IR-Tec OS-NET SRP-281 Operating instructions

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 2
Table of Contents
1. OS-NET INTRODUCTION.......................................................................................3
2. BASIC OPERATION................................................................................................3
OPERATIONNOTES.................................................................................................................................................. 4
2.1 MAINMENU................................................................................................................................................ 5
2.2 ON/OFFCONTROL........................................................................................................................................ 5
2.3 SETTING....................................................................................................................................................... 5
2.4 UPLOAD....................................................................................................................................................... 6
2.5 DOWNLOAD................................................................................................................................................. 6
3. SETTING................................................................................................................7
3.1 SETTING ITEMS............................................................................................................................................ 7
3.2 GROUPLINKSETTING...................................................................................................................................... 8
·EZ-GROUP................................................................................................................................................ 8
·ADVANCED............................................................................................................................................... 8
·UNGROUP................................................................................................................................................ 8
3.3 CREATING A NEW OS-NETNETWORK.................................................................................................................... 9
3.4 ADDING MORE OS-NETDEVICES TO AN EXISTING NETWORK........................................................................................ 9
3.5 DEVICE SETTING.............................................................................................................................................. 9
·CONTROL................................................................................................................................................. 9
·AMBIENTLUX..........................................................................................................................................11
·DELAY......................................................................................................................................................11
·TIMEOFF ................................................................................................................................................11
·HIGHDIM................................................................................................................................................12
·LOWDIM/SmartDIM...............................................................................................................................12
·RAMPUP................................................................................................................................................12
·FADEDOWN............................................................................................................................................12
·VM-TB.....................................................................................................................................................12
·VM-TA.....................................................................................................................................................12
·SENSITIVITY.............................................................................................................................................12
·BURN-IN..................................................................................................................................................12
·TEST(10-MIN).........................................................................................................................................12
·LEDINDICATOR........................................................................................................................................12
·DEFAULT..................................................................................................................................................13
3.6 LOCK/UNLOCK.............................................................................................................................................13
3.7 SAVE/RECALL ..............................................................................................................................................14
·SAVE AS...................................................................................................................................................14
·RECALL....................................................................................................................................................14
4. SETTING ACKNOWLEDGMENT INDICATION.......................................................15

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 3
1. OS-NET Introduction
Thank you for your interest in OS-NET,a simpler and smarter wireless lighting control solution developed by IR-TEC to
enable sophisticated controls onevery luminaire and lighting circuit. The OS-NET is also a wireless sensor mesh network
simultaneously deployedthrough installingthe OS-NET enabled luminaires andlighting circuits. TheOS-NETenabled
luminaire refersto the luminaire integratedwith anOS-NETSensor, and the OS-NETenabled lighting circuit refers tothe
power lineelectrically controlledby an OS-NETSensor.
The OS-NET network is formed by a number of wirelessly connected OS-NET devices; mainly refer to the OS-NET Sensors
(ONS) and the OS-NET Buttons (ONB). Each device not only provides its distinctive functionalities, but also operates as a
node to transmit, receive, orforward wireless communication commands within network.
After installing an OS-NET enabled lighting system, every OS-NET device should be grouped and linked with the network
to enable smart lighting control as desired via operating a SRP-281, a 2-way IR remote programmer exclusively designed
forconfiguring OS-NET devices. This guideis prepared to help conductallnecessaryconfigurations and settings correctly.
Pleaseread through all the contents prior to any programming operation.
2. Basic Operation
The SRP-281is ahandheldprogrammingtoolforyoutoconfigure thesettingsofOS-NETnetworkand devices. In
addition, it can also be used as a remoteto manually turn on/off the OS-NET enabled lighting in individual/group basis.
