Integra BCR-S Mini G2 User manual

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page 1
SystemHouse Solutions
Access Control –
and Security Management System
Installation manual
BCR-S Mini G2

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page 2
SystemHouse Solutions
This document is Copyrighted ©2019 by SystemHouse Solutions AB. All rights reserved.
It may not be reproduced, modified, displayed transferred or copied in any form, in any matter or on any
media, in whole or in part, without the express written permission of SystemHouse Solutions AB.
SystemHouse Solutions AB reserves the right to make changes to this document and to the product
(software and hardware) described herein without notice.
SystemHouse Solutions AB assumes no responsibility for or liability for errors contained in this guide or for
incidental, special or consequential damages arising out of the use of this guide in operating the system.
All product names and trademarks mentioned in this document belong to their respective owners.

1-981-2181-GB, 2021-03-16 Contents Page: 3
SystemHouse Solutions
Table of contents:
1SYSTEM OVERVIEW ................................................................................ 4
1.1 PARTS LIST ........................................................................................................4
1.2 TECHNICAL SPECIFICATIONS.................................................................................4
1.3 ARTICLE NUMBERS..............................................................................................5
1.3.1 Accessories......................................................................................................................... 5
2SAFETY INSTRUCTIONS .......................................................................... 6
3INSTALLATION PROCEDURE .................................................................. 7
3.1 DEVICE OVERVIEW ..............................................................................................8
3.2 OPENING DEVICE ................................................................................................9
3.3 MAXIMUM TORQUE FOR BOX INSTALLATION ...........................................................9
3.4 INSTALLATION ON METAL SURFACES .................................................................... 10
3.5 WALL TAMPER.................................................................................................. 10
4POWER SUPPLY...................................................................................... 11
4.1 POWER REQUIREMENTS ......................................................................................11
4.1.1 Power supply.................................................................................................................... 11
5COMMUNICATION AND ADDRESS .........................................................12
5.1 SETTING ADDRESS............................................................................................. 12
5.1.1 Address setting on reader ...............................................................................................12
5.2RS485 COMMUNICATION LINE............................................................................ 14
5.2.1 Line installation ...............................................................................................................15
5.2.2 Line termination ..............................................................................................................16
5.2.3 Recommended cable ........................................................................................................16
5.2.3.1 PTS-HF-2x2x0.6......................................................................................................................... 17
5.2.4 RS485 network topology and termination principles ..................................................17
6SERVICE ROUTINES .............................................................................. 18
6.1 PERIODICAL SERVICE CHECK .............................................................................. 18
6.2 FIXING COMMON ISSUES WITH THE READER ......................................................... 19
6.2.1 No communication with the Reader...............................................................................19
6.2.2 Reader is not working .....................................................................................................19
7ATTACHMENTS...................................................................................... 20
7.1 CONSTRUCTION ............................................................................................... 20
7.2 FUNCTIONS ..................................................................................................... 20
7.3 BCR-S MINI G2 AS A PART OF DOOR ENVIRONMENT .............................................. 21
7.4 DRAWINGS.......................................................................................................22
7.4.1 Dimensions ...................................................................................................................... 22
7.5 HISTORY..........................................................................................................23

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 4
SystemHouse Solutions
1 System Overview
This manual provides instructions for installation, cabling, power supply evaluation for BCR-S Mini
G2.
1.1 Parts List
Supplied:
I. BCR-S Mini G2 1 pcs
II. Connector 1 pcs
III. Wall tamper spring 1 pcs
IV. Quick Installation Guide` 1 pcs
V. Drilling pattern 1 pcs
VI. Opening Tool xCR-SD/S-Mini G2 1 pcs
Not supplied
I. Instructions for other devices that will be connected to the BCR-S Mini G2.
1.2 Technical specifications
Power supply Typical/Min/Max 24V DC/20VDC/30VDC
Power consumption Typical/Max at 24V 20 mA/25 mA
Enclosure IP 65
Operating temperature -25oto +70oC
Dimensions NET (L/W/H) 76.5/45/20 mm
Weight NET 46 g
Color NCS 8500-N
NCS 6502-B
Communication RS485

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 5
SystemHouse Solutions
1.3 Article numbers
44 28 03 55 BCR-S Mini G2
1.3.1 Accessories
There are several accessories types available:
44 28 02 80 Installation plate for xCR-S (Mini) G2
44 28 02 75 Opening Tool xCR-SD/S (Mini) G2
44 28 50 21 Flashcable for xCR G2

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 6
SystemHouse Solutions
2 Safety Instructions
The following safety instructions should observed during installation, maintenance and standard
use.
•Installation and service should only be performed by qualified personnel.
•If there exist local regulations, these must be followed. This safety information is
supplement to local regulations.
•Reader must be disconnected from voltage before installation and service.
•Do not modify any components or part of device.
•All reparation should be performed only by the manufacturer.

