- when water tank 1 reaches its assigned temperature, then the operation of circulation
pump 1 is being stopped and the heating of the second water tank is being started as
circulation pump 2 is being switched on. In this case circulation pump 2 will be started in case
temperature T3 in water tank 2 is lower than Tzad1 and there is a positive difference ∆t
between solar panel and water tank, grater than the assigned one temperatures dТ(Т1-
Т3>dT) (relay output 1 and 2).
- the operation of circulation pump 2 is being stopped in case of reaching Tzad1,
equalizing ∆t with dТor with decreasing of T2 concerning water tank 1 bellow Tzad. In the
last case after circulation pump 2 is being switched off circulation pump 1 is being switched
on for heating of water tank 1.
- If under the above mentioned conditions the solar panel temperature is going down
bellow Tcmin, then both circulation pumps operation will be stopped by force, despite of
conditions ∆t>dТand Т2<Tzad, Т3<Тzad1 could be available. (relay output 1 and 2)
- in case the solar panel temperature falls bellow Tdef, circulation pump 1 is being
switched on by force, never mind it has been switched off due to solar panel temperature
decreasing bellow Tcmin. (only in case the defrost option is activated)
- if during the previous mentioned operation mode water tank 1 temperature falls down
bellow Tbmin, then the circulation pump is being switched off as the solar panel defrosting is
being stopped.
В) Emergency operation
- if during water tanks heating, the solar panel temperature exceeds Tcmax, the circulation
pumps are being started by force in order to cool the solar panel. The previous mentioned will
be fulfilled despite of temperatures T2 and T3 of the water tanks could exceed Tzad and
Tzad1 (relay output 1 and 2).
- if during the above mentioned emergency mode the water tank temperatures reach the
critical maximum value Tbmax, then the circulation pumps are being switched off never
mind it could reflect to solar panel overheating. Thus the water tank temperature has a higher
priority than the solar panel one.
- when temperature T3 in water tank 2 exceeds Tvmax a valve is being switched on in
order to drain the hot water of the water tank (relay output 3).
ІV. Front panel indications
On the front panel are located the control elements and programming. These are two line
LCD display, seven light indications and three buttons, “SELECT”, “SCROLL” and ”SET”.
The front panel vision is shown at Figure 1 bellow.
4.1 Light indication 1 – shows the operation of circulation pump 1
4.2 Light indication 2 - shows the operation of circulation pump 2 (in case two water tanks
are installed) or heating of the water tank by means of electrical heating elements.
4.3 Light indication 3 – shows switched on valve for hot water draining.
4.4 Light indication 4 – shows emergency situation with the solar panel, for example a
maximum solar panel temperature is being reached or a defrost protection is activated.
4.5 Light indication 5 – show an emergency situation, the temperature in water tank 1 has
being reached the maximum allowed water tank temperature Tbmax.
4.6 Light indication 6 – show an emergency situation, the temperature in water tank 2 has
being reached the maximum allowed water tank temperature Tbmax.
4.7. Light indication 7 – shows that the unit is in a setting mode
After connection of the power supply the thermostat goes into an initial mode as it shows
the solar panel and water tank/tanks temperatures.