Before operating the SRP-281, ensure that good batteries are correctly placed in thecompartment. Press any button will
activate the MAIN MENU foroperating. 6buttons are available for operationwith distinctivefunctionsdescribedas
below;
BUTTON MAIN MENU SETTING PAGE
Enter into UPLOAD page Move UP setting bar
Enter into DOWNLOAD page Move DOWN setting bar
Turn ON the controlled light Decrease the setting
Turn OFF the controlled light Increasethe setting
Enter into SETTING pages Confirm the operation
Upload the setting
Swop individual/group on-off Back to previous page
Thecontents of thisguide are prepared according to theSRP-281 available atthetimewhen theguide is created.Due tocontinuous
product improvementefforts, certaincontents may notbe updatedin time.Shouldyou find any typo or incorrect contents,we would
appreciate ifyou can reportto support@irtec.com.

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 4
OPERATION NOTES
The LCD will automatically shut off 1 minute after the
last buttonoperationto savethe batterypower.
Pressing any button will activate the LCD.
If low battery sign appears while activating the LCD,
please replace with new batteries as soon as possible.
The rubber sleeve not onlyprotects the remote from
falling, but also ensures better programming reliability.
Always have therubber sleeve on the remote.
To avoid programming to the nearby sensor, alwaysaim
andholdtheremote “rightunderthe target sensor”
while uploading.
To ensure successfuldownload,alwaysaim the remote
underthe target sensorand holduntil download
completed. Do NOT remove duringdownloading.
Stronglighton the windowof remotecouldaffect
remote operation. Avoid downloading the sensor with
strong lightnearby or directsunlightfrom the back.
Some setting operationsmay beinhibited if the
network is locked.Ensureto unlock thenetwork prior
to setting change or adding newdevices.
The OS-NET Sensor will beep and blink the LED to
acknowledge successful setting,and theOS-NET Button
will blink the LED to acknowledge successful setting.

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 5
2.1 MAIN MENU
The main menu allows you to conduct basicoperationsas below;
lTo enter into SETTING pages, press
lTo conduct UPLOAD operation, press
lTo conduct DOWNLOAD operation,press
lTo turn OFF the light, aimat the sensor and press
lTo turn ON the light*, aim at the sensor and press
lTo swop individual or group control, press
*OS-NET will resume control after the delay timeelapsed.
2.2 ON/OFF CONTROL
Press the / buttonwith remoteaimingtoward an OS-NET Sensor will turnON/OFF thelights in individual
or group basis. You may press the buttonto swop the individual or group on/off control.
If a single-lamp(5) displays as the above left, it means that pressing the ON/OFF button will turn on/off only the lights
physically controlledby the individualOS-NET Sensor. If a double-lamp (55) displays as the aboveright, it means that
pressing the ON/OFF button will turn on/off all lighting groups of the OS-NET Sensor assigned.
2.3 SETTING
The SETTING pages allow youto setup/change the settingsof OS-NETdevices,includinggroup link,devicecontrol,
save/recall, and lock/unlock. The following are general instructions for SETTING operation. More details are available in
section 3.
Operation Instructions Displays
1. Press toenterinto SETTINGpagesfromMAIN MENU.
2. Press or to select the setting optionand press to enter.
GROUP LINK (Group the deviceand link tothe network)
DEVICE (Sethowthesensor will control theconnectedlight)
LOCK/UNLOCK (Lock/unlock the network)
SAVE/RECALL (Save/recall the control settings)
3. Press or toselectthe setting item,press to enter. Press
or to select the desired parameter.
4. Afterall items are selected,aim the remoteat the target device and press
to upload the setting data.
5. If you wantothersensorstohave identical setting,justaimat thesensorand
press to duplicate the setting.
1. MAIN MENU
2. SETTING options
NOTE: To setup newly installed OS-NET sensors, complete the GROUP LINK setting for all sensors first. Then execute
the DEVICE control settings via GROUP-SETto save time.
NOTE: It may take several seconds to complete data transmission, please aim and hold the remote right under the
sensor while uploading.
GroupOn/OffIndividual On/Off

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 6
2.4 UPLOAD
The UPLOAD function allows you to configure sensor settings via simple remote operation. You may select the CURRENT
SETTING or an EZ-SET profile for uploading to a specific OS-NET Sensor.
