INVT Goodrive800 Pro Series User manual


Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Change history
No.
Change description
Version
Release date
1
Firstrelease.
V1.0
December2022
2
ModifiedthecontentinTable2-2,Table2-3;
Updatedthepowerinterfacedescriptionin
Table5-1,Table5-3;
Addednotecontentinsection2.8.1.
V1.1
August2023


Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Preface
202308 (V1.1) i
Preface
ThankyouforchoosingINVTGoodrive800Proseriesengineeringvariable-frequencydrive(VFD).
Foreaseofuse,readthemanualcarefullybeforeusingGoodrive800Proseriesproduct.
As an upgrade product of Goodrive800 series engineering VFD, Goodrive800 Pro series engineering VFD
inherits the high reliability feature of Goodrive800 platform but optimizes the upgrade, structure, and
components,achievingunitmodularization,flexiblecabinetconfiguration,morecompactstructure,easier
installationandmaintenance,andoptimumprotection.
Excellentspeedandtorquecontrolperformance
Modulardesign,asflexibleasbuildingblocks,whichmakestheprojectintegrationsimpleandefficient
Long-lifecomponentselectionandfastfaultrecoverydesigntoensureefficientprocesscontrol
Ergonomicdesigntomakeinstallationandmaintenanceeasier
Enrichedexpansioncapabilitytosupportvariousprotectionoptions
Goodrive800ProseriesengineeringVFDcanbewidelyusedin:
Metallurgy:Such ashigh-speed wirerodandhotstrip rollingequipment,wide andthickplate equipment,
cold rolling equipment, pickling lines, annealing lines, galvanizing line, color coating lines, non-ferrous
metalalloymanufacturingequipment,andnon-ferrousmetalrollingequipment
Petroleum: All-electric oil drilling rigs, large well repair machines, large oil machinery and equipment
electric-drivepowertransformation,oilfieldwaterinjectionequipmentandotherheavyoilequipment
Papermaking:Papermakingjointequipment,includingflowbox,netsection,presssection,dryingsection,
sizing,hardcalendering,coating,supercalender,rewinderandothercontinuousproductionlines
Port and other large lifting equipment: Such as shore-side container overhead cranes, tire-type (orbital)
container gantry cranes, grab unloaders, grab gantry cranes, large shipbuilding gantry cranes, and large
metallurgicalcastingcranes
Others:Suchas unittestbenches, militaryequipment,oiland gastransmission,and miningtransmission
equipment
Goodrive800-81seriesistheregenerativerectifierunitofGoodrive800Proseries.Ifnototherwisespecified,
theregenerativerectifierinthismanualreferstotheregenerativerectifierunitofGoodrive800 Proseries,
that is, Goodrive800-81 series product. The rated power of a single unit is 423kW–1027kW, and the max.
parallel power can be 5726kW. The regenerative rectifier consists of regenerative rectifier filter unit and
regenerativerectifierunit.Itiscompactinstructureandeasytointegrateandmaintain,reducingcabinet
footprint.
This manual is Goodrive800 Pro series regenerative rectifier hardware manual, presenting safety
precautions, product information, mechanicaland electrical installation, and precautions related to daily
maintenance. Read through this manual carefully before installation to ensure the VFD is installed and
operated in a proper manner to give full play to its excellent performance and powerful functions. If you
haveanyquestionaboutthefunctionandperformanceoftheproduct,pleaseconsultourtechnicalsupport.
Iftheproductisultimatelyusedformilitaryaffairsorweaponmanufacture,complywiththeexportcontrol
regulationsintheForeignTradeLawofthePeople'sRepublicofChinaandcompleterelatedformalities.
To continuously improve the performance of the product to meet higher application requirements, we
reservetherighttocontinuouslyimprovetheproductandaccordinglytheproductmanual,whichmaybe
madewithoutpriornotice.Wehavethefinalinterpretationofthemanualcontent.

