INVT EC-IO801 User manual

EC-IO801 I/O Expansion Module EC-IO801 I/O Expansion Module EC-IO801 I/O Expansion Module
EC-IO801 I/O Expansion Module User Manual
Preface
Thank you for choosing INVT EC-IO801 I/O expansion module.
The EC-IO801 I/O expansion module is used with the GD880 series VFD control box.
This manual describes the product overview, installation, wiring, and commissioning
instructions. Before installing the VFD, read this manual carefully to ensure the proper
installation and running with the excellent performance and powerful functions into full
play.
Product features:
Supports analog input detection in voltage mode and current mode: AI1, AI2
Supports analog output detection in voltage mode and current mode: AO1, AO2
Supports configurable digital inputs and relay output: DI1, DI2, DI3, RO1
Provides power supply for DI: 24VDC
Enables flexible configuration of filtering time of AI and DI, improving the detection
stability of the module
1Product overview
1.1 Model description
Figure 1-1 Product nameplate and model designation
Nameplate
Product model
Manufacture No. XXXXXXXXXXXXXXX
EC-IO 801
Product model EC - IO 801
Distinguishing code
801: multi-functional IO expansion module
Module category
IO: IO expansion module
Product category
EC: expansion module
1.2 Specifications
Table 1-1 Specifications
Parameters
Specification
Working temperature
-10–50℃
Storage temperature
-20–60.0℃
Relative humidity
5%–95% (No condensation)
Running environment
No corrosive gas
Installation method
Fixed with snap-fits and screws
Ingress protection (IP) rating
IP20
Heat dissipation method
Natural air cooling
1.3 Structure
Figure 1-2 Structural diagram
3
5
4
2
1
67
8
9
10
Table 1-2 Component description
No.
Name
Description
1
STATUS
Status indicator
(green)
On: The expansion module is connecting with the control board.
Blinking (On: 500ms; Off: 500ms): The expansion module is
connected with the control board.
Off: The expansion module is disconnected from the control
board.
2 FAULT
Fault indicator (red)
On: The expansion module is faulty.
Off: The expansion module works normally.
3 Installation fixing
hole
To fix the expansion module and maintain a good connection of
the PE layer.
4 X1 connection
terminal Relay output terminal
5 X2 connection
terminal External power port
6 X3 connection
terminal Terminal for digital input and analog input
7 X4 connection
terminal Terminal for analog input and analog output
8 Nameplate Including the model and sequence number of the expansion
module
9 Connection port For electrical connection with the control box.
10 Positioning hole To align the expansion module and control box for easy
installation
2Installation and wiring
2.1 Installation precautions
Make sure the device has been powered off before installation.
Note
There are three expansion module interfaces on the control box
(expansion slot 1, expansion slot 2, expansion slot 3). You can use
expansion slot 1 or expansion slot 2 according to the actual wiring.
It is recommended to install the I/O expansion module at expansion
slot 2.
Required tools: Phillips screwdriver PH1, straight screwdriver SL3
Table 2-1 Screw torque requirements
Screw size
Fastening torque
M3
0.55 N·m
2.2 Dimensions
The dimensions of the I/O expansion module is 73.5×103×36.1mm (W*H*D).
Figure 2-1 Product dimensions (unit: mm)
73.5
103
53
M3
23.3
22.5
36.1
12 3 456
12 3 456
12 3 123
STATUS
FAULT
2.3 Installation instructions
It is recommended to place the I/O expansion module at expansion slot 1 of the control
box. The following is an example of the installation at slot 1.
Step 1 Place the module in the corresponding position of the control box expansion slot
2, align it with the slot, and then buckle it together.
Step 2 Align the expansion module positioning hole with the positioning stud.
Step 3 Fix with a M3 screw. The installation is complete.
Expansion
slot 1
Expansion
slot 2
Expansion
slot 3
Step 1 Step 2 Step 3
Note:
The expansion module and control box are electrically connected through slots. Please
install them in place.
To ensure the reliable operation of the expansion module and meet EMC requirements,
please tighten the screws according to the recommended torque for reliable
grounding.
2.4 Disassembly instructions
You can disassembly the module by reversing the order of steps described in section 2.3
Installation instructions.
Step 1 Disconnect all power supplies and disassemble all cables connected to the
expansion module.
Step 2 Use a Phillips screwdriver PH1 to remove the grounding screws of the module.
Step 3 Lift the module out of the control box positioning stud and pull it out to a suitable
position. Disassembly is complete.
2.5 User's wiring terminal
Figure 2-2 Product appearance
Table 2-2 X terminal function definition
Category
X
terminal
Terminal
definition
Description
Specifications
Relay
output
X1-1
RO1A
NO contact of
relay
1. Contact capacity: 3A/AC250V,
1A/DC30V
2. Cannot used as high frequency
switch output
X1-2
RO1B
NC contact of relay
X1-3
RO1C
Common contact
of relay
Power
supply
X2-1
COM
Digital reference
ground
1. Used to provide input digital
working power from the
external to the internal
2. PW and +24V have been short
connected.
3. Power supply: +24VDC
X2-2
PW
Power supply
X2-3
+24V
Power supply