Operation Instructions Displays
1. Press toenterinto UPLOADpagesfromMAINMENUwithoptionsbelow;
CURRENT SETTING (Upload the current settings of the remote)
EZ-SET 1 (Upload theEZ-SET1 profile stored in theremote)
EZ-SET 2 (Upload theEZ-SET2 profile stored in theremote)
EZ-SET 3 (Upload theEZ-SET3 profile stored in theremote)
EZ-SET 4 (Upload theEZ-SET4 profile stored in theremote)
2. Press or to select the profile for uploading. Press to enter into
next page with below options;
GROUP LINK (Upload the group setting)
DEVICE (Upload the devicecontrol setting)
BOTH (Upload both the group and device control settings)
3. Press or to select the data foruploading. Press to confirm.
4. Aim the remote at the target sensorandpress to upload the data.
5. The remote will display UPLOAD OK following with a successful upload. If
UPLOAD FAIL displays, press to try again.
1. MAIN MENU
2. UPLOADpages
NOTE: GROUP-SET is not available for UPLOAD operation, so you can only upload the setting to one sensor at a time.
NOTE: It may take several seconds to complete data transmission, please aim and hold the remote while uploading.
2.5 DOWNLOAD
The DOWNLOAD function allowsyouto read many data, includinggroup member, device setting,current dim level,and
currentlux,from aninstalledsensorwhile youcan alsoobtain basic informationof the remoteandnetwork. The
following are general instructions for DOWNLOAD operation.
Operation Instructions Displays
1. Press to enterinto DOWNLOADpagesfromMAIN MENUwith below
options
GROUP INFO (Downloadthegroupinfooftargetsensor)
DEVICE SETTING (Download the control setting of target sensor)
CURRENT DIM (Download the current dim level of target sensor)
CURRENT LUX (Download the current luxlevelof target sensor)
REMOTE INFO (Download the deviceinfoof theremote)
DEVICE INFO (Downloadthedevice infoof target sensoror button)
NETWORK INFO (Downloadthenetworkinfoof target sensor)
2. Press or to select the download option, press to confirm.
3. Aim the remoteat thetargetdevice(excl. REMOTE INFO) and press to
download the data.
4. The remote will display DOWNLOADOK follow with a successful download. If
DOWNLOAD FAIL displays, press to try again.
1. MAIN MENU
2. DOWNLOADpages
NOTE: Downloadeddata ofGROUPINFOand DEVICESETTINGwill be displayedon therespective pages.
NOTE: It takes several seconds to complete data transmission, please aim and hold the remote while downloading.

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 7
3. Setting
3.1 SETTING ITEMS
The table below highlights all setting items of the SRP-281. Due to distinctive functionality, most setting items and
options arenot applicablefor OS-NETButton. Theremote will display N/A to indicatenot-applicablesettings.
Setting Item Brief Description ONS ONB
GROUP
LINK EZ-GROUP Easy group assignment to all OS-NET devices √ √
ADVANCED Setting special control, such as pre-lighting or directional guide lighting √ √
UNGROUP Disengage the devicefrom the network connected √ √
DEVICE INDIV-SET To set the sensing control scheme in individual basis √
GROUP-SET To setthegroupedsensors with samecontrolschemesandparameters √
CONTROL Available sensing control schemes of OS-NET sensor √
AMBIENT LUX Thresholds of ambient light level for OS-NET sensor to execute control √
DELAY
T
ime that
the
sensor will turn off or fade downthe
controlled
light
afterthe area is vacated. √
TIME OFF
T
ime thatsensorwillkeepthe light atlowdim levelafterthe
DELAY
time elapsed. Only available with the OSLATO control. √
HIGH DIM
T
he output level set tocontrol the light during occupancy, orwhen
ambientlight islower than thethreshold if daylight sensingcontrol
scheme is selected. √
LOW DIM/
SmartDIM
L
o
wdim istheoutputlevelsettodimthe light whenspaceis
vacant
.
This setting will become SmartDIM bar if SmartDIM control is selected. √
RAMP UP
The s
peed of lighting output increas
e
.
√
FADE DOWN
The s
peed of lighting output decrease.
√
VM-TB
Time duration BEFORE Virtual Midnight. Only available if
DSVM is
selected. √
VM-TA
Time duration AFTER Virtual Midnight.
