Interlogix ESL User manual

1
ESL/ITIWireless Smoke Sensors
The major threat from fire in a family living unit occurs
at night when everyone is asleep. The principal threat
to persons in sleeping areas comes from fires in the
remainder of the unit. Therefore, smoke alarms/
detectors are best located between the bedroom areas
and the rest of the unit. In units with only one bedroom
area on one floor, the smoke alarm/detector should be
located as shown in Figure 1.
In family living units with more than one bedroom area
or with bedrooms on more than one floor, more than
one smoke alarm/detector is required, as shown in
Figure2.
The ESL/ITI Wireless Smoke Sensors (smoke alarms) are
Learn Mode™, supervised wireless, battery powered
photoelectric smoke sensors. The sensors include a built-in
sounder for alarm alerts, a visual status LED (light-emitting
diode), and an ITI crystal transmitter. The sensors work as
part of a security/fire alarm system and communicate with
the system control panel.
Under normal (non-alarm) conditions, the LED flashes once
every 9 seconds while the sensors monitor the surrounding
conditions. The sensors transmit a supervisory signal every
64 minutes that identifies their status, which the panel
processes accordingly.
When the sensors detect a smoke or fire condition, the LED
changes from flashing to on and the built-in sounder
produces a loud temporal beeping pattern. The sensors also
transmit an alarm signal, which the panel receives and
processes accordingly.
Each smoke sensor uses two 3-volt lithium batteries, which
are included.
The smoke sensors also provide the following features:
GCleanMe™self-diagnostics monitor sensor sensitivity
and operational status (see the “Testing” section).
GSensor tamper switch that triggers a tamper signal
transmission when the sensor is removed from its
mounting base.
GFixed135°F temperature/rate ofrise heat detector
(model 60-849-95 only) trips an alarm based on
temperature detected or rapidly rising temperature rate
(15°F per minute).
GReplaceable optical chamber for easy maintenance
when required (see “Maintaining the System”).
Avoid installing the unit until all construction is completed.
The mounting base may be pre-installed.
The dust cover must be removed for the unit to
detect smoke.
These smoke sensors are not compatible with
CareTaker Plus and custom version panels with
software versions 3.0 and earlier, or with
Commander 2000 and custom version panels with
software 4.0 and earlier.
Selecting a suitable location is critical to the operation of
smoke alarms/detectors. This equipment should be installed
in accordance with the National Fire ProtectionAssociation’s
(NFPA) Standard 72, Chapter 8.
GNFPA72,A-8-1.2.1.a Where to Locate the Required
Smoke Alarms/Detectors in Existing Construction.
ESL/ITI Wireless
Smoke Sensors
Installation Instructions
Product Summary
Installation Guidelines
LIVING ROOM BEDROOM
BEDROOMBEDROOMKITCHENDINING
BATH
SMOKE ALARMS/DETECTORS FOR MINIMUM PROTECTION
SMOKE ALARMS/DETECTORS FOR ADDITIONAL PROTECTION
HEAT ACTIVATED ALARMS/DETECTORS
Figure 1. Family units with one bedroom area.
CAUTION
Not
e
ITI Part No. ITI Part No.
60-848-95 60-849-95
8712g07a.dsf

