International Refrigeration Products MSM30H46ZI Manual

There should not be any heat source or steam
near the unit.
There should not be any obstacles blocking
air circulation.
Locate where there is good air circulation in the room.
Water drainage must be considered when locating the unit.
Ensure the dimensions indicated by arrows from the
wall, ceiling, floor and other obstacles are observed.
There should not be any direct sunlight. If unavoidable,
sunlight prevention should be taken into consideration.
1. Secure the mounting plate level to
structural wall supports.
Use a level to ensure the mounting
plate is leveled, so condensate can
drain properly.
2. If the wall is made of brick, concrete
or the like, drill eight (8) 0.2" diameter
holes in the wall. Insert Clip anchor for
appropriate mounting screws.
3. Secure the mounting plate on the wall
with wall anchors or proper mounting
screws.
Use the mounting plate (packaged in the back
of the indoor unit) as the template.
(Dimensions are in inches unless otherwise stated)
1. Determine hole positions according to left and right
side of the installation plate. The hole center is obtained
by measuring the distance as shown in the diagram above.
2. Drill the wall hole with a φ3.7" hole-core drill.
3. Drill the wall hole at either the right or the left and the
hole must be slightly slanted to the outdoor side.
4. Always use wall hole conduit when drilling metal grid,
metal plate or the like.
5. Wall sleeve can now be inserted into the hole from the inside.
We recommend the sleeve to be approximately 3/16” longer
than the wall thickness - cut as necessary.
1. For the left-hand and right-hand installation,
remove the pipe cover from the side panel.
2. For the rear-right-hand and rear-left-hand
installation, install the piping as shown.
3. Bundle the tubing, connecting cable, and
drain hose with tape securely, as
shown in Figure on the right.
Do not restrict water from draining out of drain pan.
1. Run the drain tubing sloping downward.
Do not install the drain hose as illustrated
in Figures.
2. When connecting extension drain hose,
insulate the drain tubing with tape and
maintain a downward slope.
Connect the indoor unit first, then the
outdoor unit.
Be careful not to let the drain hose slack.
Insulate both suction and liquid pipes.
Be sure that the drain hose is located at
the lowest side of the bundle. Locating at
the upper side can cause drain pan to
overflow inside the unit.
Run the drain hose sloping downward to
drain the condensed water smoothly.
Anchor the outdoor unit with a bolt and nut (3/8")
tightly and horizontally on a concrete or rigid mount.
Outdoor unit dimension
inch
(L1xHxW1)
L2(inch) W2(inch)
24.6
23.2
14.4
13.1
Mounting dimensions
40x38x13.6
35.4x33.9x12.4
1. Pass the piping through the hole in the wall.
2. Hook the indoor unit onto the upper portion
of installation plate(Engage the indoor unit with
the upper edge of the installation plate). Ensure
the hooks are properly seated on the installation
plate.
3. Piping can be made easier by lifting the indoor
unit with a cushioning (spacing) material between
the indoor unit and the wall. Remove after
completing the indoor installation to wall plate.
4. Press the lower left and right side of the unit
against the installation plate until hooks
engages with the their slots.
5. Indoor unit is now installed. It should be plumb,
level and flush with the wall. Ensure that the line set
stubs are completely through the wall.
Also check that the wall is plumb. The unit must be
level and plumb for proper condensate removal.
6. Check the drain hose, Observe that the condensate
drain pipe does not curve upward and is in the lower
part of the pipe bundle.
INSTALLATION AND MAINTENANCE
MANUAL
FOR MODELS: MSM30H46ZI, MSM36H44ZI
30H46ZMI, 36H44ZMI
SELECT IDEAL LOCATION
Indoor unit
WALL HOLE - REAR CABLE & DRAIN
Outdoor unit
Installation of the outdoor unit
INDOOR UNIT MOUNTING PLATE
2
CONNECTING LINE SET AND DRAIN TUBING
3
NOTE:
NOTE:
Fit the Mounting Plate
Line Set installation
Draina ge
CAUTION
Indoor unit installation
1
The mounting wall should be strong and solid
enough to prevent vibration.