Only available if DSVM is
selected. √
SENSITIVITY
Occupancy sensing
sensitivity
.
To disable the occupancy sensing capability, select OFF. √
ON DELAY
D
elaytime to turnon the loadafter
detecting the presence of
occupant. This setting is reserved for HVAC control, N/A for lighting.
BURN-IN
Time duration for burn
-
intest. Toconduct the burn
-
intest with
uncertain duration, selectMANUAL. √
TEST
Sensor
will control the light as the
scheme
set
, but with 10 seconds
delay.Automatic exit to resume normal control after 10 minutes. √
LED INDICATOR
E
nableor disablethe LEDindicator of
OS
-
NET devices.
√ √
DEFAULT
Resume factory default settings
of the REMOTE or DEVICE.
√
LOCK/
UNLOCK LOCK
Close the network to inhibit
OS
-
NET setting
change.
√ √
UNLOCK
Open the network to allow
OS
-
NET setting
change.
√ √
AUTO LOCK
Automatically lock thenetwork 12 hoursaftercreated.
√ √
SAVE/
RECALL SAVE AS
Save the settings as anEZ
-
SET profile forfuture use.
√
RECALL
Recallan EZ
-
SET profile saved
in the remote.
√

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 8
3.2 GROUP LINK setting
GROUP LINK is a fundamental setting forall OS-NET devices of an OS-NET enabled lighting system. Every OS-NET device
must beassigned to agroupto linkup thenetwork. To conduct GROUPLINK setting,press from MAIN MENU
and select the GROUP LINK to enter the setting pages. Threeoptions are available for selection.
lEZ-GROUP
EZ-GROUPsetting allowsyou toquickly groupand link the OS-NET devicesto the network. Most group controls can be
achievedby EZ-GROUP setting. Followthe proceduresbelowto conductEZ-GROUP setting;
1. Afterentering the EZ-GROUPpage, youcansee 4 lines of MBR OF GRP(Memberof Group) forgroup number
assignment.Each line representsa member of groupto beassigned for the device.
2. Press or to select the group number(001-250) to be assigned forthe target device. If the target
sensorisa memberof multiplegroups, you should alsoselect thegroupnumberforthe2nd,3rd or 4th line.
3. Aim at the target sensor and press to upload the grouping data while also linking up the network.
NOTE: The grouping sensor will blink its LED inBLUE and GREEN intermittently while linking up the network and
eventually display in GREEN to indicate successfulnetwork linkage.
Changing Group
To change the group assignment of a specificdevice, enter the EZ-GROUPpage and select the NEWgroupnumber(s) to
be assigned, aim at the target device and press to upload the grouping data. The sensorwill switch on and off
the connected light two timesto acknowledge the group change.
lADVANCED
Although most group controlscan be achieved by EZ-GROUPsetting, some specificspaces may require sophisticated
group control.This would require the ADVANCEDsetting.
Exampleof specialgroupcontrol:When Zone A isoccupied, the lightingof ZoneA and B shouldbe activated. Butwhen
Zone B isoccupied, onlythe lightingof ZoneBare required to be activated.
The group control of OS-NET Sensors isactually a combined operation of TRANSMITTING and RECEIVING groups. To
achieve the above control, you canuseEZ-GROUPto setup the OS-NET Sensors of ZoneA and ZoneB with respective
group numbers. Then usethe ADVANCED setting tochange the number of TRANSMITTINGor RECEIVINGgroup of zone
sensors. You can eitheradd thegroup number of Zone B to the TRANSMITTINGgroup of Zone A sensors, oradd group
number of ZoneA tothe RECEIVINGgroup ofZoneB sensors.
lUNGROUP
The UNGROUP settingcan be usedto off-link aspecificOS-NET device fromthe connected network. Ungrouping an
OS-NETdevice may be needed if the device hasbeen mistakenlyconnectedto the neighboring network. Toungroupan
OS-NETdevice, select the UNGROUPunder the GROUPLINKpage, and press to enter the UNGROUPING page.