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Contents
202308 (V1.1) ii
Contents
1 Safety precautions .....................................................................................................................................1
1.1Safetydeclaration.................................................................................................................................................1
1.2Safetydefinition....................................................................................................................................................1
1.3Warningsymbols...................................................................................................................................................1
1.4Safetyguidelines...................................................................................................................................................2
1.4.1Deliveryandinstallation.............................................................................................................................2
1.4.2Commissioningandrunning......................................................................................................................3
1.4.3Maintenanceandcomponentreplacement..............................................................................................3
1.4.4Disposal.......................................................................................................................................................3
2 Product overview .......................................................................................................................................4
2.1Productspecifications..........................................................................................................................................4
2.2Productnameplateandmodel............................................................................................................................5
2.3Productratings.....................................................................................................................................................5
2.4Overloadcapability...............................................................................................................................................6
2.5Hardwareprinciples.............................................................................................................................................7
2.5.1Basicprinciples...........................................................................................................................................7
2.5.2Parallelingprinciple....................................................................................................................................8
2.6Productstructure................................................................................................................................................10
2.6.1LayoutofL+A8..................................................................................................................................................10
2.6.2LayoutofL+2*A8..............................................................................................................................................11
2.7Systemconfiguration.........................................................................................................................................12
2.8Electricalmodelselection..................................................................................................................................12
2.8.1Buffercomponent.....................................................................................................................................12
2.8.2Breaker......................................................................................................................................................13
2.8.3ACfuse.......................................................................................................................................................13
2.8.4DCfuse.......................................................................................................................................................14
2.9Lightningprotectioncomponent.......................................................................................................................14
3 Mechanical installation ............................................................................................................................16
3.1Safetynotes.........................................................................................................................................................16
3.2Installationenvironment....................................................................................................................................16
3.3Preparing.............................................................................................................................................................17
3.3.1Unpackinginspection...............................................................................................................................17
3.3.2Transportation..........................................................................................................................................17
3.3.3Unpacking.................................................................................................................................................18
3.3.4Lifting........................................................................................................................................................19
3.3.5Installationspaceandheatdissipation...................................................................................................21
3.3.6Cabinetinstallation..................................................................................................................................22
3.3.7Fasteningtorque.......................................................................................................................................30
3.3.8Checklist....................................................................................................................................................31
4 Electrical installation ...............................................................................................................................32
4.1Safetynotes.........................................................................................................................................................32
4.2Insulationinspection..........................................................................................................................................32
4.3EMCregulations..................................................................................................................................................33
4.3.1Powercable...............................................................................................................................................34
4.3.2Controlcable.............................................................................................................................................35

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Contents
202308 (V1.1) iii
4.3.3Wiringsuggestions....................................................................................................................................35
4.3.4Shieldedcableconnection.......................................................................................................................37
4.4Electricalwiring..................................................................................................................................................38
4.4.1Maincircuitwiring....................................................................................................................................38
4.4.2Electricalinstallationchecklist................................................................................................................41
5 Rectifier Control Unit (RCU) ......................................................................................................................42
5.1RCUcomposition................................................................................................................................................42
5.2RCUsizeandinstallation....................................................................................................................................43
5.2.1Preparing...................................................................................................................................................43
5.2.2RCUsize.....................................................................................................................................................43
5.2.3RCUinstallationspace..............................................................................................................................43
5.2.4RCUinstallationprocedure......................................................................................................................45
5.3RCUinterface......................................................................................................................................................46
5.4RSTsignaldetectioncard...................................................................................................................................48
6 Maintenance and inspection .....................................................................................................................50
6.1Periodicalmaintenance......................................................................................................................................50
6.1.1Overview...................................................................................................................................................50
6.1.2Requiredtools...........................................................................................................................................50
6.1.3Maintenancecycle....................................................................................................................................50
6.2Replacementofwearingparts...........................................................................................................................52
6.2.1Coolingfan................................................................................................................................................52
6.2.2Replacementofregenerativerectifierfilterunitpowerbox...................................................................54
6.2.3Fusereplacement.....................................................................................................................................55
6.2.5Regenerativerectifierunit........................................................................................................................56
Appendix A Technical data ..........................................................................................................................58
A.1Deratedapplication............................................................................................................................................58
A.1.1Capacity....................................................................................................................................................58
A.1.2Derating....................................................................................................................................................58
A.2Gridspecifications..............................................................................................................................................59
A.3Applicationstandards........................................................................................................................................59
A.3.1CEmarking................................................................................................................................................59
A.3.2EMCcompliancedeclaration...................................................................................................................59
A.4EMCregulations..................................................................................................................................................59
A.4.1VFDcategoryofC2....................................................................................................................................60
A.4.2VFDcategoryofC3....................................................................................................................................60
Appendix B Expansion card .........................................................................................................................61
B.1Externalview......................................................................................................................................................61
B.2Namingrule........................................................................................................................................................61
B.3Function..............................................................................................................................................................62
Appendix C Dimension drawings .................................................................................................................67