There should not be any obstructions for the discharge air.
Ensure the dimensions indicated by arrow from a wall
fence or other obstacles are maintained.
I
N
D
O
O
R
U
N
I
T
Mounting Plate
Remote Control
Remote Control Holder
Batteries for Remote Control (2 AAA)
Operation Manual
The following items are necessary for the installation of the ductless mini splits.
Par ts included with unit
Description
NOTE:
The seriousness is classified by the following indications.
This symbol indicates the possibility of death, serious injury or property damage.
1) This equipment must be properly or personal injury and erratic operation may occur.
2) Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and
accumulates at surrounding of the unit, it may cause fire.
3) Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water
may enter the room and damage the furniture.
grounded
1) Install according to this installation instruction. If installed improperly, it may cause property
damage, water leakage, electrical shock and fire damage.
2) Use the included accessories and specified parts for installation, otherwise, it cause collateral damage.
3) Install outdoor unit on a firm solid base capable of supporting the weight of the unit.
The indoor unit must be installed on a wall capable of supporting the weight of the unit.
4) The electrical installation must follow all local and national codes by a certified installer. Supply power
must be from a protected circuit. The supply circuit must be used with an outdoor approved disconnect
box.
5) Use only the specified wire or cable. All connections must be secured to prevent external
pulling of wires to terminal connections, this may cause fire or personal harm.
6) Wire routing must be arranged so that control board cover is fixed properly. If control board
cover is not fixed perfectly, it will cause fire or electrical shock.
7) When installing the line set (piping) take precautions not to let air and any foreign materials from
entering the system, this will cause lower capacity, abnormal pressure and damage to the compressor.
SAFETY PRECAUTIONS
WARNING/CAUTION
CAUTION
WARNING
Please read this installation document completely before installing the product.
Installation must be performed by a certified installer and all electrical wiring must meet local and
national electrical codes.
Contact an authorised service technician for repair, maintenance or installation of this unit.
The design and specifications are subject to change without prior notice for product improvement.
Consult with the sales agency or manufacturer for details.
All the pictures in the instructions are for explanation purposes only.
The actual dimensions and shape may have been revised.
Correct orientation
of Mounting Plate
MINI-SPLIT
950-0182revC November 27, 2013
6" or more
5" or more
5" or more
90.6" or more
12" or more
24" or more
12" or more
24" or more
79" or more
Wall Anchors
Indoor
unit
Installation Manual
Plastic Drain Connection
• Refrigerant line set: Flared connection only, suitable for R410A with both lines insulated.
Max length for connection see product label on outdoor unit.
• High voltage interconnect wiring: 16AWG wiring from outdoor unit to indoor unit for power and
control.
• 5/8" drain tubing as necessary.
• Wall Sleeve
• Sealant
• 2" wide tape
• Main system breaker: Sized per unit requirements (See product label on the outdoor unit)
• Refrigerant: R410A required for additional line set Charge - See product label on the outdoor unit.
• Mounting hardware, condenser pad, etc.
Left wall hole
4.7" or more
from the wall
4.7" or more
from the wall
5.9" or more
from the ceiling Hook Mountings
Indoor unit outline Right wall hole
57.1"
40.3"
16.8" 16.6"
7.5"
2.8" 2.8" 2.8"
13.4"
0.98"
0.8" 6.85"
1.4"
1.26"
1.26"
12.5" 12.5"
1.4"
3.7"
2.16"
2.16"
Low Ambient Controller is included for use in Server Rooms or in Commercial applications.
Outdoor
unit
Op t i o n al Co ntrols and Compo n e n t s
• Condensate Pump:
• Decorative Channel: Plastic-Duct
• Wall brackets: Our Catalog# BR-440L
for up to 440 lbs.
Siccom P/N DE05LUA720 (4100123)
or P/N D05LUB100 (4100130)
Detail of cover removal