Press or to select YES and press to confirm UNGROUPING. Aimtoward the target device and press
againto ungroup.
NOTE: An ungrouped OS-NET Sensor can still control the connected lightsin standalone basis as set,but an ungrouped
OS-NET Button is functionless.

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 9
3.3 Creating a new OS-NET network
After installing the OS-NET enabled lighting system, anew OS-NET network should be created to link all devices to
enablethe group control. Follow the instructionsbelowto create anew OS-NET network.
1. Ensure the field is free of open (unlocked) OS-NET network. See the NOTE below.
2. Assign the 1st OS-NET Sensor to its group (ex. 001). The LED indicator will blink from BLUE to GREEN andcontinue
for aperiod of time.Please note that 001 isjust anexample,you can use any appropriate group number.
3. Assign the 2nd OS-NET Sensor to the same group (ex. 001) within 1 minute. The LED’s of two sensors shall blink
in BLUE and GREEN intermittently. If both sensors eventually display in GREEN,it means thatan OS-NETnetwork
is created successfully.
NOTE: To verify if the field is clear of other OS-NET network, you can select a newly installed OS-NET Sensor and test
with a temporary EZ-GROUP setting. Wait and observe the sensor LED after uploading the group setting data. If the
sensor LED eventually turns to BLUE after the network linking process completed, it means that the field is clear.If the
LED eventually displays in GREEN, itmeansthat thefieldhas an open OS-NET. Execute the UNGROUP process to off-link
the testing sensor fromthe connected network toprevent cross-network groupcontrol which isnormally undesired.
3.4 Adding more OS-NET devices to an existing network
To linkmore OS-NETdevicestoan existingnetwork, youcancontinuetogroup the otherOS-NETdevices viaEZ-GROUP
setting.After thegroupingcommandis dulyreceived, the device will blink its LED while scanningfor anopen OS-NET
and linkup automatically. Continue grouping all other devices and then conduct the DEVICEcontrol settings as required.
3.5 DEVICE setting
DEVICE setting is to configure how an OS-NET Sensor will control the connected lights. The network connected OS-NET
Sensorscan be configured in individualorgroup basis.
Setting an individual sensor
Select the INDIV-SET after enteringtheDEVICE setting page.Selectthe desired control scheme and parameters page by
page and upload the settings to the target sensor. A single lamp sign (5) will display at the upper right corner of all
pages to indicate the settings are forindividual sensor.
Setting allsensors in group basis
Select the GROUP-SET afterentering theDEVICE settingpage. Select the desired control schemeandparameters page
by page and upload the settings to an OS-NET Sensor, all other sensors of thegroup will control the connected lights in
the same scheme and parameters. A double lamp sign (55) will display at the upper right cornerof all pages to
indicate the settings are for grouped sensors.
The following items are availablefor setting the OS-NET Sensors.
lCONTROL
Every OS-NET Sensor can be set to provide different sensing control schemes to the connected light,including typical
on/off switching,bi-levelor continuousdimmingbased on occupancy, vacancy anddaylightsensing control strategies.
Following table highlights all control schemes available forthe OS-NETSensor.

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 10
Scheme Status Day* Night* Description
ON/OFF Vacant OFF OFF Lighting will be inhibitedwhen theambient lightlevelishigherthan the set
threshold, regardless ofoccupancy or vacancy. When theambient light
level is lower thantheset threshold,the controlledlightwillbe turnedon
automatically once the sensor detectsthepresence of occupant, and
turnedoff afterthedelaytimeelapsed.
NOTE:This is a typical occupancy sensing control scheme can be used
withdimmable or non-dimmable lighting, but not HID.
Occupied ON/OFF ON
OSO Vacant Low Dim Low Dim Whenspace is vacant, the lightswill bemaintainedatLowDimlevel.
Wheneverspaceis occupied, lighting outputwill be increased toHigh Dim
level orcontinuously regulated to maintain within thepre-set rangeby
SmartDIM control.
NOTE:This is anoccupancy sensing control scheme can be applied in
areasthatrequire 24-hourlighting.
