SECTION 7 - The HIU Controller rst power up and set up
Page 19
SECTION 10 - Fault nding Guide
05/20 E&OE
Ref REPORTED ISSUES Trouble Shoong Checklist
1The water from the hot taps is COLD.
First check………..Is the unit going into hot water mode?
No ow or insucient ow through the ow sensor or ow sensor
not working.?
• Is there power to the HIU?
• Possible blockages – if there is heat coming into the HIU
from the communal heang system, follow the path
through the Strainer, PICV, Diverter ?
• Plate Heat Exchanger blockage, possibly scale. If suspect-
ed take the necessary steps to remove and clean (Fig 8B
in the Secon Maintenance)
Once blockages are cleared, then reconnect the unit, and fol-
low the commissioning instrucons.
2There is NO WATER at the Hot Taps. • Is there water at the cold taps? If not, check the mains
stop tap. If it is found to be closed, open it and check the
fault is resolved.
• Are the HIU isolaon valves open or closed?
If not check for blockages on the cold water supply pipe.
Check all lters and clean if blocked.
3Insucient Hot Water at the taps, but no error codes at the
Controller
First check ………….. Is it a ow or temperature problem?
Is the primary ow sucient?
Low primary ow caused poor or no DHW performance!
If all checks prove the HIU is working correctly,
• Is there a bypass ed on the primary before the HIU,
and it has been le open? CLOSE the valve, the HIU will
now work as designed.
• Is the TMV set at the correct temperature? Has it been
tampered with or reset in error? Set to 57C
• Is there enough FLOW at the HIU? If the supply pumps
have not been designed to the required ow of the HIU,
then DHWS will not be sucient
• Similar for pipework, if not sized correctly, the HIU will
not be able to deliver to its designed output
4• No Room Heang
• Radiators are COLD.
• Under Floor Heang is installed Floor is COLD.
• No Room Heang or Hot Water
• Check the ambient temperature. Is the reason that the
room thermostat seng is too low to switch on the
heang?
• system low pressure. Has the safety valve discharged?
Check system pressure and top up if necessary.
• Air blockage in the radiators
• Check the Circulang Pump (see LED lights on the pump
which can warn of a problem or a fault). Is the pump fully
operaonal?
• Is the controller set up correctly? See Installer sengs
• Is the Room thermostat wired correctly? Is it working?
• Check that the communal heang is supplying heat to the
unit
• Check then that the isolaon valves to the unit are open.
• Is the Bypass Valve open on the valve above the HIIU?
5The Control mode seems to be stuck in either Heang or Hot wa-
ter funcon, and wont change even if either the room stat or ow
switch is disconnected.
• A PCB in the Controller is damaged. Look for the cause
rst before replacing. Usual suspect is that a 230v supply
has been connect in error to a zero volt connecon,
either the T1 / T2 connecon for the room stat or on the
AUX plug for pre-payment connecon
10.2 Performance issues where no fault code is displayed