Indoor unit
terminal strip
Outdoor unit
terminal strip
4C
(NOT INCLUDED)
16 AWG
2
30K unit: 12 AWG 3C
36K unit: 10 AWG 3C
(NOT INCLUDED)
208/230 VAC LINE IN
1S
2
1SG
L1 L2 G
L1 L2
I
N
D
O
O
R
U
N
I
T
ELECTRICAL WIRING - INDOOR UNIT
4
Electrical safety regulation
1. Supply voltage should be in the range of 90% to 110% of rated voltage.
2. Check specification label on outdoor unit for the breaker size.
3. Ensure the system is properly grounded.
4. Connections must be as the wiring diagram.
5. All wiring must be in compliance with all local and national electrical codes.
6. Installer to be certified in accordance with local codes.
The cable size and the current of the
fuse or switch are determined by the
maximum current indicated on the
product label which located on the
side panel of the unit.
Please refer to the product label before
selecting the cable, fuse and switch.
Install the outdoor unit on a rigid base.
Confirm the discharge air outlet direction is not blocked.
If the outdoor unit is exposed to strong wind such as a seaside, make sure the fan can operate
properly by placing the unit lengthwise along the wall or install a wind shield.
See example of wind protection below.
Be sure there is no obstacle which may block exhaust air.
Strong
wind
Strong
wind
Barrier
Incorrect Correct
Seal
Drain joint
Base pan hole
of outdoor unit
(A) (B)
The drain joint may vary with different models.
For the drain joint with the seal (Fig.A), first fit the seal onto
the drain joint, then insert the drain joint into the base pan
hole of outdoor unit, rotate 90 degrees to securely assemble.
To install drain joint as shown in Fig.B, insert the drain
joint into the base pan hole of outdoor unit until it clicks into
position.
Connecting the drain joint with an extension drain hose (not supplied).
6
DRAIN JOINT INSTALLATION
OUTDOOR UNIT INSTALLATION
7
Oblique
O
90 Roughness
Burr
REFRIGERANT PIPE CONNECTION
1. Cut the copper tubing with a sharp tubing cutter.
2. Remove flare nuts attached to indoor and
outdoor unit and place them on the copper tubing
after removing all burrs and flare
the copper tubing.
3. Firmly hold copper pipe in a die in the
dimension shown in the table below.
.
Align pipes to be connected.
Tighten the flare nut with fingers,
and then tighten it with a spanner and torque
wrench as shown.
Excessive torque can break nut depending
on installation conditions.
Outer diam.
(inch)
A(inch)
Max. Min.
3/8"
0.063" 0.039"
5/8"
0.087" 0.079"
Bar
Copper pipe Clamp handle
Handle
Bar
"A"
Indoor unit tubing Flare nut Pipings
.
Outer
diam. Tightening
torque(lbs.ft)
Additional tightening
torque(lbs.ft)
φ5/8"
φ3/8"
33.2
(459kgf.cm)
34.7
(479kgf.cm)
18.4
(255kgf.cm)
19.2
(265kgf.cm)
AIR PURGING AND TEST OPERATION
8
9
1. Remove the electrical cover from the outdoor unit by removing the mounting screws.
2. Connect the cables to the terminals as identified with their respective matched numbers
on the terminal block of indoor and outdoor units.
3. Secure the cable to the terminal strip with the cord clamp.
4. To prevent the ingress of water, form a loop of the connective cable as illustrated in the installation
diagram of indoor and outdoor units.
5. Insulate unused cords (conductors) with PVC-tape. Process them so they do not touch any electrical
or metal parts.
Liquid side: φ3/8"
R410A: (Design length - 16.4 ft) x 0.43 oz./ft.
Connective pipe length
Less than 16.4 ft.
More than 16.4 ft.
Air purging method
Use vacuum pump
Additional amount of refrigerant to be charged
Open the valve stem until it fully opens to
the stop. Do not try to open it further.
Securely tighten the valve stem cap with
a spanner or the like.
Valve stem cap tightening torque. See
Tightening torque table.
.
.
.
Flare nut
Stopper
Cap
Valve body
Valve stem
Use vacuum pump
DO NOT EXCEED THE SPECIFIED MAXIMUM LINE LENGTH - SEE PRODUCT LABEL.
The service ports have a 5/16" connection to gauges.
When relocating the system to another location, using vacuum pump to perform evacuation
and leak testing..
.
.
.
Air and moisture in the refrigerant system will damage the operation of the system and reduce the life
of the compressor. Therefore, the indoor unit and tubing between the indoor and outdoor unit must be
leak tested and evacuated to remove any non-condensables and moisture from the system.
Check that each tube (both liquid and gas side tubes) between the indoor and outdoor units have
been properly connected and all wiring for the test run has been completed.
Pipe length and refrigerant amount:
Outdoor
unit
Indoor
unit
Refrigerant
Packed valve
Half union
Gas side
Liquid side
AC
D
B
1. Completely tighten the flare nuts, A, B, C, D, connect
the manifold valve charge hose to a charge port of the
packed valve on the gas pipe side.
2. Connect the charge hose connection to the vacuum
pump.
3. Fully open the handle Lo of the manifold valve.
4. Operate the vacuum pump to evacuate. After starting