Do NOT usewithnon-dimmable lighting.
Occupied High Dim/
SmartDIM High Dim/
SmartDIM
OSLA
Vacant OFF Low Dim
Lightingwill be inhibited if theambientlight level is higher than theset
threshold, regardless ofoccupancy or vacancy. When theambient light
level is lower thanthe set threshold, thesensorwill automatically control
the lightat LowDim level. Whensensordetects thepresenceof an
occupant, lighting output will be increased to the High Dim levelor
continuously regulated within the pre-setrangeby SmartDIM control. After
thedelay timeelapsed,lighting outputwill be reduced to Low Dim levelor
shut off if the ambientlightis higher than thesetthreshold.
NOTE:This is anoccupancy sensing control scheme can be applied in
spaces that require automatic lighting whenever ambient light level is
lowerthan the set threshold.
Do NOT usewithnon-dimmable lighting.
Occupied OFF High Dim/
SmartDIM
OSLATO
Vacant OFF OFF
Lightingwill be inhibited if theambientlight level is higher than theset
threshold, regardless ofoccupancy or vacancy. When theambient light
level is lower than theset threshold,andany sensordetectsthe presence
of occupant, lightingoutputwill be increasedtoHigh Dim level or
continuously regulated to maintain overall lightinglevelwithin the pre-set
range by SmartDIMcontrol. After thedelay time elapsed, lighting output
will bereduced toLow Dimlevel for aperiodof TIMEOFFdelaybefore shut
off.
NOTE:This is anoccupancy sensing control scheme can be applied in
spaces that require maintainingLow Dimlightingfora period oftime
before shutting off.
Thisschemerequiresdimmable lightingto enabledimming control. If
lighting is non-dimmable, thecontrolledlights will be shut off afterthe
TIME OFF delay elapsed.
Occupied OFF High Dim/
SmartDIM
& Low Dim
DSVM
Vacant OFF High Dim/
SmartDIM
& Low Dim
Lightingwill be inhibited if theambientlight level is higher than theset
threshold. When theambient light level is lower than the set threshold, the
sensor will turn the light to High Dim level or continuously regulate the
output tomaintain overall lighting levelwithinthepre-set rangeby
SmartDIM control. Lighting output will be reducedtoLow Dim levelfrom a
certain timebeforevirtual midnightto a certain timeafter.
NOTE:This is a daylight sensing control scheme can be applied in spaces
thatrequire automaticallydimmingthelight to alow levelbetween a
certain time before and after virtual midnight. This scheme requires
dimmable lighting toenable dimmingcontrol. If lightingis non-dimmable,
the controlled lighting will remainfull on whenever theambientlight level
is lower than the set threshold.
Occupied OFF High Dim/
SmartDIM
& Low Dim
*Day/Night refersto the condition when ambient light level is higher/lower than the threshold set.

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 11
Scheme Status Day* Night* Description
DSC
Vacant OFF High Dim/
SmartDIM
The sensor will automatically turn on the light to High Dim level or
continuously regulate the output tomaintain overall lighting levelwithin the
pre-set rangeby SmartDIMcontrolwhen the
ambient light level is lower than
thesetthreshold, and automatically turn off the lightwhen the ambient light
level ishigherthanthe set threshold.
NOTE:This is a daylight sensing control scheme can be applied in spaces
that require automatic lighting wheneverthe ambient light islowerthan
the set threshold.
Thisschemerequiresdimmable lightingto enabledimming control. If
lighting is non-dimmable, all lights will remain full onwhenever ambient
lightlevelislowerthanthe threshold.
Occupied OFF High Dim/
SmartDIM
VSC
Vacant OFF OFF
Theoccupantwouldhavetopress theOS-NET Button to turnon the
lighting groupassigned. Thesensorwillcontrol the lights atHighDim level
or continuously regulatetheoutput to maintainoverall lighting levelwithin
the pre-setrange bySmartDIM control. The sensorwill control the
connected lightingasper OSLATO.
NOTE:This is a vacancy sensing control schemecan be applied in spaces
that require usersto manuallyturn onthelight, andhavethe sensor turn
off automatically.
