Weatherproof Terminal Module.
P/N: 995010
INSTALLATION MANUAL
Overview
The Weatherproof Terminal Module currently provides the following operations:
1. Single Door PIN code Access control including the “auto area off” and REX/REN button options.
Note: AWiegand Reader can also be connected in parallel with the keypad to provide “PIN or Card” operation.
2. Control and status indication of a single “Associated Area” assigned to the Module, or a User’s “Extra Area”.
The Weatherproof Terminal supports all Concept 3000/4000 1 to 8 digit PIN codes.
The keypad features a CODE lamp (green), an ARMED lamp (red), two general purpose yellow lamps, numeric keys 0 to 9, an OK
key and an ON/OFF key. Beeper feedback is provided for each key press and the beeper can also be controlled by an Auxiliary
output.
Two methods of keypad tamper protection are provided:
-A built-in optical device detects removal of the keypad from its mounting surface.
-Presence of the keypad connections is monitored via the data inputs on the PCB.
In addition to this, a Tamper switch input is also provided on the PCB for cabinet tamper monitoring.
IMPORTANT NOTES:
1) Control Module Firmware must be V5.60 or later.
2) The Weatherproof Terminal is enrolled on the LAN and programmed as a Reader Module. (MENU, 7, 2, 4) When programming;
options relating to “2nd Door / 2nd Lift”, “2 Door Mode”, “Reader 2...” and “Backup Cards” should not be programmed.
3) Separate Inputs are provided for Exit & Entry buttons. Regardless of whether these inputs are used for Exit or Entry buttons, they
must be programmed for Exit button operation. i.e. Select the “B”utton option in the “Exit Options” of the Access Group
assigned to the Door. Note that Review will therefore always record the direction for the button operation as “Exit”.
4) Zones Rnn:Z02 to Z05, Z07 and Z08 do not exist on the Weatherproof Terminal Module and therefore must not be programmed.
5) Auxiliaries Rnn:X07 and X08 do not physically exist on the Weatherproof Terminal Module and therefore can only be used as
phantom Auxiliaries.
Installing the Weatherproof Terminal.
Weatherproof Terminal Parts List
- Weatherproof Terminal Module PCB assembly.
- Inner Range Weatherproof keypad with 1 metre connection cable.
- Installation Manual. (This document)
- Installation Kit in Plastic bag containing:
- 1 x 3 Way Plug on Screw Terminal.
- 3 x 6 Way Plug on Screw Terminals.
- 1 x 5 Way Plug on Screw Terminal.
- 1 x 6.3mm Quick Connect.
- 1 x 500mAAmp Fuse. (Spare)
- 2 x Jumper Link 0.1”.
- 5 x 2k2 End-of-line resistors. (red-red-black-brown-brown)
- 5 x 6k8 End-of-line resistors. (blue-grey-black-brown-brown)
- 1 x 1N4004 protection diodes. (For connecting across lock strike)

WW
WW
Weatherproof Teatherproof T
eatherproof Teatherproof T
eatherproof Terminal Module.erminal Module.
erminal Module.erminal Module.
erminal Module. Installation Manual.
2
Keypad layout and functions.
Lamp 1 Green CODE (Logged on) On while User is logged on.
Lamp 2 Red ARMED Current Area status. Only displayed while logged on. On = Area On.
Lamp 3 Yellow General purpose. Normally connected to Auxiliary 4.
Lamp 4 Yellow General purpose. Normally connected to Auxiliary 5.
Numeric keys PIN code Entry. When logged on, pressing the 0 key will logoff the User.
OK key. Pressed after PIN code to logon.
Door access request while logged on.
ON/OFF keys. Toggle Area state while logged on.
Buzzer. Buzzer control wire (Yellow) may be connected to Auxiliary 6 to provide Entry/Exit delay warning, etc.
(Rxx:X06 will need to be assigned to the required AreaAuxiliary/s)
Lamp 1 Lamp 2 Lamp 3 Lamp 4
Green Red Yellow Yellow
Mounting hole
Numeric keys
ON / OFF key
OK key
Mounting hole
Buzzer