evacuation, slightly loose the flare nut of the packed
valve on the gas pipe side and check that the air is
entering. (Operation noise of the vacuum pump changes
and a compound meter indicates 0 instead of minus)
5. After the evacuation is complete, fully close the handle
Lo of the manifold valve and stop the operation of the
vacuum pump.
Evacuate for 15 minutes or more and check the
indicating gauge is -76cmHg(-14.7 psi).
O
6. Turn the stem of the packed valve B about 45 counter-
clockwise for 6~7 seconds after the gas exits, then
tighten the flare nut again. Make sure the pressure display
in the pressure indicator is a little higher than the atmosphere
pressure.
7. Remove the charge hose from the Low pressure charge hose.
8. Fully open the packed valve stems B and A.
9. Replace the valve caps of the service ports.
Manifold valve
Compound meter
-76cmHg
Handle Lo Handle Hi
Charge hose Charge hose
Vacuum pump
Pressure gauge
Packed valve
Perform test operation after completing refrigerant leak check at the flare
nut connections and electrical safety check.
Check that all tubing and wiring have been properly connected and tight.
Check that the gas and liquid side service valves are fully open.
1. Connect the power, press the ON/OFF button on the remote
controller to turn the unit on.
2. Use the remote to select COOL, HEAT, AUTO and FAN and
confirm all the functions operate properly..
O
3. When the room ambient temperature is too low (lower than 62 F),
the unit cannot be controlled by the remote controller in the cooling
mode, manual operation must be used. Manual operation is used only when the remote controller is
disable or maintenance is necessary.
Hold the panel sides and lift the panel up to an angle until it remains open (clicking sound).
Press the Manual control button to select the AUTO or COOL, the unit will operate under
AUTO or COOL mode (see User Manual for details).
4. Test should last about 30 minutes.
Electrical work
Connect the cable to the indoor unit
Flaring
Tightening connection
1. Air purging
2. When using the Vacuum Pump
4. Operation Testing
3. Safety and leak test
A: Lo packed valve B: Hi packed valve
C and D are ends of indoor unit connection.
CAUTION
1. Soap water method:
Apply a soap/water solution or a liquid detergent to the indoor line set
connections and outdoor service port connections with a soft brush
to check for leakage of the connecting points of the tubing. If bubbles
are observed, it indicates leakage and must be immediately corrected.
2. Leak detector
Use the leak detector to check for leakage.
O
U
T
D
O
O
R
U
N
I
T
ELECTRICAL WIRING - OUTDOOR UNIT
CAUTION
5
Indoor unit
check point D
B
C
A
Outdoor unit
check point
Cover
NOTE:
Before performing any electrical work, turn the systems main power off.
1. The inside and outside connecting cable can be connected without removing the front grille.
2. The indoor power cord type is H05VV-F or H05V2V2-F, the outdoor power cord and
interconnected cord type is H07RN-F.
3. Lift the indoor unit panel up, remove the electrical box cover by removing the screw.
4. Ensure the color of wires of outdoor unit and the terminal identifications. are the same to the
indoor unit respectively.
5. Wrap those cables not connected with terminals with insulation tapes, so that they will not touch
any electrical components.
6. Secure the cable with the cord clamp.
NOTE:
NOTE:
Panel
Electrical box
cover
Terminal block of indoor unit
Terminal block of outdoor unit
Cover
Screw
Manual control
Button
AUTO/COOL
1
2
S
To outdoor unit
To indoor unit To power supply
1 2 S L1 L2
950-0182revC November 27, 2013
Exceeding the tightening torque will damage the flare surface.
NOTE:
NOTE:
1. Use a small screwdriver
for terminals.
2. Breaker size and wiring
must be sized per the rating
plate amperage. If smaller
than required breaker is used
there is a possibility of damage
and safety issues.
3. Use breaker as specified in
product label on the unit.
*** DO NOT CROSS WIRES BETWEEN TERMINALS. ***
***DO NOT IN STA LL A LI QU ID LINE SIGHT GLA SS O R FI LTER DRIER IN THE SYST EM . ** *
.
.
International Refrigeration Products warrants the accompanying split air conditioner or heat pump system
to be free of defects in material and workmanship for the applications specified in the operation manual
and installation manual for a period of one (1) year on parts and five (5) years on compressor, valid from the
date of original retail purchase in the United States or Canada. Labor or shipping is not covered under this
warranty.
Warranty card must be completed and sent in to activate the warranty for the accompanying unit. Warranty
may also be activated via the website www.irproducts.biz
WARRANTY
TECHNICAL SUPPORT
If you need technical support please call (215) 750-9876 M-F 8:00 am to 4:30 pm.
International Refrigeration Products
1035 Wheeler Way, Langhorne, PA 19047
.