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 7
SystemHouse Solutions
3 Installation Procedure
Installation procedure consist of evaluation of power requirements, mounting accessories, power
and communication lines wiring to S-Node G2, C-Node G2, Moveo, Moveo XL mounting,
connecting cables, setting switches and verification.
Set the device address according requirements. Default address is “2”. For setting
follow procedure in the section 5.2 Setting Address
When mounting outside, make sure no water can leak in through cable holes.
Evaluate power requirements as described in section 4 Power Supply.Same time evaluate
required power cables determined by required power and length of the cables.
Select cables used for communication lines as described in section 5 RS485 Communication
Line
Determine an appropriate mounting position for the device. The BCR-S Mini G2 is supported
to be installed on walls, mounting column, mounting brackets. The back plate of the unit
contain rubber sealing so it SHALL BE NOT used as a template for drilling. Use attached
drilling pattern instead.
Route the interface cables to S-Node G2, C-Node G2, Moveo, Moveo XL or to the other reader if
the actual reader is in the middle of the bus. Route cables to other accessories to be connected.
Install the bottom part of BCR-S Mini G2 box to the wall. Feed all cables inside the box to
appropriate position and fix them to the box with cable ties.
Connect all cables to the terminals as required.
Set termination jumper SW1 to enabled (default setting) if the actual reader is placed at the end
of the bus.
After wiring the BCR-S Mini G2 and accessories, device is ready to be tested. If the card reader
have been properly installed, connect terminal PL1 to the BCR-S Mini G2. The card reader will
beep for 1 second and starts working after short while (this is valid only in case that system was
already configured at PC level and that the parent node is up and running). This indicates that
unit is working properly.
Assemble the unit by pressing the top part down on the back plate. Ensure correct positioning
in the top before it is pressed into place.

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 8
SystemHouse Solutions
3.1 Device overview

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 9
SystemHouse Solutions
3.2 Opening device
To open device always use proper opening tool. Using other tools can cause scratches and damages
of the box that will cause warranty refusal.
For opening device follow instructions in Quick Installation Guide (part of device delivery) or look
in section Quick installation guide in this document.
Opening tool:
3.3 Maximum torque for box installation
When device is installed by using an electrical screwdriver the maximum torque used shall be 2.5
N/m.

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 10
SystemHouse Solutions
3.4 Installation on metal surfaces
When device is installed on metal surface is strongly recommended to use proper accessory
44280280 Installation plate for xCR-S (Mini) G2.
This will minimize problems with low reading distance caused by interfering with metal surface.
3.5 Wall tamper
In case when is required to use also wall tamper for higher security grades where it is necessary to
install wall tamper springs.
Installation procedure:
1. Open device using opening tool.
2. Cut tamper activators placed at bottom cover at plastic level.
3. Install springs from bottom side.
4. Fix bottom cover with screws at installation place. Surface level needs to be even.

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 11
SystemHouse Solutions
4 Power Supply
BCR-S Mini G2 doesn’t use own power supply instead it is powered from S-Node G2, central unit C-
Node G2, Moveo or Moveo XL. The S-Node G2 is normally powered from central unit C-Node G2
where power supply and communication line are distributed together to door environments.
S-Node G2, C-Node G2, Moveo/XL are equipped with fused terminals to supply power to card
readers.
4.1 Power requirements
Before starting installation, power requirements needs to be evaluated.
Typical power consumption is 20 mA, it can slightly increase while applying card.
4.1.1 Power supply
The device is powered by terminal PL1. Connector for power supply and communication line is
fixed to bottom cover and it’s released from electronics while opening device.
PL1 24VDC/RS485

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 12
SystemHouse Solutions
5 Communication and address
There is one RS485 communication line to/from the BCR-S Mini G2.
5.1 Setting address
For proper communication on RS485 device needs to have proper address assigned. All devices
have from production address 2. If another address is required default address must be changed by
using tool for address setting.
5.1.1 Address setting on reader
To set address on BCR-S Mini G2 you need to use BCR-G2 Setup program.
Valid address range when connected to S-Node G2: 1-2
Valid address range when connected directly to C-Node G2/Moveo/XL: is 1-8
Procedure to setup address:
1. Connect a USB to RS485 cable to readers RS485 connector. Make sure that RS485 connection
to S-Node G2 is not connected since it will interfere with BCR-G2 Setup program and upgrade will
fail.
2. Start BCR-G2 Setup program, select proper Serial port and address of Reader. Baudrate should
be 19200.

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 13
SystemHouse Solutions
3. If you are successfully connected you will see *Disconnect“ with green text.
4. In the New Address field change address to wanted address, address range is 1-16, press change,
next press Reset.
5. Reader will now reset and new address has been set.
6. The connection button will change color to red – disconnect since it lost connection to reader
with previous address.
7. To test that reader has proper address change Address to new Address and press Connect. You
should now get Disconnect with green color.

