- The heating is done until the temperature at the top of the tank Tb2equals with setpoint
Tbset, then the pump is switched off;
- If the above conditions, the boiler drops below Tkmin, the pump operation is turn off,
however, that there may be ∆t2>dТ2+2° C and Тb2<Tbset;
- If the boiler temperature drops below Tkdef, pump 2 is force, although it has been
turned off because of temperatures below Tkmin.
- In systems with buffer tank, pump 2 operation is controlled by Tb1!
Conditions determining the operation of electric heaters on the tank:
- If the temperature at the top part of tank Tb2is lower than the set Thset-h.syst is
allowed heating by electric heaters (relay output 3). Does this happen when there are no
conditions for the pumps and heaters to work independent of the pump, select the option
"Heaters" in the menu (see section 4.2).
Conditions determining the operation of pump 3:
- With option Heaters Opt.3 (see section 4.2), the controller is configured to work with a
third pump that is connected to the relay output 3 instead of electric heaters and Tb2
sensor is mounted in the second tank
- At a temperature Tb2in the second heater below the setpoint Tbuff and panel
temperature Tp, as well as a positive difference Δt3between the temperature Tp of the
panel and the second heater, larger than the set dT1by 2 °C, turn on a pump 3 . But only
in cases where there is no running pump 1;
- Heating is performed while the temperature Tb2equals the set Tbuff, then the pump is
switched off;
- If the conditions for their turn on of pump 1, work pump 3 is terminated.
In this way the heating of the first heater is given priority.
B) Alarm Modes
- If in the process of heating the heater, the temperature of the panel exceeds Tpmax,
pump 1(and the pump 3 if used) will be forced the purpose cool the panels. This is done
despite the temperature at the bottom of the tank Tb1can exceed Tbset.
- If in the process of heating the heater, the temperature of the boiler exceeds Tkmax,
pump 2 (and the pump 3 if used ) is force for cooling of the boiler. This is done despite the
temperature at the bottom of the tank Tb1can exceed Tbset.
- If, at the above conditions temperature in the lower or upper part of the heater reaches
the critical maximum value Tbmax, pump 1 is turned off, although this may result to
overheating of the panel. In this way the temperature in the boiler has a higher priority to
the temperature of the panel.
In this case operation of the pump 2 also terminate.