manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. UltimateAir
  6. •
  7. Heating System
  8. •
  9. UltimateAir RecoupAerator 2000DX Safety guide

UltimateAir RecoupAerator 2000DX Safety guide




178 Mill Street
Athens, Ohio 45701
740.594.2277
ultimateair.com
[email protected]

Thank you for your purchase of a RecoupAerator 2000DX, the most advanced energy recovery
ventilation system available today! Your RecoupAerator 2000DX is designed to bring fresh,
filtered air into your building while simultaneously exhausting stale air.
The 2000DX is an Energy Recovery Ventilator (ERV), meaning the RecoupAerator recovers and
transfers air temperature and moisture from the stale outgoing air to the incoming fresh air.
No matter what the season, you stay comfortable while breathing fresh clean air.
In addition to having an energy transfer rating of up to 95%, the RecoupAerator moderates
indoor humidity in the winter and turns away outdoor humidity in the summer.






The RecoupAerator 2000DX is a modular unit with separate housings for the fans and heat
recovery wheel. The Fan Housing contains the intake and exhaust fans and their associated
controls while the Wheel Housing contains the heat recovery wheel and its respective drive
components. The two housings are coupled via external draw latches and join with an
airtight seal. The heat recovery wheel is made up of removable cartridge filter inserts
which contain the heat recovery and filter material. The cartridge inserts allow the heat
recovery and filter material to be easily removed and cleaned. Both housings sit on a
vibration isolating rubber pad on the included base which has vibration dampening,
adjustable height feet. The 2000DX controls are custom per installation.
The 2000DX has four 18” dia. duct connections. Please see illustrations contained in this
manual. Both housings have removable doors at each duct connection for access to the
interior for maintenance. All user performed maintenance will occur in the Wheel Housing.
The Fan Housing contains no user adjustable or replaceable parts.

Patented random fiber matrix rotary
energy recovery core
oStainless steel rotary wheel
oWashable
oElectronically commutated DC
motor for efficient wheel speed
control
Backward curve electronically
commutated DC motorized impellors (2)
Variable air flow
External electrical connection and low
voltage controls
Fully insulated housing
Exterior powder coat/painted steel
MERV 8-12 filtration

Economic cooling control
CO2 based demand ventilation control
Duct pressure/occupancy demand
control
Fully programmable flow controls

Case: 16 gauge baked powder coat sheet steel insulated with 1.5
inch EPS with flame retarder additive.
Blowers: Two maintenance free EBM backward inclined motorized
ECDC impellers with permanently lubricated sealed ball
bearings and thermal overload protection.
Wheel motor: Maintenance free ECDC motor with permanently lubricated
sealed ball bearings and thermal overload protection.
Energy Recovery Core: The energy recovery core is manufactured from a blend of
visil and nylon designed to transfer both sensible and latent
heat. The core also acts as the MERV 8-12 filter.
Controls: Standard control is on/off function with capability of setting
continuous flow within the operating flow range of 200-2000
CFM. Boost input, external control input, pressure input are
available.
Serviceability: The unit is designed in two main housings (wheel housing and
fan housing). The unit can be split in two for transport,
service, and installation. Each of the two housings have two
doors for ease of service. The wheel is accessible for cleaning
without removal-or easily removed for more detailed
cleaning.
Mounting: Unit comes with a vibration mounting stand. Any other
orientation is acceptable with the proper designed mount and
access.
 The RecoupAerator is warranted to be free from defects in material and
workmanship, and all parts for a period of 2 years from purchase date.
The energy recovery core is warranted for 5 years with a proper yearly cleaning schedule.