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Safety precautions
202308 (V1.1) 1
1Safety precautions
1.1 Safety declaration
Read this manual carefully and follow all safety precautions before moving, installing, operating and
servicingtheproduct.Otherwise,equipmentdamageorphysicalinjuryordeathmaybecaused.
Weshallnotbeliableorresponsibleforanyequipmentdamageorphysicalinjuryordeathcauseddueto
youroryourcustomers'failuretofollowthesafetyprecautions.
1.2 Safety definition
Danger:Severepersonalinjuryorevendeathcanresultifrelatedrequirementsarenotfollowed.
Warning: Personalinjuryorequipmentdamagecanresultifrelatedrequirementsarenotfollowed.
Note:Actionstakentoensureproperrunning.
Trained and qualified professionals: People operating the equipment must have received professional
electrical and safety training and obtained the certificates, and must be familiar with all steps and
requirementsofequipmentinstalling,commissioning,runningandmaintainingandcapabletopreventany
emergencies.
1.3 Warning symbols
Warningscautionyouaboutconditionsthatcanresultinsevereinjuryordeathand/orequipmentdamage
andadviceonhowtopreventdangers.Thefollowingtableliststhewarningsymbolsinthismanual.
Symbol
Name
Description
Danger
Severepersonalinjury orevendeathcan resultifrelated requirements
arenotfollowed.
Warning
Personalinjuryorequipmentdamagecanresultifrelatedrequirements
arenotfollowed.
Electrostatic
discharge
ThePCBAmaybedamagedifrelatedrequirementsarenotfollowed.
Hotsides
Donottouch.Theregenerativerectifierbasemaybecomehot.
25 min
Electric
shock
As high voltage stillpresents in the buscapacitor after power off, wait
for at least 25 minutes (depending on the warning symbols on the
machine)afterpowerofftopreventelectricshock.
Note
Note
Actionstakentoensureproperrunning.

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Safety precautions
202308 (V1.1) 2
1.4 Safety guidelines
Onlytrainedandqualifiedprofessionalsareallowedtocarryoutrelatedoperations.
Donotperformwiring,inspectionorcomponentreplacementwhenpowersupplyis
applied.Ensurealltheinputpowersupplieshavebeendisconnectedbeforewiring
or inspection, and wait for at least the time designated on the Goodrive800 Pro
series product or until the DC bus voltage is less than 36V. The minimum waiting
timeislistedinthefollowing.
Model
Minimum waiting time
380V
>423kW
25minutes
690V
>685kW
25minutes
Do not refit the Goodrive800 Pro series product unless authorized; otherwise fire,
electricshockorotherinjurymayresult.
ThebasemaybecomehotwhentheGoodrive800Proseriesproductisrunning.Do
nottouch.Otherwise,youmaygetburnt.
TheelectricalpartsandcomponentsinsidetheGoodrive800Proseriesproductare
electrostaticsensitive.Takemeasurementstopreventelectrostaticdischargewhen
performingrelatedoperations.
1.4.1 Delivery and installation
Do not install the regenerative rectifier on inflammables. In addition, prevent the
regenerativerectifierfromcontactingoradheringtoinflammables.
Donotruntheregenerativerectifierifitisdamagedorincomplete.
Donotcontacttherectifierunitwithdampobjectsorbodyparts.Otherwise,electric
shockmayresult.
Note
Selectappropriatetoolsforregenerativerectifierdeliveryandinstallationtoensure
thesafeandproperrunningandavoidphysicalinjuryordeath.Toensurepersonal
safety,takemechanicalprotectivemeasureslikewearingsafetyshoesandworking
uniforms.
Protect the regenerative rectifier against physical shock or vibration during the
deliveryandinstallation.
Donotcarrytheproductonlybyitsfrontcoverasthecovermayfalloff.
Theinstallationsitemustbeawayfromchildrenandotherpublicplaces.
Preventthescrews,cablesandotherconductivepartsfromfallingintotherectifier
unit.
Asregenerativerectifierleakagecurrentcausedduringrunningmayexceed3.5mA,
ground properly and ensure the grounding resistance is less than 10Ω. The
conductivityofPEgroundingconductormustmeetthefollowingrequirements:
Power cable conductor
cross-sectional area S (mm2)
Grounding conductor
cross-sectional area (mm2)
S≤16
S
16<S≤35
16
35<S
S/2
R,S,andTarethepowerinputterminals,whileU,V,andWaretheDCbusoutput
terminals.Connecttheinputpowercablesandoutputbusbarsproperly;otherwise,
theregenerativerectifiermaybedamaged.

