (out) Phase 2 output
L3 (in) Phase 3 input - L3 (out) Phase 3 output
N not used
4 S0 output 1 (+)
5 Ground (-)
6 S0 output 2 (+)
7 Modbus communication contact A
8 Modbus communication contact B / M-bus communication contact
9 M-bus communication contact
10, 11: Tari switching (230V AC)
L1 (in) Phase 1 input - L1 (out) Phase 1 output
L2 (in) not used - L2 (out) not used
L3 (in) not used - L3 (out) not used
N Neutral input
4 S0 output 1 (+)
5 Ground (-)
6 S0 output 2 (+)
7 Modbus communication contact A
8 Modbus communication contact B / M-bus communication contact
9 M-bus communication contact
10, 11: Tari switching (230V AC)
L1
IN
L2 L3 N
L1
OUT
L2
L3
10 11
4
5
6789
Tariff
S01
GND
S02
A
B/BUS2
BUS1
L1
L2
L3
L1
L2
L3
N
L1
IN
L2 L3 N
OUT
10 11
L1L2
L3
4
5
6789
Tariff
S01
GND
S02
A
B/BUS2
BUS1
L1
L2
L3
L1
L2
L3
N
L1 L2 L3 N10 11
L1L2
L3
4
5
6789
Tariff
S01
GND
S02
A
B/BUS2
BUS1
IN OUT L1
L2
L3
L1
L2
L3
L1 L2 L3 N10 11
L1L2
L3
4
5
6789
Tariff
S01
GND
S02
A
B/BUS2
BUS1
IN OUT L1
L2
L3
L1
N

Inepro Metering - 4PU & 4PS - 13
• The connecting wire, connecting the device to the outside circuit, should be sized in accordance with local
regulations for the maximum amount of the current breaker or other overcurrent protection devices used in the
circuit.
• An external switch or a circuit-breaker should be installed on the supply wires, which will be used to disconnect
the meter and the device supplying energy. It is recommended that this switch or circuit-breaker is placed near
the meter because that is more convenient for the operator. The switch or circuit-breaker should comply with the
specications of the building’s electrical design and all local regulations.
• An external fuse or thermal cut-o used as an overcurrent protection device for the meter must be installed on the
supply side wires. It’s recommended that this protection device is also placed near the meter for the convenience
of the operator. The overcurrent protection device should comply with the specications of the building’s electrical
design and all local regulations.
• This meter can be installed indoor, or outdoor enclosed in a meter box which is suciently protected, in
accordance with local codes and regulations.
• To prevent tampering, an enclosure with a lock or a similar device can be used.
• The meter has to be installed against a re resistant wall.
• The meter has to be installed in a well-ventilated and dry place.
• The meter has to be installed in a protective box if the meter is exposed to dust or other contaminants.
• The meter can be installed and used after being tested and can be sealed afterwards.
• The device can be installed on a 35mm DIN rail.
• The meter should be installed on a location where the meter can be read easily.
• In case the meter is installed in an area with frequent surges for example due to thunderstorms, welding
machines, inverters etc., the meter is required to be protected with a Surge Protection Device.
• The device should be sealed immediately after installing it in order to prevent tampering.
6 Installation
Caution
• Turn o and if possible lock all sources supplying the energy meter and the equipment that is connected to it
before working on it.
• Always use a properly rated voltage sensing device to conrm that power is o.
Warning
• The installation should be performed by qualied personnel familiar with applicable codes and regulations.
• Use insulated tools to install the device.
• A fuse, thermal cut-o or single-pole circuit breaker should be tted on the supply line and not on the neutral
line.

14 - Inepro Metering - 4PU & 4PS
7.1 Display part 1 (MID relevant)
Part 1 of the display shows the MID relevant software version number, the meter serial number, the CRC code, the
actual tari and an indication of the MID-relevant measurement units (kWh). Meter serial number and CRC code are
scrolling every 10 seoconds. When Bluetooth communication is activated, icon 1 will be shown. When Modbus or
M-bus communication is activated, icon 2 will be shown on the display.
7.2 Display part 2 (MID relevant)
Part 2 of the display shows the MID relevant measurement values.
OBIS codes are used to identify the corresponding measurement values:
1.8.1: Positive active energy in tari 1
1.8.2: Positive active energy in tari 2
1.8.3: Positive active energy in tari 3 (will be shown in the display when T3 and/or T4 are activated)
1.8.4: Positive active energy in tari 4 (will be shown in the display when T3 and/or T4 are activated)
2.8.1: Negative active energy in tari 1
2.8.2: Negative active energy in tari 2
2.8.3: Negative active energy in tari 3 (will be shown in the display when T3 and/or T4 are activated)
2.8.4: Negative active energy in tari 4 (will be shown in the display when T3 and/or T4 are activated)
The meter has a 6+3 digit display for kWh values. When reaching 999999,999 the kWh value goes back to
000000,000.
7.3 Display part 3 (non-relevant)
Part 3 of the display shows the non-relevant data like current direction, trip counter, reactive energy, power factor,
present quadrant, frequency, active power, apparent power, reactive power, voltage and current.
Scroll through the display pages (Total - L1 - L2 -L3) using the capacitive touch buttons on the frontside of the meter.
7 Operation
1 2

Inepro Metering - 4PU & 4PS - 15
7.4 Settings
Activate settings mode by holding the middle button (*) for >3 seconds.
The following display will appear:
7.5 Bluetooth
Press the middle button to activate Bluetooth:
Scan the QR code on the display using the inepro Metering mobile phone app.