2ESL/ITIWireless Smoke Sensors
and hallways not protected by the required smoke
alarms/detectors. The installation of smoke alarms/
detectors in kitchens, attics (finished or unfinished), or
garages is not normally recommended, as these locations
occasionally experience conditions that can result in
improper operation.
Regulations pertaining to smoke alarm/detector
installations vary from state to state. For more information,
contact your local fire department or local authority
having jurisdiction.
GDO NOT mount a smoke alarm to a drop ceiling tile;
mount it to a metal runner.
GMount all smoke alarms within 100 feet of the panel.
GInstall a minimum of two smoke alarms in any house
hold, no matter how small it is.
GPut a smoke alarm in the hallway outside of every
bedroomarea.Aminimum of twosmokealarmsare
required in homes with two bedroom areas.
GPut a smoke alarm on every level of a multi-level
residence.
GInstall basement alarms on the ceiling as close to the
center of the room as possible. If this is not practical,
install it on the ceiling no closer than 4 inches (10 cm)
fromany wall or corner.
GIf ceiling mounting is not practical, install on an
inside wall between 4 and 6 inches (10 and 15 cm) from
the ceiling.
GPut smoke alarms at both ends of a bedroom hallway
if the hallway is more than 30 feet (9 meters) long.
Large rooms over 900 square feet require more than a
single sensor.
GAreas with rough ceilings or short, transom-type walls
coming down from the ceiling require additional
smokealarms.
GInstall second-floor smoke alarms on the ceiling at the
top of the first-to-second floor stairwell. be sure no
door or other obstruction blocks the path of smoke to
the unit.
GIn rooms with sloped, peaked, or gabled ceilings, install
smoke alarms 3 feet (0.9 meter) measured down on the
slant from the highest point of the ceiling (see Figure 5).
In addition to smoke alarms/detectors outside of the sleeping
areas, Chapter 8 requires the installation of a smoke alarm/
detector on each additional story of the family living unit,
including the basement. These installations are shown in
Figure 3. The living area smoke alarm/detector should be
installed in the living room or near the stairway to the upper
level, or in both locations. The basement smoke alarm/
detector should be installed in close proximity to the stairway
leading to the floor above. Where installed on an open-joist
ceiling, the alarm/detector should be positioned relative to
the stairway so as to intercept smoke coming from a fire in
the basement before the smoke enters the stairway.
NFPA72,A-8-1.2.1.b Where to Locate the Required Smoke
Alarms/Detectors in New Construction. All of the smoke
alarms/detectors specified inA-8-1.2.1.a for existing construc-
tion are required and, in addition, a smoke detector is
required in each bedroom.
NFPA72,A-8-1.2.1.c Are More Smoke Alarms/Detectors
Desirable? The required number of smoke alarms/detectors
might not provide reliable early warning protection for those
areas separated by a door from the areas protected by the
required smoke alarms/detectors. For this reason, it is
recommended that the householder consider the use of
additional smoke alarms/detectors for those areas for
increased protection. The additional areas include the
basement, bedrooms, dining room, furnace room, utility room,
LIVING ROOM
KITCHEN
BEDROOM
BEDROOM
BEDROOM
TV ROOM
DINING ROOM
BATHROOM
SMOKE ALARMS/DETECTORS
FOR MINIMUM PROTECTION
SMOKE ALARMS/DETECTORS
FOR ADDITIONAL PROTECTION
HEAT ACTIVATED ALARMS/DETECTORS
KITCHEN
BEDROOM
LIVING
ROOM
GARAGE
BASEMENT
BEDROOM
BEDROOM
SMOKE ALARMS/DETECTORS FOR MINIMUM PROTECTION
SMOKE ALARMS/DETECTORS FOR ADDITIONAL PROTECTIO
N
HEAT ACTIVATED ALARMS/DETECTORS
Figure 2. Family units with more than one
bedroom area.
Figure 3. Multilevel family units.
Figure 4. Smoke alarm mounting locations.
BEST LOCATION
ACCEPTABLE LOCATION
DEAD AIR
SPACE BEST IN CENTER
OF CEILING
NO CLOSER THAN 4
"
(10 cm)
FROM SIDE WALL
MOUNT ON WALL
AT LEAST 4
"
(10 cm)
FROM CEILING
NO MORE
THAN 6
"
(15 cm)
FROM CEILING
Important !