950-0182revC November 27, 2013
TECHNICAL SPECIFICATIONS FOR 30000 and 36000 BTU UNITS (208-230V)
Thermal Zone (Indoor / Outdoor) 242-1106-E, 242-1106-C
MSM30H46ZEI, MSM30H46ZCI
242-1107-E, 242-1107-C
MSM36H44ZEI, MSM36H44ZCI
Sea Breeze (Indoor / Outdoor) 242-1306-E, 242-1306-C
30H46ZIMI, 30H46ZOMI
242-1307-E, 242-1307-C 36H44ZIMI,
36H44ZOMI
Power supply PH-V-Hz 1Ph,208/230V~,60Hz 1Ph, 208/230V~,60Hz
Cooling
Capacity BTU/H 30000 36000
Input W 2800 3000
Operating current A 15 16
SEER BTU/WH 16.0 14.5
EER BTU/WH 10 9.5
Heating
Capacity BTU/H 30000 36000
Input W 2860 3600
Rated current A 16 18
HSPF 9.6 9
Moisture Removal PNTS/H 6.3 8
Min. circuit Ampacity / Breaker Size A 16.0 / 25.0 20.0 / 30.0
Compressor
Model DA250S2C-30MT TNB306FPGMC-L
Type ROTARY ROTARY
Brand GMCC GMCC
Input W 2120 3080
Rated current(RLA) A 8.85 13.5
Locked rotor Amp(LRA) A / /
Thermal protector position Compressor Top Compressor Top
Capacitor uF / /
Refrigerant oil/oil charge ml ESTER OIL VG74/820 FV50S / 1100
Indoor fan motor
Model YDK65-4B YDK65-4B
Brand Welling Welling
Input W 113 / 87 / 68 113 / 87 / 68
Current A 0.51 0.78
Capacitor uF 3.0 3.0
Speed(H/M/L) RPM 1260 / 1090 / 950 1260 / 1090 / 950
Indoor air flow (H/M/L) CFM 942 942
Indoor noise level (H/M/L) dB(A) 50 / 48 / 46 50 / 48 / 46
Indoor unit
Dimension(W*H*D) IN 56 7/8 x 13 3/8 x 10 7/8 56 7/8 x 13 3/ 8 x 10 7/8
Packing (W*H*D) IN 60 1/4 x 14 3/8 x 16 9/16 60 1/4 x 14 3/8 x 16 9/16
Net/Gross weight LB 53 / 71 53 / 71
Outdoor fan motor
Model YDK53-6NB YDK180-8GB
Brand Welling Welling
Input W 157.3 / 93.8 299 / 223
Current A 0.75 0.78
Capacitor uF 2.5 10
Speed RPM 790 / 540 750 / 615
Outdoor air flow CFM 2060 2237
Outdoor noise level dB(A) 59 59
Outdoor unit
Dimension(W*H*D) IN 35 4/ 16 x 33 1/4 x 13 39 x 38 x 13 9/16
Packing (W*H*D) IN 41 1/16 x 36 x 15 9/16 44 1/8 x 43 5/16 x 17 1/8
Net/Gross weight IN 157 / 165 181 / 190
Refrigerant type Oz. R410A / 89.94 R410A / 97.0
Design pressure PSIG 550 / 340 550 / 340
Refrigerant piping
Liquid side/ Suction side
IN
3/8" / 5/8" 3/8" / 5/8"
Max. refrigerant pipe length FT 164 213
Maximum vert ical height FT 82 98
Design length FT 25 25
Extra Refrigerant charge
above design length OZ/FT 0.322 0.322
Thermostat type Remote Control Remote Control
Electrical Shock Protection I I
Indoor selection range - remote °F 62°F to 86°F 62°F to 86°F
Outdoor operating range (cooling/heating) °F 5°F to 122°F - Cooling
5°F to 92°F - Heating
5°F to 122°F - Cooling
5°F to 92°F - Heating
This manual suits for next models
3
Table of contents
Other International Refrigeration Products Heat Pump manuals
Popular Heat Pump manuals by other brands

Supreme Heating
Supreme Heating HEATSEEKER VORTEXPRO 10 KW Installation & user manual

STIEBEL ELTRON
STIEBEL ELTRON WWK 220 electronic Operation and installation

Nibe
Nibe F110 Installer manual

evoheat
evoheat Evo Flex Installation & operation manual

Panasonic
Panasonic WH-MDC06E3E5 Service manual

Graco
Graco HIGH-FLO 311211L Instructions - parts