manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Inovonics
  6. •
  7. Security Sensor
  8. •
  9. Inovonics EN1262HT User manual

Inovonics EN1262HT User manual

12.9.21 357-00056-01 Rev A © Inovonics, 2021 - www.inovonics.com
EN1262HT High Traffic Motion Detector
Installation and Operation Manual
1 Overview
The EN1262HT high traffic motion detector solves the battery limitation
problems of motion sensors in commercial applications through an
intelligent sleep timer and low current technology. It features a pet immune
PIR detection element, and wall and housing tamper switches.
1.1 Inovonics Contact Information
If you have any problems with this procedure, contact Inovonics technical
support:
• E-mail: [email protected].
• Phone: (800) 782-2709; (303) 939-9336.
2 Installation and Startup
2.1 Installation Notes
• These products are designed to be maintained by professional
security technicians.
• Products are tested for indoor use.
• All products should be manually tested weekly.
2.2 Mount the Housing and Install the Battery
1. Loosen the captive housing screw.
2. Open the housing.
Figure 1 Open the housing
3. Remove the EN1262HT from the mounting bracket per Figure 2.
Figure 2 Remove the EN1262HT from the mounting bracket
4. Noting the detection coverage in Figure 3, determine mounting location.
• Avoid areas facing direct sunlight, areas that may change temperature
rapidly, and areas where there are air ducts or substantial airflows.
• The recommended mounting height is 6.5 feet to 7.5 feet
(2.1 to 2.3 m).
Figure 3 EN1262HT detection coverage area
For product and installation videos visit us at
www.inovonics.com/videos or use the QR
code below.
TOP VIEW
along side wall
7.2 ft
26.2 ft
6.6 ft
13.1 ft
0
89°
37 ft
26.2 ft
37 ft26.2 ft
Side VIEW
6.6 ft
13.1 ft
26.2 ft
12.9.21 357-00056-01 Rev A © Inovonics, 2021 - www.inovonics.com 2
5. Use the included mounting screws to mount the EN1262HT.
• To mount on the wall, see Figure 4.
• To mount in a corner, see Figure 5.
Figure 4 Wall mount configuration
Figure 5 Corner mount configuration
6. Install the battery per Figure 6.
Figure 6 Install the battery
Note: When disposing of this device or depleted batteries, please do so in
accordance with federal, state and local regulations.
2.3 Select Pulse Count
The pulse count options provides control for difficult operating
environments. Automatic pulse count is recommended for reliable
operation in environments subject to temperature fluctuation that can cause
false alarms. The single pulse count mode is more sensitive to minor
temperature variations, and should be used in sites where variant heat
sources will not cause alarms. Automatic pulse count is the factory default
because it allows more reliable operation in environments subject to
temperature fluctuation. To select pulse count:
1. Press the tamper button five times within three seconds.
Figure 7 Press the tamper button
2. Wait for the green LED to blink five times, then:
• Press the tamper button one time within three seconds to select single
pulse count.
12.9.21 357-00056-01 Rev A © Inovonics, 2021 - www.inovonics.com 3
• Press the tamper button two times within three seconds to select
automatic pulse count.
3. Confirm your selection.
• The green LED will blink once to indicate single pulse count has been
selected; twice to confirm automatic pulse count has been selected.
2.4 Select Fixed/Variable Sleep Time
The sleep time setting provides control for normal or high-traffic operating
environments. When set to fixed, if the EN1262HT senses motion, it will
transmit an alarm, then enter sleep mode for 180 seconds; if motion is
sensed when the sleep time has expired, the EN1262HT will transmit
another alarm. When set to variable, if the EN1262HT senses motion, it will
transmit an alarm, then enter sleep mode for 180 seconds; if motion is
sensed before the sleep time has expired, the EN1262HT will restart the
180 second interval. Variable sleep time is the default setting as shipped
from the factory. To select sleep time:
1. Press the tamper button four times within three seconds.
2. Wait for the green LED to blink four times, then:
• Press the tamper button one time within three seconds to select fixed
sleep time.
• Press the tamper button two times within three seconds to select
variable sleep time.
3. Confirm your selection.
• The green LED will blink once to indicate fixed sleep time has been
selected; twice to confirm variable sleep time has been selected.
2.5 Register the Transmitter
The EN1262HT must be registered with the system receiver in order to be
monitored and supervised. Each EN1262HT has a unique factory-
programmed identification number. Refer to the receiver, network
coordinator or control panel installation instructions for details on
registering a transmitter.
1. When prompted to register the device, remove and replace the battery.
Note: Registration can only occur upon battery installation.
2. Replace the housing cover.
Caution: The EN1262HT should be tested after registration to ensure
operation. To test the EN1262HT, activate each of the conditions and
ensure an appropriate response.
3 Test the EN1262HT
When in walk test mode the test LED will light red every time the
EN1262HT senses motion. The unit will not transmit alarm signals during
this test period. Once initiated, the walk test will last for ten minutes and
then the EN1262HT will automatically return to normal operation. To initiate
a walk test:
1. Press the tamper button three times within three seconds.
Note: The test LED only lights red during the walk test.
4 Specifications
Dimensions: 5.2” x 2” x 2.4” (132 mm x 50 mm x 60 mm).
Weight: 4.2 ounces (120 grams)
Operating temperature: 32°F to 120°F (0°C to 49°C).
Humidity: 0 - 93% (non-condensing).
Battery: Two Energizer L91 AA lithium 1.5V batteries.
Typical battery life: Three years.
Tamper: Housing and wall.
PIR: Quad element PIR.
Coverage area: 26’ (8m).
Warm up period: 40 seconds.
Check-in time: Three minutes.
5 Television and Radio Interference
This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
in a residential installation. This equipment generates, uses and can
radiate radio frequency energy and, if not installed and used in accordance
with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
6 FCC Part 15 and Innovation, Science and
Economic Development Canada (ISED)
Compliance
This device complies with part 15 of the FCC Rules, and ISED license-
exempt RSS standard(s). Operation is subject to the following two
conditions: (1) this device may not cause interference, and (2) this device
must accept any interference that may cause undesired operation of the
device.
Le présent appareil est conforme aux CNR Innovation, Sciences et
Développement économique Canada applicables aux appareils radio
exempts de licence. L'exploitation est autorisée aux deux conditions
suivantes: (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur
de l'appareil doit accepter tout brouillage radioélectrique subi, même si le
brouillage est susceptible d'en compromettre le fonctionnement.
Caution: Changes or modifications not expressly approved by the party
responsible for compliance could void the user's authority to operate the
equipment.
7 Radiation Exposure Limits
7.1 FCC
This equipment complies with FCC radiation exposure limits set forth for an
uncontrolled environment. In order to avoid the possibility of exceeding the
FCC radio frequency exposure limits, human proximity to the antenna shall
not be less than 20 cm during normal operation and must not be co-located
or operating in conjunction with any other antenna or transmitter.
7.2 ISED
This equipment complies with ISED RSS-102 radiation exposure limits set
forth for an uncontrolled environment. This transmitter must be installed to
provide a separation distance of at least 20 cm from all persons and must
not be co-located or operating in conjunction with any other antenna or
transmitter.
Cet équipement est conforme avec ISED RSS-102 des limites d'exposition
aux rayonnements définies pour un environnement non contrôlé. Cet
émetteur doit être installé à au moins 20 cm de toute personne et ne doit
pas être colocalisé ou fonctionner en association avec une autre antenne
ou émetteur.