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Safety precautions
202308 (V1.1) 3
1.4.2 Commissioning and running
Cut off all power supplies connected to the regenerative rectifier before terminal
wiring, and wait for at least the time designated on the rectifier unit after
disconnectingthepowersupplies.
Highvoltagepresentsinsidetheregenerativerectifierduringrunning.Donotcarry
outanyoperationontherectifierunitduringrunningexceptforkeypadsetup.For
products at voltage class of 4 or 6, the control terminals form extra-low voltage
circuits. Therefore, you need to prevent the control terminals from connecting to
accessibleterminalsofotherdevices.
Beforeturningonthepowersupply,checkthecableconnectionstatus.
Preventanyonefromdirectlytouchingtheenergizedpartofthecabinetdoor.Pay
specialattentiontosafetywhenhandlingshieldsthataremadeofmetalsheets.
Donotdoanywithstandvoltagetestingduringregenerativerectifierconnection.
Disconnectthemotorcablebeforeperforminganyinsulationandvoltagewithstand
testsforthemotorormotorcable.
DonotopenthecabinetdoorsincehighvoltagepresentsinsidetheGoodrive800
Proseriesproductduringrunning.
Note
Do not switch on or switch off the input power supplies of regenerative rectifier
frequently.
If the regenerative rectifier has been stored for a long time without use, perform
checkingandcarryoutpilotrunfortheinverterunitbeforeusingitagain.
Closetheregenerativerectifierfrontcoverbeforerunning;otherwise,electricshock
mayoccur.
1.4.3 Maintenance and component replacement
Only trained and qualified professionals are allowed to perform maintenance,
inspection,andcomponentreplacementfortheregenerativerectifier.
Cutoffallpowersuppliesconnectedtotheproductbeforeterminalwiring,andwait
foratleastthetimedesignatedontherectifierunitafterdisconnectingthepower
supplies.
During maintenance and component replacement, take measures to prevent
screws, cables and other conductive matters from falling into the internal of the
regenerativerectifier.
Note
Usepropertorquetotightenscrews.
During maintenance and component replacement, keep the regenerative rectifier
and its parts and components away from combustible materials and ensure they
havenocombustiblematerialsadhered.
Donotcarryoutinsulationvoltage-endurancetestontheregenerativerectifier,or
measurethecontrolcircuitsoftherectifierunitwithamegohmmeter.
Duringmaintenanceandcomponentreplacement,takeproperanti-staticmeasures
ontheregenerativerectifieranditsinternalparts.
1.4.4 Disposal
Theregenerativerectifiercontainsheavymetals.Disposeofascraprectifierunitas
industrialwaste.
Dispose of a scrap product separately at an appropriate collection point but not
placeitinthenormalwastestream.

