
© Intatec Ltd 2023 3
Preparation for installation
Flush the water supply pipes thoroughly prior to installation. Do not allow debris, PTFE tape or
any metal particles to enter the system.
Important: All plumbing is to be installed in accordance with applicable codes and
regulations.
Important: When fitting/installing a heat pump system or components it is essential that the
correct insulation is used and properly sealed to reduce the heat loss from the system,
maintaining the system efficiency.
Installation
The Zero anti-freeze valve must only be installed in a vertical position, with the outlet facing
downwards, to allow the draining water to flow out free from obstructions.
The Zero antifreeze valves must be installed outdoors, where the lowest temperatures can be
reached if the heat pump is not operating.
The Zero anti-freeze valve should be properly insulated and sealed to reduce heat loss. Only
the vacuum breaker and discharge point should be exposed.
The valve(s) must also not be placed close to heat sources which could interfere with their
function.
For the valve(s) to work properly, keep the system under pressure at all times.
Most installations only require one anti-freeze valve, located outside and at the lowest point in
the system.
We recommend at least 15cm clearance between the valve and the
ground as discharged water could freeze and hinder the operation of
the valve.
The discharge from anti-freeze valves must be collected in a suitable
drain and routed to a suitable collection point.
If a second valve is required, Inta recommend leaving at least 10 cm
between the valves to avoid water discharging onto the lower valve.
5cm