EC-IO801 I/O Expansion Module EC-IO801 I/O Expansion Module EC-IO801 I/O Expansion Module
Category
X
terminal
Terminal
definition
Description
Specifications
Digital
input
X3-1
DI1
Digital input 1
1. Internal impedance: 3.3kΩ
2. 12–30V voltage input is
acceptable
3. Bi-direction input terminal
4. Max. input frequency: 1kHz
X3-2
DI2
Digital input 2
X3-3
DI3
Digital input 3
X3-4
COM
Digital reference
ground
Analog
input
X3-5
AI2+
Analog input 2
1. Input range: 0–10V or 0–20mA
2. Input impedance: 30KΩ for
voltage input; 500Ω for current
input
3. Whether voltage or current is
used for input is set through the
jumper J1, J2.
X3-6
AI2-
X4-5
AI1+
Analog input 1
X4-6
AI1-
Analog
output
X4-1
AO1
Analog output 1
1. Output range: 0–10V or 0–20mA
2. Whether voltage or current is
used for output is set through
the jumper J3, J4.
3. Error: ±1% at 25°C
X4-2
GND
Analog reference
ground
X4-3
AO2
Analog output 2
X4-4
GND
Analog reference
ground
Figure 2-3 External wiring diagram when using EC-IO801 expansion module
V
+24V
PE
COM
DI3
PW
PE
Expansion module
Digital input
DI1
DI2
AI1+
AI1-
0~+20mA
PE
D/A
conversion
Analog
output 1
Analog input 1
Analog input 2
PE
Analog
output 2
I
I
U
I
I
V
I
V
V
AI2+
AI2-
0~+10V
RO1C
RO1A
Relay output
RO1B
D/A
conversion
AO1
AO2
GND
GND
2.6 Wiring precautions
Figure 2-4 I/O module analog input/output signal connection diagram
J2
J1
J3
J4
VI
VI
VI
VI
Note:
Analog input should not exceed the range: 0–10V, 0–20mA.
Analog input/output type selection: The jumper selection signal (voltage or current)
must be consistent with the input method of the user interface.
As shown in Figure 2-4, J1/J2 are used to select the analog input signal type and J3/J4
are used to select the analog output signal type. For voltage signal input/output, short
circuit the two adjacent terminals at the upper part. For current signal input/output,
short circuit the two adjacent terminals at the lower part.
3Commissioning instruction
Figure 3-1 I/O expansion module configuration flowchart
The status is displayed
as 1: online.
Start
End
Check the electrical connection
of IO module is correct.
Wait for the module to be
powered on.
Configure AI, AO, DI, relay
parameters.
Set the slot position corresponding
to the module (P51.00, P52.00).
Check the parameters (P51.01,
P52.01) to confirm module status.
Y
N
Table 3-1 Function code parameters related to I/O expansion module
Function
code Name Description
Setting
range
Default
P51.00
(P52.00)
Module slot
selection
The system allows installing modules of
the same type in multiple slots and this
function code is used to select the
expansion slot at which the module is
enabled (P51.00 and P52.00 cannot be
set to the same value).
0: SLOT1
1: SLOT2
2: SLOT3
3: SLOT2-1
4: SLOT2-2
5: SLOT2-3
6: SLOT3-1
7: SLOT3-2
8: SLOT3-3
9: Invalid
0–9
9
P51.01
(P52.01)
Module
online status
Bit0: Online status of SLOT1 module
Bit1: Online status of SLOT2 module
Bit2: Online status of SLOT3 module
Bit3: Online status of SLOT2-1 module
Bit4: Online status of SLOT2-2 module
Bit5: Online status of SLOT2-3 module
Bit6: Online status of SLOT3-1 module
Bit7: Online status of SLOT3-2 module
Bit8: Online status of SLOT3-3 module
Online status
0: Offline
1: Online
0x00–
0x1FF
0x00
Note: For other parameter settings of the I/O expansion module, see software manuals
of the GD880 series products.
Other INVT I/O System manuals
Popular I/O System manuals by other brands

Industrial Shields
Industrial Shields M-DUINO PLC ARDUINO ETHERNET 58 manual

M-system
M-system R3Y-SV8N instruction manual

Aspar
Aspar Sfar Mini Modbus 1TE user manual

Assa Abloy
Assa Abloy effeff ePED Hi-O 1386IO Installation and fitting instructions

Sony
Sony LKRI-005 operating instructions

NI
NI 9223 Getting started guide