Other Inovonics Security Sensor manuals

Inovonics EE1265 EchoStream User manual

Inovonics

Inovonics EE1265 EchoStream User manual

Inovonics EE1261 User manual

Inovonics

Inovonics EE1261 User manual

Inovonics D-TECT GJD1030 User manual

Inovonics

Inovonics D-TECT GJD1030 User manual

Inovonics EN1266 User manual

Inovonics

Inovonics EN1266 User manual

Inovonics EN1260EchoStream User manual

Inovonics

Inovonics EN1260EchoStream User manual

Inovonics EchoStream ES1260 User manual

Inovonics

Inovonics EchoStream ES1260 User manual

Inovonics EN1263 User manual

Inovonics

Inovonics EN1263 User manual

Inovonics EN1248 User manual

Inovonics

Inovonics EN1248 User manual

Inovonics EN1751 User manual

Inovonics

Inovonics EN1751 User manual

Inovonics EE1260 EchoStream User manual

Inovonics

Inovonics EE1260 EchoStream User manual

Inovonics EN1751 User manual

Inovonics

Inovonics EN1751 User manual

Inovonics Bosch Appliances Home Security System ES1260 User manual

Inovonics

Inovonics Bosch Appliances Home Security System ES1260 User manual

Inovonics EchoStream ES1265 User manual

Inovonics

Inovonics EchoStream ES1265 User manual

Inovonics Frequency Agile FA206C User manual

Inovonics

Inovonics Frequency Agile FA206C User manual

Inovonics EE1261 User manual

Inovonics

Inovonics EE1261 User manual

Inovonics EN1245 User manual

Inovonics

Inovonics EN1245 User manual

Popular Security Sensor manuals by other brands

Visonic CH-1000 installation instructions

Visonic

Visonic CH-1000 installation instructions

industrie technik SIR-PW instructions

industrie technik

industrie technik SIR-PW instructions

Dyacon LD-1 manual

Dyacon

Dyacon LD-1 manual

Plugwise Scan manual

Plugwise

Plugwise Scan manual

Viking LDB-2 product manual

Viking

Viking LDB-2 product manual

LightPro 227A user manual

LightPro

LightPro 227A user manual

Amprobe RLD-1 user manual

Amprobe

Amprobe RLD-1 user manual

Hytronik Dual Sense HIM16 manual

Hytronik

Hytronik Dual Sense HIM16 manual

Servodan niko PLUS 41-800 user guide

Servodan

Servodan niko PLUS 41-800 user guide

Profort luxSpot manual

Profort

Profort luxSpot manual

ZyXEL Communications SHD1110 quick start guide

ZyXEL Communications

ZyXEL Communications SHD1110 quick start guide

PCB Piezotronics ICP M260A01 Installation and operating manual

PCB Piezotronics

PCB Piezotronics ICP M260A01 Installation and operating manual

Ezviz T6 quick start guide

Ezviz

Ezviz T6 quick start guide

QOLSYS IQ Motion QS1200-P01 installation manual

QOLSYS

QOLSYS IQ Motion QS1200-P01 installation manual

Viessmann 5206 Operation manual

Viessmann

Viessmann 5206 Operation manual

jablotron JA-187P manual

jablotron

jablotron JA-187P manual

Zircon Leak Alert + LED! user manual

Zircon

Zircon Leak Alert + LED! user manual

Alula RE610P manual

Alula

Alula RE610P manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.