Thisschemerequiresdimmable lightingto enabledimming control. If
lighting is non-dimmable, thecontrolledlighting will beshut off after the
TIME OFF delay elapsed.
Occupied Manual
ON Manual
ON
OSB
Vacant OFF OFF/
Low Dim
Lightingwill be inhibited if theambientlight level is higher than theset
threshold, regardless ofoccupancy or vacancy. When theambient light
level is lower than the setthresholdand the first occupantis detectedby a
groupedsensor,theoutputofsensorconnected lightwill be increased to
High Dim level orcontinuously regulated withinthepre-set rangeby
SmartDIMcontrol during occupancy, andthe unoccupiedareas ofentire
lighting groupwill brighten up to Low Dim levelas background light. The
entire lighting group turns off after the lastperson leaves anddelay time
elapsed.
NOTE: This is an advanced occupancy sensing control scheme canbe
appliedin openofficesto provide background light level before the area of
entire lightinggroupis vacant.
Do NOT use this schemeto control non-dimmable lighting.
Occupied OFF High Dim/
SmartDIM
OFF Vacant OFF OFF Once this scheme is set, all OS-NET controlled lighting will remain off until
another scheme is selected.
NOTE:Thisis amanual control scheme can be used when you need the
lightto beoff fora certain periodof time.
Occupied OFF OFF
*Day/Night refersto the condition when ambient light level is higher/lower than the threshold set.
lAMBIENT LUX
AMBIENT LUX represents various thresholds of ambient lightlevel forthe OS-NETSensor to execute the daylight
harvesting control.Thehigherthe lux valueis, the brighter the ambient light level.DISABLE means disablingthe ambient
lightsensor that willallow theOS-NET Sensorto executethe controlregardlessof theambient light level. CURRENT
meansto set the current ambientlight levelas the day/nightthreshold.
lDELAY
DELAY representsthetime that OS-NETSensorwill turnoffor dim the lighttoalowlevelafterthearea is vacated.
lTIME OFF
TIME OFF represents the time that OS-NET Sensor will keep the light at low dim level after the DELAY timeelapsed. TIME
OFF setting is only available with OSLATOcontrol.

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 12
lHIGH DIM
HIGH DIM settingisto settheoutputlevel(in%)of connected lightingduringoccupancy,or whenambient light levelis
lower than the threshold if daylight sensing control is set. For StepDIM control, 8 levels ranging from 50% to 100% can
be selected. If SmartDIM is set, the sensor will continuously dim the lighting output to maintain the overall area lighting
level withinthe preset range.
lLOW DIM/SmartDIM
LOWDIM setting isto set the outputlevel(in%) ofconnected lightingduringvacancy. The sensorwill regulate the
lighting output at the set level. Setting the LOW DIM at 0 means light full off during vacancy. The LOW DIM setting will
become a SmartDIM setting bar if the sensor is set with SmartDIM control. The LOW DIM level under SmartDIM control
will be 50% of the SmartDIMlevel.
lRAMP UP
RAMP UPrepresentsthespeedof lighting output will be increasedwhensensordetectsthe presence of occupant. 3
options (INSTANT/SOFT/SLOW) are available for selection.
lFADE DOWN
FADE DOWN represents the speed of lighting output will be decreased by theSensor. 3 options (INSTANT/SOFT/SLOW)
are available for selection.
lVM-TB
VM-TB is to set the timeperiod BEFORE Virtual Midnight. This setting isavailable only if DSVM control is set.
lVM-TA
VM-TA is to set the time period AFTER Virtual Midnight. This setting is available only if DSVM control is set.
lSENSITIVITY
SENSITIVITY is for setting the occupancy sensing sensitivity of OS-NET Sensor.For typical low bay applications, LOW
sensitivity can be set to eliminate false-on triggering. For high bay applications, NORMAL or HIGH can be set to enhance
the motion sensingcapability.