ULTIMATEAIR MODEL: 2000 DX
US Units
Metric Units
FLOW
200 –2000 CFM
340 –3740 CMH
ASE
92% - 95%
TRE
44% - 53%
CORE
Patented rotary random matrix polymer
FILTRATION
MERV 8 - 12
EU 6 - 7
ELECTRICAL
208-240VAC, 25 Amp, 50/60 Hz, Single phase
DIMENSIONS
64 H x 64 W x 42 D (inch); 700 lbs.
1.63 H x 1.63 H x 1.07 D
(meter)
DUCT
4 Round Collars @ 18 Dia (inch)
4 Round Collars @ 458 Dia
(mm)
MAINTENANCE
Yearly filter service –light maintenance



STATION
1 outside
supply
2 inside
supply
3 inside
exhaust
4 outside
exhaust
Temperature [C]
34.7
26.0
24.0
32.6
Relative Humidity
[%]
50.3
62.5
49.5
43.9
SRE: 70% TRE: 53% LPC: 0.43 ASE: 85%
Temperature [C]
0.0
20.3
22.0
4.8
Relative Humidity
[%]
75.3
37.8
39.4
76.5
SRE: 83% TRE: 79% LPC: 0.69 ASE: 96%
SRE: Sensible recovery effectiveness
TRE: Total recovery effectiveness
LPC: Latent performance coefficient
ASE: Apparent sensible effectiveness

PWM
Power
Flow
Watt/CFM
command
watt
cfm
Low
18%
129.5
240
0.54
Med
42%
462
720
0.64
Med - Hi
65%
1295
1210
1.07
High
100%
2730
1795
1.52

Install the 2000DX in a position where ventilation ducts can be easily run to each of the
four duct connection points and there is adequate room to access each door on the unit for
maintenance purposes. (See Airflow Diagrams for duct connection locations and airflow
designations, these are also labeled on the unit.) It is recommended that there be at least
36” of clearance at each duct connection point to ensure there is enough room to remove
the doors. To facilitate easy duct removal for maintenance, make a portion of each duct
section, 24” to 36”, easily removable.













The 2000DX is supplied ready to be hard wired to a building power system. Terminal blocks
are supplies in the electronics cover of the Fan Housing to connect power to. To connect
the power wiring, remove the four sheet metal screws holding on the electronics cover.
Be careful when removing the cover on the Fan Housing, as the control knob is in some
configurations affixed to the cover. Wire the terminal blocks as shown in the illustrations.
Please see the Diagrams for additional reference.
Always wait at least 60 seconds before turning power back on.
Fan Housing Wiring Arrangement
The Fan Housing should be wired to a 240 VAC, single phase, 50 / 60 Hz dedicated circuit
with a maximum service rating of 15 Amps.










The DX2000 is set to provide a constant pressure inside the main duct despite the flow
changes. The main control board DCC7545 and a feedback pressure transducer: Veris
PXDLX01S are used to accomplish the function. Both the DCC7545 and the transducer are
powered by the 24VAC power.
The transducer is mounted on the duct monitoring the inside pressure. The output signal is
a DC signal varying from 0V~10V. The DCC7545 takes the signal as a feedback and uses the
PID control strategy to maintain a constant pressure inside the duct which can be set by
three jumpers on the DCC7545.
Model: PXDLX01S Manufacturer: VERIS INDUSTRIES
Jumper Settings:
JP8 Set to FAST
JP7 Set to IN W.C
Jp5 Set to UNI
JP4 Set to 10V
OUTPUT Set to Volt
Rotary Switch Position:
The position of the flow transducers rotary switch corresponds with the RecoupAerator Main
Control Board JP5.
Example: Transducer Rotary Switch in Position 2 requires the RecoupAerator JP5=0
Transducer Rotary Switch in Position 3 requires the RecoupAeraotor JP5=1
Position 0 - 0.1 inch w.c.
Position 1 - 0.25 inch w.c.
Position 2 - 0.5 inch w.c.
Position 3 - 1.0 inch w.c.


