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 14
SystemHouse Solutions
If there are any problems connecting to reader, make sure you have correct address set in settings
and that tamper switches is not active. Make sure that you have correct addresses set in Integra
Client.
5.2 RS485 communication line
The RS485 bus must be configured as a bus with no branches. The bus needs to be terminated at
each end. Jumpers are provided on each device (C-Node G2, Moveo, Moveo XL, S-Node G2 and
card readers) to enable or disable termination. Up to two card readers can be connected to the same
S-Node G2, as in-reader and out-reader.
Since together with communication line is distributed also power line we do use mixed cable to
supply both in one.

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 15
SystemHouse Solutions
5.2.1 Line installation
PL1 24VDC/RS485

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 16
SystemHouse Solutions
5.2.2 Line termination
SW1 CR RS485 termination
RS485 bus terminated
No termination
For RS485 termination must be On at beginning and end of line only, all other devices must have it
Off.
SW1 RS485 Termination
5.2.3 Recommended cable
Maximum length of RS485 line can be up to 1000 meters from the first to last unit on the bus.
Always use twisted pair cables, and we always recommend the use of shielded cable for connecting
card readers.
NOTE:
ALWAYS calculate total power consumption and choose a cable with conductor cross-sectional
area designed for that total power consumption.
ALWAYS calculate voltage drop before selecting cable.

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 17
SystemHouse Solutions
5.2.3.1 PTS-HF-2x2x0.6
We always recommend screened, twisted pair cables, type PTS-HF-2x2x0.6 for RS485 lines.
A screened cable is considerably more difficult to wiretap than an unscreened cable.
Higher cable cross-sectional areas may be necessary in the case of long lines, as voltage drops can
be expected.
5.2.4 RS485 network topology and termination principles
•Linear double terminated bus
•Linear double terminated cascade bus with S-Node G2 in the middle.
Star formation in the wiring from S-Node G2
•Two linear double terminated cascade buses on C-Node G2.
RS485 lines from C-Node G2 can have bus formation although wiring is performed as a star
network. This can be done by using two cable pairs for the bus, "RS485 out" and "RS485 in".
C-Node G2 can be equipped with an optional connection block for this, CG2-VDE

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 18
SystemHouse Solutions
6 Service routines
6.1 Periodical service check
Periodical service check consist of from several steps.
•Visual inspection - check mechanical damage of the box
oThere shall be no visible damage on the box.
•Apply valid card
oGreen light stripe must be activated together with single beep from buzzer.
•Apply not valid card
oRed light stripe must be activated together with two beeps from buzzer.
•Open box and check wiring
oEvery wire must be properly inserted and fixed in screw terminal.
•Check visually electronics for any possible damages.
oThere shall be no damage on electronics.
•Check both parts – bottom and lid for traces of water or humidity.
oAre any signs of humidity or water ingress the device must be evaluated for
possible source of water leakage. In most cases the cable is not properly
sealed inside back sealing and it is leading water inside the device. In this
case bottom part must be exchanged.
•Measure voltage on screw terminal and compare it against level on used power supply.
oVoltage must be within range 20-30 V DC.

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 19
SystemHouse Solutions
6.2 Fixing common issues with the reader
6.2.1 No communication with the Reader
Solution:
1. Check wires for RS485 if they are properly attached to screw terminal.
2. Check polarity for wires.
3. Check setting of switch SW1 – termination of RS485 according position of reader on the
line.
4. Compare device address with address set in the system.
6.2.2 Reader is not working
Solution:
1. Check wiring of the connectors, check polarity.
2. Check power supply if it’s within range 20-30 V DC.
3. Check setting of switch SW1 – termination of RS485 according position of reader on the
line.
4. Check setting inside system if device has proper address set.

1-981-2181-GB, 2021-03-16 BCR-S Mini G2 Page: 20
SystemHouse Solutions
7 Attachments
7.1 Construction
The Card Reader is equipped with a built-in antenna for card reading, LED indication and internal
buzzer.
The Card Reader is sabotage protected in a sturdy case with EIA485 interface.
The smart card reader use technology in the 13.56 MHz frequency range.
7.2 Functions
The Card Reader is used for contactless smart card access cards in a 30 mm range, status
indications of the door environment.
LED’s for indication of door status, etc.
Built in buzzer for warning and button press indication etc.
Table of contents
Popular Security System manuals by other brands

SYAC-TB
SYAC-TB DIGIEYE COMPACT Quick setup

Ingics
Ingics iBS02M2 Guide

Wheelock
Wheelock SAFEPATH SCSP-15SP Installation, testing, operation and maintenance manual

DMP Electronics
DMP Electronics XR500 SERIES user guide

Visonic
Visonic POWERMAXEXPRESS - Installer's guide

Alexor
Alexor PC9155-433/868 installation guide