16 - Inepro Metering - 4PU & 4PS
When Bluetooth connection is active, the Bluetooth activation icon will be show on the display:
Go to Appendix 4 - Bluetooth for the inepro Metering mobile phone app user guide.
7.6 Button settings
Settings can also be done using the capacitive touch buttons on the front of the meter. Scroll through the options
using the left << and right >> button. Conrm the setting using the middle button. Select the following page to go to
the settings menu:
Enter the password to get acces to the settings menu (default 0000).
Conrm each digit (1-9) using the middle button:
The settings menu will appear after entering the password correctly:

Inepro Metering - 4PU & 4PS - 17
7.6.1 Password
The button setting function can be protected by setting a password. This password is also valid for settings via Blue-
tooth. The default password is 0000. This password can only be changed using the button function.
7.6.2 Tari
The default tari is 1. The tari can be set to T2, T3 and T4. Tari 1 and 2 are always displayed in part 1 and 2 of the
meters. kWh values in tari 3 and 4 will be added to the automatic scroll in part 2 of the display.
7.6.3 S0 output
The energy meter is equipped with two pulse outputs (forward & reverse or active & reactive) which are optically
isolated from the inside circuit. It generates pulses in proportion to the measured consumption for purpose of remote
reading or accuracy testing.
The pulse output is a polarity dependent, open-collector transistor output requiring an external voltage source
for correct operation. For this external voltage source, the voltage (Ui) should be lower than 27V DC. The maximum
switching current (Imax) is 100mA. To connect the impulse output, connect 5-27V DC to connector xx/xx (collector),
and the signal wire (S) to connector xx/xx (emitter).
The default imp/kWh setting for the S0 output is 1.000. The S0 output setting can be modied to 10.000 / 2.000 /
100 / 10 / 1 / 0,1 / 0,01 imp/kWh.

18 - Inepro Metering - 4PU & 4PS
7.6.4 Pulse type setting
The default pulse type setting is active & reactive. This means that the two pulse outputs pulse based on the active
and reactive energy. The pulse type can be set to forward & reverse, which means that the pulse outputs pulse based
on forward and reverse active energy.
7.6.5 S0 Pulse width
The default S0 pulse width is 30ms. The pulse width setting can be modied to 2-99ms (depending on the imp/kWh
setting).
7.6.6 Modbus ID
The Modbus ID can be set from 1 to 247, the default Modbus ID is 1.
7.6.7 Modbus baud rate
The default Modbus baud rate setting is 9600. The Modbus baud rate setting can be modied to 115.200 / 56.700 /
38.400 / 19.200 / 4800 / 2400 / 1200 / 600 / 300 bps.

Inepro Metering - 4PU & 4PS - 19
7.6.8 Modbus parity
The default Modbus parity setting is even. The Modbus parity can be modied to none or odd.
7.6.9 M-bus ID
The Modbus ID can be set from 0 to 250, the default Modbus ID is 0.
7.6.10 M-bus baud rate
The default M-bus baud rate setting is 2400. The Modbus baud rate setting can be modied to 9600 / 4800 / 1200 /
600 / 300 bps.

20 - Inepro Metering - 4PU & 4PS
7.6.11 Backlight
The meter is equipped with a blue backlight. The backlight can be set to always on, o or button mode.
7.6.12 Powerdown counter
The powerdown counter registers the number of times that the meter has been turned o.
7.6.13 Trip counter
The meter is equipped with a trip counter that can be set to zero by the user. This is the energy calculated based on
the combination code setting (see 7.6.15).
7.6.14 OBIS codes
OBIS codes can be used to identify the corresponding measurement values. OBIS codes are turned o by default.
This manual suits for next models
1
Table of contents
Other Inepro Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Rohde & Schwarz
Rohde & Schwarz CMW-B400B user manual

Konica Minolta
Konica Minolta FD-9 instruction manual

Bayer HealthCare
Bayer HealthCare Clinitek Atlas Service manual

AGS
AGS MERLIN CO2-TFT Installation, operation & maintenance manual

Hanna Instruments
Hanna Instruments LP 2000-11 instruction manual

Ponovo
Ponovo PNS630 user manual