The DCC7545 is programmed to maintain constant duct pressure
Set the Pressure Control Point
JP5=0 Range 0.5IN W.C.
oJMP2=0 JMP3=0 0.08 IN W.C.
oJMP2=0 JMP3=1 0.125 IN W.C.
oJMP2=1 JMP3=0 0.25 IN W.C.
oJMP2=1 JMP3=1 0.5 IN W.C.
JP5=1 Range 1.0 IN W.C.
oJMP2=0 JMP3=0 0.1 IN W.C.
oJMP2=0 JMP3=1 0.3 IN W.C.
oJMP2=1 JMP3=0 0.5 IN W.C.
oJMP2=1 JMP3=1 0.7 IN W.C.
Manual Override is allowed in some scenarios.
To enable override, JP4= 1
When the override is not enabled, VR and BLWR must connected together via jumper wire.
JP4=1 JP3=REM Wall Controller Override
JP4=1 JP3=0~10V 0~10V input Override
JP4=0 No Override











When the RecoupAerator is wired directly to the optional CO2 monitor, the air flow will be
controlled by the CO2 level input. The CO2 monitor will respond approximately as follows:
<800 ppm CO2: lo flow 240 CFM
800-1000 ppm CO2: med flow 720 CFM
1000-1200 ppm CO2: med hi flow 1210 CFM
>1200 ppm CO2: hi flow 1795 CFM
The control will default to the higher flow position –being the command from the CO2
monitor or via the dial control.



The RecoupAerator is EconoCool-equipped, so that you can make use of outside air in
summer (e.g., during the night) to cool your building, thereby providing AC energy savings.
Using a temperature sensor on the incoming air stream and a sensor on the room
temperature, the RecoupAerator automatically stops energy recovery at some preset
certain conditions. The user can select between the presets by changing JP2~JP6.
178 Mill Street
Athens, Ohio 45701
740.594.2277
ultimateair.com
[email protected]
For more information and/or ordering replacement parts, please contact UltimateAir Inc.
Revised: 9.19.2013 by MB

Other UltimateAir Heating System manuals

UltimateAir 200DX Installation and operating instructions

UltimateAir

UltimateAir 200DX Installation and operating instructions

Popular Heating System manuals by other brands

flamco Flexcon P Installation and operating instructions

flamco

flamco Flexcon P Installation and operating instructions

Vents AOW 25 user manual

Vents

Vents AOW 25 user manual

Monitor GF3800 Servise manual

Monitor

Monitor GF3800 Servise manual

Hotstart OCLE Installation & operation manual

Hotstart

Hotstart OCLE Installation & operation manual

RenewAire EV Premium ERV Series Installation, operation and maintenance manual

RenewAire

RenewAire EV Premium ERV Series Installation, operation and maintenance manual

BoilerMag BM22 Installation & servicing instructions

BoilerMag

BoilerMag BM22 Installation & servicing instructions

Burnham BASE-RAY 81441001R8-3/06 installation manual

Burnham

Burnham BASE-RAY 81441001R8-3/06 installation manual

Vortice VORT INVISIBLE MINI Instruction booklet

Vortice

Vortice VORT INVISIBLE MINI Instruction booklet

ubbink Ubiflux Series manual

ubbink

ubbink Ubiflux Series manual

Ambrell EasyHeat 0112 Technical handbook

Ambrell

Ambrell EasyHeat 0112 Technical handbook

Wood master 3300 Installation, operating and maintenance manual

Wood master

Wood master 3300 Installation, operating and maintenance manual

A2B Accorroni A CFR+ 40 manual

A2B Accorroni

A2B Accorroni A CFR+ 40 manual

Viessmann VITOBLOC 200 Technical description

Viessmann

Viessmann VITOBLOC 200 Technical description

Valeo spheros thermo 230 Workshop manual

Valeo

Valeo spheros thermo 230 Workshop manual

Lenz rcB 1200 manual

Lenz

Lenz rcB 1200 manual

Laars NEOTHERM NTH User information

Laars

Laars NEOTHERM NTH User information

Salda RIS 700PE EKO 3.0 Technical manual

Salda

Salda RIS 700PE EKO 3.0 Technical manual

NuAire ecosmart SQURBO XBOX Installation, operating and maintenance instructions

NuAire

NuAire ecosmart SQURBO XBOX Installation, operating and maintenance instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.