3
ESL/ITIWireless Smoke Sensors
All alarms are subject to possible compromise or failure-to-
warn for a variety of reasons, for example:
GSmoke alarms cannont detect smoke in chimneys,
walls, roofs, or smoke blocked by a closed door.
GAlarms may not detect smoke on other levels of the
building.
GAlarms may not warn in time when fires are caused by
smoking in bed, explosions, improper storage of
flammables, overloaded electrical circuits, or other
hazardous conditions.
GIn or near areas where combustion particles are
normally present such as kitchens; in garages where
there are particles of combustion in vehicle exhausts;
near furnaces, hot water heaters, or gas space heaters.
GOn the ceiling in rooms next to kitchens where there is
no transom between the kitchen and these rooms.
GIn damp or very humid areas, or next to bathrooms with
showers. Install sensors at least 5 feet (1.5 meters)
away from bathrooms.
GIn very cold or very hot areas.
GIn dusty, dirty, or insect infested areas.
GNear fresh air inlets or returns or excessively drafty
areas.Air conditioners, heater, fans, and fresh air
intakes and returns can drive smoke away from smoke
alarms.
GIn dead air spaces at the top of a peaked ceiling or
wall/ceiling intersect. Dead air may prevent smoke from
reaching a smoke alarm.
GNear flourescent light fixtures. Install smoke alarms at
lease 10 feet (3 meters) away from flourescent light
fixtures.
This section describes the basic steps for adding the sensor
to panel memory. For complete programming information,
refer to the specific panel installation instructions.
8712g11a.dsf
Limitations
Insert Batteries
Where Not to Locate Detectors:
Programming
To add the detector to panel memory:
Installing
To mount the base:
HORIZONTAL
DISTANCE
FROM PEAK
3 FEET
(.9M)
+_
3 V
+_
3 V
O P E N
B A T T E R Y
C O V E R
B A T T E R Y
C O M P A R T M E N T
8712g10a.dsf
Figure 5. Sloped, peaked, or gabled ceilings.
Figure 6. Removing cover from the mounting base.
Figure 7. Battery Installation
1. Remove the detector from the mounting base by turning
the sensor counter clockwise about 15 degrees. The
sensor should snap off of the mounting base.
2. Slide the battery cover away from the detector to
unsnap it and lift it off.
3. Observing proper polarity, insert the two lithium
batteries provided into the battery compartment and
replace the battery cover.
4. Attach the sensor to the mounting base.
1. Make sure the sensor is attached to the mounting base.
2. Put the panel in Program Mode/Learn Sensors.
3. Select a sensor group and sensor number.
4. When prompted by the panel to trip the sensor, activate
the sensor tamper switch by removing the sensor from
the mounting base.
The panel will indicate that the sensor has been learned.
5. Exitfromprogrammode.
Note
The plastic dust cover must be removed for the
unit to detect smoke. The detector is shipped with
a dust cover for protection on construction sites
with dusty environments.
The mounting base must be separated from the unit before
you begin. Using the two screws and anchors provided,
mount the base.

4ESL/ITIWireless Smoke Sensors
button is pressed (model 60-848-95 only). The sensor
automatically resets when smoke is no longer present.
A sensor that fails to activate with either the sensor or
smoke test may require cleaning. If a sensor still fails to
activate after cleaning, return the unit for service.
Each smoke sensor includes a sensitivity level test mode
that lets you check the sensitivity using the test/silence
button and the LED as follows:
1. Press and hold the test/silence button for 2 seconds,
then release it. The LED flashes one to nine times.
2. Count the number of LED flashes and use the
following table to determine the status of the sensor
sensitivity and what action to take, if any.
When the batteries are low, the sensor transmits a low
battery signal for at least 7 days, allowing the monitoring
company time to contact the customer for service.
After 10 days, the sensor will chirp every 30 seconds until
the batteries are exhausted. Press and release the test/
silence button to silence the low battery beeps for 24
hours.
Constant exposure to high or low temperatures or high
humidity may reduce battery life. Replace both batteries
when the sensor or panel notifies you that the batteries are
low. Always test the system after replacing the batteries.
Attach the sensor to the base as follows:
1. Line up the raised tab on the lip of the sensor with the
slot on the lip of the mounting base.
2. Attach the sensor onto the base and turn clockwise
approximately 15 degrees. It should snap firmly
into place.
Test each smoke sensor every week to verify that its siren
and signal integrity are adequate. Refer to the specific panel
installation instructions for system response.
1. Put the panel in the Dealer or User Sensor Test mode.
2. Press and hold the test/silence button on the detector
for 2 seconds, then release it.
After a slight delay (about 10 seconds), the LED turns
on and the built-in sounder emits one temporal
3 pattern (3 beeps).
Note
The model 60-849-95 (UL 268 version) does not produce
any sound when the test/silence button is pressed.
3. Listen for the appropriate response from system
sirens to determine signal integrity from the sensor
to the panel (refer to the specific panel installation
instructions).
4. Exit from Dealer or User Sensor Test mode.
Smoke detectors should be tested in place annually using
canned aerosol simulated smoke (Smoke! in a Can, ESL Part
No. SM-200). Follow the instructions on the can.
To avoid a fire department dispatch, contact the central
monitoring station or put the system into sensor test
mode
before
activating the sensor using this method.
The LED should remain on while the built-in transmitter
sends an alarm signal to the control panel. The sensor
produces a temporal 3 beeping pattern until the test/silence
Flashes Approximate Sensor Action
Obscuration Condition
1 N/A Self-diagnostics Return sensor for
failure. service/
replacement.
2-3 N/A Sensor is not Clean the sensor
sensitive enough (see the
“Maintaining the
System” section)
and retest. If
error persists,
replace sensor.
4 3.1%/ft Sensor is within N/A
5 2.6%/ft normal
6 2.1%/ft sensitivity range.
7 1.6%/ft
8-9 N/A Sensor is too Verify that the
sensitive. smoke chamber
is snapped down
securely. Clean
the sensor (see
“Maintaining
the System” )
and retest.
Testing
Sensor Test
Smoke Test
SensitivityTest
Sensitivity Ranges
Maintaining the System
Replacing Batteries
8712g04a.dsf
Slot and raised tab
Figure 8. Sensor-to-Base Alignment
CAUTION
Attaching the sensor to the base:

