20 P/N 0320-7201-00 • REV A • ISS 14MAR18 ©2018 United Technologies Corporation
8.2 Adding Alarms to an Existing Wireless
Interconnected Network
For various reasons, you might want to add additional alarms to your existing wireless interconnection
network.
1. Remove the new alarm from its packaging.
2. Choose one existing, installed alarm (not the new alarm). Place and hold a magnet for four seconds
on the cover of the existing alarm in the network at the designated location per Figure 5. The alarm will
beep once when the magnet is detected, then the alarm will beep twice and will start flashing the RED
LED rapidly to indicate the alarm is in System Test Mode.
3. Push and hold the test button on the same alarm (in System Test Mode) until two beeps are heard
(approximately 4 seconds), and then release the button.
• The button-pushed alarm will cause the GREEN LED to fade on/off on each alarm in the existing
network to signal that the wireless interconnection network has been opened.
NOTE: From this point, you have fifteen (15) minutes to power up the new alarm.
4. Power up the new wireless alarm by twisting the alarm onto the mounting bracket (trim plate) to activate
the battery, or by carefully turning the red activation wheel with a screwdriver. See Figure 4.
• After initial GREEN LED on/off sequence, the new alarm’s RED LED will fade on/off every 3 sec-
onds as it searches for the network.
• A fast GREEN LED flickering, followed by a slow GREEN LED fading on/off confirms the new alarm
has found and joined the existing wireless interconnection network.
5. Wait fifteen (15) minutes for the network setup to timeout, OR to immediately close the network, push
and hold the test button on any device enrolled in the network until two beeps are heard (approximately
4 seconds), and then release the button.
• GREEN LED flashes once every 60 seconds on the new alarm to indicate normal operation.
6. After selecting the proper location for your alarm, attach the mounting bracket to the wall or ceiling. To
ensure aesthetic alignment of the alarm with the hallway, or wall, the “A” line on the mounting bracket
must be parallel with the hallway when ceiling mounted or horizontal when wall mounted.
• Install the alarm fully on the mounting bracket (trim plate) by rotating the alarm in a clockwise direc-
tion. NOTE: The alarm will mount to the bracket in four positions (every 90 degrees).
7. The alarm is now activated. After installation / activation, test your alarm as described in Operation and
Testing section.