Revision 1.0 March 2006. 3
Installation
Installation environment.
Module PCB: 0º to 40º Celsius and 15% to 85% Relative humidity (non-condensing)
Keypad: -20º to 70º Celsius. Moisture and Dust rating = IP68.
Dimensions.
PCB dimensions: Length: 96mm Width: 96mm
Keypad dimensions: Height: 130mm Width: 81mm Depth: 21mm
Distance between mounting hole centres: 82.2mm
Mounting hole diameter: 4.15mm
Mounting.
1. Choose suitable mounting locations for the keypad and PCB assembly so that:
a) The keypad is at a convenient height for viewing the status lamps and for ease of use.
b) The keypad cable can be terminated into the PCB connectors securely and without strain.
2. a) The PCB assembly can be mounted in a suitable enclosure using the 4 self adhesive PCB standoffs provided, or other suitable
PCB standoffs.
b) One or two “Normally Closed” Tamper switches may be fitted to the enclosure before it is mounted, and wired in parallel
between the “TAMP” and “0V” terminals on T1. (Switch is Open cct when plunger depressed)
3. Connect the keypad cable to the PCB using the plug-on screw terminal connectors. See diagram below.
4. The Module Number is set using DIPswitches 1 to 7 as required. See table on page 6.
Grey
Black
Red
White
Green
Brown
Blue
Violet
Orange
Yellow
Keypad cable
Red +12V power supply
Black 0V power supply
Green Data 0’s
White Data 1’s
Brown LED 1 -Green
Blue LED 2 -Red
Violet LED 3 -Yellow
Orange LED 4 -Yellow
Yellow Buzzer
Grey Tamper
Yellow/Green Earth (Connected to case only)
Multicore cable
from keypad
To building earth
Yellow/Green.
DO NOT
connect to 0V

WW
WW
Weatherproof Teatherproof T
eatherproof Teatherproof T
eatherproof Terminal Module.erminal Module.
erminal Module.erminal Module.
erminal Module. Installation Manual.
4
LAN+
0V
A
B
TAMP
OV
EXTERNAL
PWR SUPPLY
(BATTERY
BACKED)
+
-
Heavy duty Fig. 8 cable (24/0.20 or 14/0.20) recommended
for Ext. Power Supply wiring.
* Note: If required, the LAN to subsequent Modules may
derive +12V from “+VE” of the incoming LAN cable.
From
Previous
module
To
next
module
+ - A B
+ - A B
* Note: If both “LAN +VE” wires provide a Power supply source, the
one that is not required to power the Module MUST NOT be connected to
the Module.
i.e. +VE connections from two different power supply sources must
never be connected together.
From Previous
LAN module To next
module
+ - A B
+ - A B
See Note. *
*
MODULE POWERED FROM THE LAN
ZONE INPUT AND EXIT/ENTRY BUTTON WIRING.
LAN+
0V
A
B
TAMP
OV
Cabling.
LAN and Power Supply Wiring
MODULE POWERED FROM EXTERNAL SUPPLY (Recommended)
Input Wiring
Door Reed and Tongue Sense Inputs are wired using the End-of-Line (EOL) Resistors.
The “REX/REN” button Inputs are wired to the Normally Open contact of the respective button, while the COMMON contact is
connected to 0V. EOL reistors are not required.
REED
0V
REN
TNG
0V
REX
T4
2k2
6k8
Normally Closed
Tamper contact
Norm. Closed
Alarm contact.
(REED /
TONGUE)
Normally Open
Button contact.
(REX / REN)
Notes:
Tongue Sense (“TONG”) wired
as per “REED”.
“REN” button wired as per
“REX”.