5
ESL/ITIWireless Smoke Sensors
10. Reattch the sensor to the mounting base.
11. Test the sensitivity as described in “Testing”.
In the event that the smoke sensor needs servicing, send it
to: ITI, 2266 Second St. North, North St. Paul, MN 55109.
Develop plans for a variety of emergency situations.
Periodically discuss and rehearse emergency plans that
include the following:
GKnow the normal state of doors and windows; open,
closed, or locked.
GUse a different escape route if closed doors feel hot to
the touch.
GEmphasize that everyone should escape as quickly as
possible. Do not stop to gather any belongings.
GCrawl and hold your breath as much as possible to
help reduce smoke inhalation during your escape.
GMeet at a designated outdoor location.
GEmphasize that no one should return to the premises if
there is a fire.
GNotify the fire department from a neighbor’s phone.
If you arrive at the premises and hear sirens, do not
attempt to enter the building. Call for emergency
assistance from a neighbor’s phone.
Figure 11 is an example of a multilevel floor plan. Use it as a
guide and draw your floor plan below.
SQUEEZE HERE
8712g06a.dsf
SMOKE
CHAMBER
OPTICAL
BASE
SENSOR
CAP
OPTICAL
CHAMBER
INDENTATIO
N
8712
g
08a.dsf
Cleaning
To clean the sensor chamber: Planning for Emergencies
Servicing
Planning Escape Routes
SMOKE ALARMS/DETECTORS FOR MINIMUM PROTECTION
SMOKE ALARMS/DETECTORS FOR ADDITIONAL PROTECTIO
N
HEAT ACTIVATED ALARMS/DETECTORS
KITCHEN
ATTIC
BASEMENT
LIVING
ROOM
BEDROOMBEDROOM
DINING
ROOM
LIVING
ROOM
KITCHEN BEDROOM BEDROOM
BEDROOM
BATH
BEDROOM
BEDROOM
BEDROOM
KITCHEN
DINING
ROOM
TV
ROOM
LIVING
ROOM
BATH
RECREATION
ROOM
BEDROOM BEDROOM
LIVING
ROOM
BASEMENT
A smoke detector should
be located on each level.
Smoke detectors should be located
between the sleeping area and the
rest of the family living unit.
In family living units with more than
one sleeping area, locate a smoke
detector at each area.
Figure 10. Sensor Parts.
Figure 11. Example of a floor plan.
WARNING
Figure 9. Removing the Sensor Cap.
Note
For UL installations, use the following battery brands: Sanyo
CR123A, Panasonic CR 123A, or Duracell DL123A. These
can be obtained through ITI. Do not mix brands.
Clean the sensor cover with a dry or damp cloth as needed to
keep it free from dust and dirt.
Clean the sensor interior at lease once each year. This
requires replacing the optical chamber. Use only ESL model
211 Optical Chambers for replacement.
1. To clean the sensor you must first place the panel in
sensor test mode.
2. Remove the sensor from the mounting base.
3. Remove the batteries
4. Slide a flat-blade screwdriver in the slot on the sensor
cap and gently push the handle down to pry the cap off.
5. Press in on the sides of the existing smoke optical
chamber and pull it up and away from the sensor and
discard.
6. Blow out or use a soft-bristled brush to remove dust
and dirt from the smoke chamber base.
7. Align the new optical chamber with the base and snap
down into place.
8. Replace the sensor cap by lining the cap up with the
sensor, then press the cap onto the sensor and turn
clockwise approximately 15 degrees. It should snap
firmlyinto place.
9. Observing the proper polarity, re-install the batteries
and replace the battery cover.
SMOKE
BASE