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Product overview
202308 (V1.1) 4
2Product overview
ForGoodrive800Proseriesregenerativerectifier,theratedpowerofasingleunitis423kW–1027kW,while
thatofparallelunitscanbeupto5726kW.Theregenerativerectifierconsistsofregenerativerectifierfilter
unitandregenerativerectifierunit.Itiscompactinstructureandeasytointegrateandmaintain,reducing
cabinetfootprint.
2.1 Product specifications
Table2-1Productspecifications
Description
Specifications
Basic
performance
ACinput
voltage
400Vsystem:380–480VAC3PH ±10%; the running time < 1min at
-15%
690Vsystem:520–690V AC 3PH ±10%; the running time < 1min at
-15%
Input
frequency
50Hzor60Hz;Allowedrange:47–63Hz
Unbalance
degree
Less than ±3% of the rated interphase voltage
Overload
capacity
Light overload: Overload running at 110% of the rated current is
allowedfor1minuteevery5minutes.
Heavyoverload:Overloadrunningat150%oftheratedcurrentis
allowedfor1minuteevery5minutes.
Working
efficiency
≥98%
Powerfactor
≥ 0.95 (@ rated current)
Environment
condition
Working
temperature
-10°C – +50°C; Derating is required when the ambient temperature
exceeds 40°C.
Relative
humidity
5%–95%,nocondensation
Installation
altitude
Below1000m(Deratingisrequiredwhenthealtitudeexceeds1000m.
Derateby1%foreveryincreaseof100m.)
Mechanical
data
Anti-vibration
performance
Compliantwith3M4vibrationlevelinGB/T4798.3
IPrating
Forthemodule:IP00
Forthecabinet:IP20(Optional:IP23andIP42)
Safety
performance
CompliantwithEN61800-5-1
Cooling
method
Forcedaircooling
Protection
function
Protection
function
Includingfunctionsofprotectionagainstshortcircuit,overcurrent,
overload,overvoltage,undervoltage,overtemperature,andphase
loss

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Product overview
202308 (V1.1) 5
2.2 Product nameplate and model
Figure2-1Productnameplate
Note: The preceding nameplate is a standard product nameplate example. The marking varies slightly
depending on the model.
The modeldesignation codecontainsbasic productinformationsuch asratedcurrent andrated voltage.
Youcanfindthemodeldesignationcodeontheproductnameplate.
Figure2-2Productmodel
GD800 81 0640 6 01- - - - Version
01:Proseries
Productseries
GD800:Goodrive800seriesengineeringVFD
Rating
0640:640A
Producttype
81:Regenerativerectifierunit/regenerativerectifierframe
04:Regenerativerectifierfilterunit
Voltageclass
4:AC3PH380V(-15%)–480V(+10%)
6:AC3PH520V(-15%)–690V(+10%)
Note:
The preceding model is only an example of GD800-81 models.
The model name of the regenerative rectifier unit contains the suffix ZJ.
2.3 Product ratings
UN=400V(Rangefrom380Vto480V).Theratedpower(423–3319kW)isvalidwhentheratedvoltageis400V.
Table2-2Ratingsof400Vsystemproductmodel
Model
Rating
Light overload
application
Heavy overload
application
Structure
Heat
dissipation
Air
volume
IN
IN
Imax
SN
PN
ILd
PLd
Ihd
PHd
A(AC)
A(DC)
A(DC)
kVA
kW (DC)
A(DC)
kW (DC)
A(DC)
kW (DC)
kW
m³/h
GD800-81-0640-4-01
640
783
1018
443
423
752
406
587
317
A8+L
4.9
3000
GD800-81-0900-4-01
900
1102
1432
624
595
1057
571
826
446
A8+L
6.88
3000
GD800-81-1180-4-01
1180
1445
1879
818
780
1387
749
1081
584
2*A8+L
8.4
4500