Revision 1.0 March 2006. 5
Lock Wiring.
Heavy duty Fig. 8 cable (24/0.20 or 14/0.20) is recommended for all Power & Lock wiring.
CAUTION: A voltage selection link (LK2) for the Lock relay Common contact is provided, and is located next to connector T3.
Note that this link should only be used when switching low-current non-inductive loads.
When controlling locks, always connect the lock as shown below and do not fit link LK2.
REED
0v
REN
TONG
0v
REX
NC
COMM
NO
EXTERNAL
PWR SUPPLY
(BATTERY
BACKED)
-
+
Lock
Strike
1N4004 Protection Diode
(supplied) fitted as close as
possible to the strike.
Cathode (bar) to +VE.
-
+
+VE wired directly to
External Power Supply.
Reader Wiring.
A Wiegand Reader may be wired in parallel with the keypad to provide “PIN or Card” Door access operation.
The Reader supply (+VRD) is fixed at 12V.
i.e. A 5V Reader supply is not available and any Wiegand Reader connected must be able to accept a 12V supply.
Readers with Clock and Data output (e.g. Magnetic Swipe Readers), and Readers that will only operate from a 5V supply are not
supported.
LED and/or beeper control wires provided on the Reader can be wired directly to an appropriate Auxiliary output on T5. (No drop-
ping resistor required) See information supplied with Reader for LED control details.
RELAY T3
(Rnn:X01)
Power
to Lock Power
to Un-Lock
or
T4
KTAMP
0V
+VRD
D1
D0
T2
Black
Red
White
Green
Multicore cable from
Wiegand Reader.
NOTE: Use shielded Data cable. Tycab DMC6702,
Garland MC7-6S, etc. DO NOT use twisted pairs!
Shield.
Connect to Earth terminal if earthing is provided.
Connect to 0V if no earthing is provided.

WW
WW
Weatherproof Teatherproof T
eatherproof Teatherproof T
eatherproof Terminal Module.erminal Module.
erminal Module.erminal Module.
erminal Module. Installation Manual.
6
Module Numbering
The Single Door Access Module is enrolled on the LAN as a Reader Module (R).
The Module number is set using DIPswitches 1 to 7.
The Module number equals n+ 1, where nis the binary number set on DIPswitches 1 to 7.
Module No: DIPswitch: 1 2 3 4567
Binary value: 1 2 4 8 16 32 64
1 off off off off off off off
2 ON off off off off off off
3 off ON off off off off off
4 ONONoff off off off off
5 off off ON off off off off
6 ON off ON off off off off
7 off ON ON off off off off
8 ONONONoff off off off
9 off off off ON off off off
through to
99 off ON off off off ON ON
Fault Lamps
L1 (RX) L2 (TX) EXPLANATION / REMEDY
ON ON Module is un-addressed.
OFF ON Module type unknown. Firmware upgrade required to Control Module.
Flash ON Duplicate Module.
This module number is already in use by a module of the same type.
Flash Flash Module number selected is too big for Control Module RAM size.
Select a lower Module number.
ON OFF Too many modules on Network for Control Module RAM size.
Alternating Flash EEPROM fault. Return for service.
Link Settings
LK1 TERM
Off: Unterminated.
On: Terminated. Only fitted if unit is one of the two furthest Modules from the Control Module.
LK2 RELAY COMMON CONNECTION
Not fitted. Relay common is voltage-free.
+ Relay common is +12V.
0V Relay common is 0V.
CAUTION: Note that this link should only be used when switching low-current non-inductive loads.
When controlling locks, always connect the lock as shown on page 5 and do not fit link LK2.