6ESL/ITIWireless Smoke Sensors
Your Floor Plan
When establishing your escape routes, consider the
following guidelines:
GShow all building levels.
GShow all exits, (two exits per room are recommended).
GShow the location of all components of the fire system.
GShow the locations of any fire extiguishers, hoses,
ladders, etc.

7
ESL/ITIWireless Smoke Sensors
Compatibility: Advent, Commander 2000 and
Customs Versions with software
versions 4.1 and later, CareTaker
Plus and Custom Versions with
software versions 3.1 and later,
UltraGard and Custom Versions,
Concord, Concord Express, Simon
Dimensions:
Detector 5.5in.x2.3 in.(14cmx5.6 cm)
Base 4.88in.x 0.38in.(12.3cm x9.5cm)
Temperature:
Operating range 40°to 100°F (4°to 38°C)
Storage Temperatures -30°to140°F (-34°to 60°C)
Humidity: 90% non-condensing
Voltage: 3VDC
PowerSource: Two 3-volt lithium batteries of the
same type. UL-approved types:
Sanyo CR123A, Panasonic
CR123A,DuracellDL123A.
Sensitivity: 2.3%±0.8%
Driftcompensation
adjustment: 0.5%/ft.max.
Heatdetector(model60-849-05only):
Rate of rise 15°F/min>105°F
(8.3°C/min>40.6°C)
Fixed 135°F±5°F(57.2°C±2.8°C)
Agency Listings: UL 217 (60-848-95)-Residential Installations
UL 268 (60-849-95)-Commerical Installations
This device complies with part 15 of the FCC rules. Operation is
subject to the following two conditions:
This device may not cause harmful interference.
This device must accept any interference received, including
interference that may cause undesired operation.
Changes or modifications not expressly approved by ITI can void the
user’s authority to operate the equipment.
FCC ID: B4Z-773A-SMOKE
Patent No.: 4,855,713 - 4,864,636 - 5,686,885 - 5,686,896 -
5,798,701 - 5,821,866 - 5,936,533 - 5,546,074
NoticesSpecifications

8ESL/ITIWireless Smoke Sensors
ITI, Advent, CareTaker, Commander, UltraGard, and Simon are registered trademarks of Interlogix, Inc. Concord, Concord Express, andLearnModeare trademarks of Interlogix,Inc.
466-1814Rev. A(1033570) 10/00
Other manuals for ESL
1
This manual suits for next models
3
Table of contents
Other Interlogix Fire Alarm manuals
Popular Fire Alarm manuals by other brands

Panasonic
Panasonic EBL512 operating instructions

Pertronic
Pertronic SYSTEM SENSOR FAAST LT Series Installation and maintenance guide

Honeywell
Honeywell NOTIFIER AM-8000 installation manual

Notifier
Notifier NBG-12LOB quick start guide

Opal
Opal KD-125C user manual

Honeywell
Honeywell XL 800 Series Operator's manual

Tyco
Tyco F3200 Installation & programming manual

CWSI
CWSI CP-3000DA Operating and installation instruction manual

Autronica
Autronica Autroprime Operator's handbook

Bosch
Bosch FMM-7045 installation instructions

Simplex
Simplex 4002 Life Alarm Service instructions

Hochiki
Hochiki HCA-2 Installation and operation manual