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Product overview
202308 (V1.1) 6
Model
Rating
Light overload
application
Heavy overload
application
Structure
Heat
dissipation
Air
volume
IN
IN
Imax
SN
PN
ILd
PLd
Ihd
PHd
A(AC)
A(DC)
A(DC)
kVA
kW (DC)
A(DC)
kW (DC)
A(DC)
kW (DC)
kW
m³/h
GD800-81-1770-4-01
1770
2168
2818
1226
1171
2081
1124
1622
876
2*A8+L
12.2
4500
GD800-81-2360-4-01
2360
2890
3758
1636
1560
2774
1498
2162
1168
2*(2*A8+L)
16.8
9000
GD800-81-3540-4-01
3540
4336
5636
2452
2342
4162
2248
3244
1752
2*(2*A8+L)
24.4
9000
GD800-81-5310-4-01
5310
6504
8454
3678
3513
6243
3372
4866
2628
3*(2*A8+L)
36.6
13500
UN=690V(Rangefrom520Vto690V).Theratedpower(685–5726kW)isvalidwhentheratedvoltageis690V.
Table2-3Ratingsof690Vsystemproductmodel
Model
Rating
Light overload
application
Heavy overload
application
Structure
Heat
dissipation
Air
volume
IN
IN
Imax
SN
PN
ILd
PLd
Ihd
PHd
A(AC)
A(DC)
A(DC)
kVA
kW (DC)
A(DC)
kW (DC)
A(DC)
kW (DC)
kW
m³/h
GD800-81-0600-6-01
600
734
955
717
685
705
657
550
512
A8+L
5.4
3000
GD800-81-0900-6-01
900
1102
1432
1076
1027
1058
986
824
768
A8+L
7.2
3000
GD800-81-1180-6-01
1180
1445
1879
1410
1346
1387
1292
1081
1007
2*A8+L
9.3
4500
GD800-81-1770-6-01
1770
2168
2818
2115
2019
2081
1939
1622
1510
2*A8+L
12.3
4500
GD800-81-2360-6-01
2360
2890
3758
2820
2692
2774
2584
2162
2014
2*(2*A8+L)
18.6
9000
GD800-81-3540-6-01
3540
4336
5636
4230
4038
4162
3878
3244
3020
2*(2*A8+L)
24.6
9000
GD800-81-5310-6-01
5310
6504
8454
6345
6057
6243
5817
4866
4530
3*(2*A8+L)
36.9
13500
Note:
Thevoltagedropofthegridtransformershouldnotbelessthan4%attheratedcurrent.
INindicates the rated current for continuous running when no overload occurs at 40℃, while Imax
indicatesthemax.outputcurrent.
Lightoverloadapplication:ILd indicatesthecontinuousrunningcurrentatlightoverload.Every5
minutes,theoverloadwiththecurrentof110%*ILd can last for 1 minutes at 40℃.
Heavyoverloadapplication:ILd indicatesthecontinuousrunningcurrentatheavyoverload.Every5
minutes,theoverloadwiththecurrentof150%*IHd can last for 1 minutes at 40℃.
2.4 Overload capability
Basedonthelightoverloadcontinuousruncurrent(ILd),theregenerativerectifiercankeeprunningfor60s
at110%oftheratedcurrent.SeeFigure2-3.

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Product overview
202308 (V1.1) 7
Figure2-3Lightoverloadapplication
60s
Short-timeoverloadcurrent
110%ILD
LightoverloadratingILD RatedcurrentIN(Continuous)
Basedontheheavyoverloadcontinuousruncurrent(ILd),theregenerativerectifiercankeeprunningfor60s
at150%oftheratedcurrent.SeeFigure2-4.
Figure2-4Heavyoverloadapplication
60s 60s
300s
Short-timeoverloadcurrent
Heavyoverloadrating
RatedcurrentIN(Continuous)
150%IHD
IHD
2.5 Hardware principles
2.5.1 Basic principles
The regenerative rectifier, a four-quadrant rectifier system, mainly consists of regenerative rectifier filter
unitandregenerativerectifierunit.Itisusedwiththepre-chargecircuitandcontrolunit.Theregenerative
rectifier unit converts 3PH AC voltage into intermediate DC voltage, and the intermediateDC voltage can
supply the subsequentinverter modules todrive motors. It can also feed the regenerative energy of the
motorbacktothegrid.Oneormultipleinvertermodulescanbeinstalled.
The regenerative rectifier filter unit, which is the filter, is used to suppress input orregenerative current
harmonics.
TheregenerativerectifiermainlyconsistsofACfuse,regenerativerectifierfilterunit,andDCfuse.Figure2-5
showsthesimplifiedmaincircuit.