Revision 1.0 March 2006. 7
THE WEATHERPROOF TERMINAL MODULE PCB
1
2
3
4
5
6
1. Earth. Connect to building earth or electrical earth.
2. LK1. TERM. Fitted only if this unit is one of the two
furthest modules from the Control Module.
3. T1. LAN, External Power & Tamper Switch Connections.
LAN+ LAN +ve connection.
0V LAN 0V (-VE) connection.
A LAN Data A connection.
B LAN Data B connection.
TAMP Tamper Switch input.
0V Ext. Power Supply -VE input.
& Tamper switch 0V return.
See “LAN & Power Supply Wiring” on page 4.
4. F1. 500mA FUSE M205.
MUST BE 500mA. Do not substitute higher values.
5. T2. Keypad & Reader connections.
KTAMP Keypad tamper connection.
0V Keypad/Reader 0 Volt (-ve) connection.
+VRD +12V Keypad/Reader power.
D1 Keypad/Reader Data 1’s input.
D0 Keypad/Reader Data 0’s input.
6. T5. Auxiliary Outputs.
X2. Keypad Lamp 1 (CODE) control.
X3 Keypad Lamp 2 (ARMED) control.
X4 Keypad Lamp 3 (Yellow) control.
X5 Keypad Lamp 4 (Yellow) control.
X6 Spare. May be used for keypad buzzer.
+VRD +12V Auxiliary power. (Note required for
Auxiliaries connected to the keypad)
7. JP3. Factory use only.
8. L1 (RX). LAN Data Transmit
& FAULT DIAGNOSIS
L2 (TX). LAN Data Receive
& FAULT DIAGNOSIS
9. DIPswitch SW1: Switch 1-7. Module number.
(See table on page 6)
10. D0 Data 0’s Reader #.
11. D1 Data 1’s Reader #.
12. LK2. Lock relay Common contact voltage selection.
Only use when switching low-current non-inductive loads.
When controlling locks, connect the lock as shown on
page 5 and do not fit this link.
Not fitted. Common contact is voltage-free.
+ Common contact is +12V.
0V Common contact is 0V.
13. T3. Lock Relay Connections. (Rnn:X01)
See “Lock Wiring” on page 5.
14. T4. Input connections.
REED Reed Switch Input. *1
(Zone 1 I/P)
0V 0 Volt return for Input connections.
REN Entry Button I/P. *2
TNG 1 Optional Tongue Sense I/P. *1 & 3
OR Zone 6.
REX Exit Button Input. *2
*NOTES:
1. End-of-line (EOL) Resistors required.
2. EOL’s NOT required. See Note 3 on page 1.
3. “Tongue Sense” selected in Reader Module options.
7
8
9
10
11
12
13
14

WW
WW
Weatherproof Teatherproof T
eatherproof Teatherproof T
eatherproof Terminal Module.erminal Module.
erminal Module.erminal Module.
erminal Module. Installation Manual.
8
Due to on-going product development this manual is subject to change without notice.
© Inner Range Pty Ltd. 2006. Part No: 635010
Specifications
Electrical.
Power Supply Input: 11V to 14V DC
Current Consumption. Standby: 25mA.
Logged on: 35 to 40mA.
X01 (Lock relay) active only. 60mA.
All Auxiliaries active: (Lock relay, keypad lamps and beeper all on) 105mA.
(These figures do NOT include current drawn by any Reader connected, or by any device connected to theAuxiliary outputs other than
the weatherproof keypad connections)
NOTE: Allow 50 to 120mA for small Prox Reader (~10cm range)
Allow 120 to 180mA for standard Prox Reader (~15cm range)
These values are general approximations.
See information supplied with Reader for actual current consumption.
Lock Relay Contacts:
Voltage: 30V DC maximum.
Current: 750mA maximum.
Fuse Protection: 500mA Reader Power Fuse.
Reader current must not exceed 400mA.
ALWAYS REPLACE WITH SAME FUSE TYPE AND VALUE!
Physical.
Installation Environment.
Module PCB: 0º to 40º Celsius and 15% to 85% Relative humidity (non-condensing)
Keypad: -20º to 70º Celsius. Moisture and Dust rating = IP68.
PCB dimensions:
Length: 96mm
Width: 96mm
Keypad dimensions:
Height: 130mm
Width: 81mm
Depth: 21mm
Distance between mounting hole centres: 82.2mm
Mounting hole diameter: 4.15mm
Other manuals for 3000
2
This manual suits for next models
1
Table of contents
Other Inner Range Keypad manuals