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Product overview
202308 (V1.1) 8
Figure2-5Simplifiedmaincircuitdiagramoftheregenerativerectifier
Regenerative
reactor
Regenerative rectifier
filter unit
Regenerative rectifier
unit
R
S
T
DC+
DC-
2
3
4
1
No.
Name
Description
1
ACfuse
To protect against overload and short-circuit on the
regenerativerectifierunitside.
2
Regenerativerectifier
filterunit
TosuppressACvoltageandcurrentharmonics.
3
Regenerativerectifier
unit
ToconvertACcurrenttoDCcurrent.
4
DCfuse
To prevent backend short circuit from causing machine
burndown.
Note: The AC fuse is not a component of the regenerated rectifier. You can choose to configure AC
fuses according to the actual application requirements.
2.5.2 Paralleling principle
TheregenerativerectifiersupportsparalleluseinL+2A8framestructure,thatis,oneregenerativerectifier
filter unit is connected with two regenerative rectifier units, as shown in Figure 2-6. To meet the
requirementsofgreatercapacity,theparallelpattern(L+2A8)*Nshouldbeused,whereNcannotbegreater
than3.Inparallelconnection,ensurethattheregenerativerectifierfilterunitshavethesamespecifications
andregenerativerectifierunitsusethesamesoftwareandhardware.

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Product overview
202308 (V1.1) 9
Figure2-6Simplifiedparallelsystemdiagramoftheregenerativerectifier
Regenerative
reactor
Regenerative
rectifier filter unit
Regenerative rectifier
unit
R
S
T
DC+
DC-
2
3
4
1
Regenerative rectifier
unit
DC+
DC-
3
4
No.
Name
Description
1
ACfuse
Toprotectagainstoverloadandshort-circuitonthe
regenerativerectifierunitside.
2
Regenerativerectifierfilter
unit
TosuppressACvoltageandcurrentharmonics.
3
Regenerativerectifierunit
ToconvertACcurrenttoDCcurrent.
4
DCfuse
Topreventbackendshortcircuitfromcausingmachine
burndown.

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Product overview
202308 (V1.1) 10
2.6 Product structure
2.6.1 Layout of L+A8
ThefollowingfigureshowstheframelayoutofL+A8.
Figure2-7Structureofregeneratedrectifierframe(L+A8)
4
3
1
2
No.
Name
1
Cabinet
2
Regenerativerectifierunit
3
Regenerativerectifierfilterunit
4
Channelsteelbase

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Product overview
202308 (V1.1) 11
2.6.2 Layout of L+2*A8
ThefollowingfigureshowstheframelayoutofL+2*A8.
Figure2-8Structureofregeneratedrectifierframe(L+2*A8)
5
43
2
1
No.
Name
1
Cabinet
2
Regenerativerectifierunit
3
Regenerativerectifierfilterunit
4
Regenerativerectifierunit
5
Channelsteelbase

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Product overview
202308 (V1.1) 12
2.7 System configuration
Figure2-9showsthetypicaltopologyinwhichtheregenerativerectifierworkswiththreeinverterunits.
Figure2-9Systemconfiguration
12
11
10
98
7
6
5432
1
No.
Name
1
Transformer
2
Breaker
3
Regenerativerectifierfilterunit
4
Regenerativerectifierunit
5
RectifierunitDCfuse
6
InverterunitDCfuse
7
Inverterunit
8
Bufferbreaker
9
Buffercontactor
10
Rectifierbridge
11
Bufferresistor
12
Motor
Note: The induction voltage drop of the transformer should not be less than 4% at the rated current.
2.8 Electrical model selection
2.8.1 Buffer component
Thebuffercomponentconsistsofbreaker,contactor,rectifierbridge,andbufferresistor,asshowninFigure
2-9. Table2-4Buffercomponentselection
Power supply module
Rated current
Recommended
specification
Recommended model
Qty
Buffer breaker
400V
640–1770A
690V63A
CDM6i-63L/3300
1
690V
600–1770A
690V63A
CDM6i-63L/3300
1
Buffer contactor

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Product overview
202308 (V1.1) 13
Power supply module
Rated current
Recommended
specification
Recommended model
Qty
400V
640–1770A
690V65A
LC1-D65M7C
1
690V
600–1770A
690V65A
LC1-D65M7C
1
Buffer rectifier bridge
400V
640–1770A
200A,1600V
3-phaserectifierbridgeMDS200-16
1
690V
600–1770A
200A,2400V
3-phaserectifierbridge
MD200S24M3
1
Buffer resistor
400V
640–1770A
5Ω, 1000W
Power resistor;520W;10Ω
2
690V
600–1770A
5Ω, 1000W
Power resistor;520W;10Ω
2
Note:
Forbuffercircuitconfigurationswithacurrentgreaterthan1770A,pleaseconsultlocaltechnical
support.
Topreventoverheatingofthechargingresistor,itisrecommendedtohaveatimeintervalofnoless
thanthreeminutesbetweentwobrakeclosingoperations.
2.8.2 Breaker
A breaker can effectively prevent the overload of the variable-frequency equipment and break the fault
currentgeneratedbythephase-to-phaseorto-groundshortcircuit,andatthesametimeithasthefunction
ofisolationsoastoavoidelectricshockaccidentsduringmaintenance.
The breaker should be equipped with an external terminal to controls the opening and closing of the
breaker and a status feedback auxiliary contact!
Table2-5Breakermodelselection
Power supply module
Frame size
Recommended
specification
Recommended breaker
(ABB)
Qty
GD800-81-0640-4
L+A8
690V800A
T7S800M
1
GD800-81-0900-4
L+A8
690V1000A
T7S1000M
1
GD800-81-1180-4
L+2*A8
690V1600A
T7S1600M
1
GD800-81-1770-4
L+2*A8
690V2000A
E3S2000
1
GD800-81-2380-4
2*(L+2*A8)
690V3200A
E3S3200
1
GD800-81-3348-4
2*(L+2*A8)
690V4000A
E4S4000
1
GD800-81-5022-4
3*(L+2*A8)
690V6300A
E6H6300
1
GD800-81-0600-6
L+A8
690V800A
T7S800M
1
GD800-81-0900-6
L+A8
690V1000A
T7S1000M
1
GD800-81-1180-6
L+2*A8
690V1600A
T7S1600M
1
GD800-81-1770-6
L+2*A8
690V2000A
E3S2000
1
GD800-81-2360-6
2*(L+2*A8)
690V3200
E3S3200
1
GD800-81-3540-6
2*(L+2*A8)
690V4000A
E4S4000
1
GD800-81-5310-6
3*(L+2*A8)
690V6300A
E6H6300
1
2.8.3 AC fuse
An AC fuse protects the rectifier unit and input power cable in case of short circuit, avoiding thermal
overload.SeethefollowingtabletoselectACfuses.

Goodrive800 Pro Series Regenerative Rectifier Hardware Manual Product overview
202308 (V1.1) 14
Table2-6ACfusemodelselection
Power supply
module
Frame size
Voltage (V)
Current (A)
Qty
GD800-81-0640-4
L+A8
690V
1000A
3
GD800-81-0900-4
L+A8
690V
1250A
3
GD800-81-1180-4
L+2*A8
690V
1000A
6
GD800-81-1770-4
L+2*A8
690V
1250A
6
GD800-81-0600-6
L+A8
690V
1000A
3
GD800-81-0900-6
L+A8
690V
1250A
3
GD800-81-1180-6
L+2*A8
690V
1000A
6
GD800-81-1770-6
L+2*A8
690V
1250A
6
2.8.4 DC fuse
ADCfuseprotectstherectifierunitandDCbusincaseofshortcircuit,avoidingthermaloverload.Thesame
brandreplacementprincipleshouldbefollowed.Seethefollowingtableforselection.
Table2-7DCfusemodelselection
Power supply module
Frame size
Voltage (V)
Current (A)
Qty
GD800-81-0640-4
L+A8
690V
1250A
2
GD800-81-0900-4
L+A8
690V
1000A
4
GD800-81-1180-4
L+2*A8
690V
1250A
4
GD800-81-1770-4
L+2*A8
690V
1000A
8
GD800-81-0600-6
L+A8
1250V
700A
4
GD800-81-0900-6
L+A8
1250V
900A
4
GD800-81-1180-6
L+2*A8
1250V
700A
8
GD800-81-1770-6
L+2*A8
1250V
900A
8
2.9 Lightning protection component
TheproductadoptsINVTlightningprotectioncomponenttopreventdamagefromlightningandsurge.The
lightningprotection component isinstalledinthe incomingcablecabinetand connected totheoutgoing
sideofmaincircuitbreaker.Figure2-10showsthedimensionsofthecomponent.
Figure2-10Dimensiondrawingsoflightningprotectioncomponent