For theareascontain with interferencesourcefor occupancy sensor, youmay disablethe occupancy sensingcapability
of local sensor by setting the SENSITIVITY OFF. For the sensor with occupancy sensing capability disabled, it will require
the OCC signalsfromother sensors of the group toexecute the control as programmed.
lBURN-IN
BURN-IN setting is toconduct a test on all connected lightings with full on for a period of time set (in hours) or manually
controlto start andstopthetest bythe remote.
lTEST (10-MIN)
A 10-minute TESTmodecanbe initiated foryoutoverify how the OS-NETSensorwillcontrol thelights witha shorten
delay (10 seconds).The sensor will automatically resume to normal control after 10 minutes. You may also exit from
TESTmode anytimebygivingthe STOP commandto thesensor.
lLED INDICATOR
This setting allows youto enable/disable the LED indicator of OS-NET device which is factory set as enabled.

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 13
lDEFAULT
DEFAULT allows youto resume factory default settings for the REMOTE or DEVICE if necessary. To resume factory default
for an OS-NET Sensor, select DEVICE and press while aiming the remote toward the target sensor. To resume
factory defaultfor theSRP-281remote programmer, just select REMOTEand press .
3.6 LOCK/UNLOCK
To prevent unauthorizedsetting changes of OS-NETdevicesandensurethe independenceof an existing OS-NET
network,you should lock the network aftercompleting the all settings.
LOCK is to close the network to inhibit most setting changeson the installed OS-NET devices.
UNLOCK istoopenthenetwork toallowsettingchangesonthe installed OS-NETdevices.
AUTO LOCK is a self-activated network protection that will automatically lock the network in 12 hours after it is created.
The AUTOLOCKcan be enabledto prevent accidentallinkage by neighboring network in caseof forgettingto lock the
network after setting completed.
NOTE
1. A lockednetworkstill allowscertain remotecontroloperations, includingLight ON,Light OFF,TEST,BURN-IN,
current lux/dim andnetwork data reading.
2. If settingthe wholenetwork requires more than 12hours, and youcannot besure about if any otherOS-NET willbe
established within the field before settings complete, please enable the AUTO LOCK.
To LOCK an OS-NET network
1. Enter the LOCK/UNLOCK page and select LOCK.
2. Pointing the remote to an OS-NET device and press ENTER.
To UNLOCK an OS-NET network
1. Enter the LOCK/UNLOCK page and select UNLOCK.
2. Pointing the remote to an OS-NET device and press ENTER.
To enable AUTO LOCK
1. Enter the LOCK/UNLOCK page and select AUTOLOCK.
2. Press enter and select ENABLED.
3. Pointing the remote to an OS-NET device and press ENTER.

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 14
3.7 SAVE/RECALL
SAVE isto storea specificcontrol scheme with preferred parameters asanEZ-SETprofile in theremoteforfuture use.
RECALListorecallthe DEFAULT settingofa specific OS-NETdeviceor an existingEZ-SETprofilestoredin the remotefor
uploading to the OS-NET Sensor.
NOTE: SAVE/RECALL is a remote operationthat can be done withoutbeingat site.
lSAVE AS
To save the current settings as a new EZ-SET profile
1. Enter the SETTING page and navigateto the setting item.
2. Press or to select the desired parameter.
3. Continue setting on allother items as required.
4. Enter the SAVEAS page and select an EZ-SETprofile (1-4) tobe saved.
5. Press to save the settingsas a new EZ-SETprofile.
lRECALL
This operation allows you to recall the factory DEFAULT settings of an installed OS-NET Sensor or an EZ-SET profile to
setup other OS-NET Sensors with identical parameters or certain parameters changed. The parameters of selected
profile will be displayed on the respective setting pages for your review. Following table highlights the factory preset
parameters of EZ-SET profiles.
Factory preset parameters of EZ-SET profiles
PROFILE
EZ
-
SET 1
EZ
-
SET 2
EZ
-
SET 3
EZ
-
SET 4
CONTROL
ON/OFF
OSO
OSLA
OSLATO
AMBIENT LUX
20
N/A
200
DISABLE
D
DELAY
5
MIN
3 MIN
10
MIN
5 MIN
TIME OFF
N/A
N/A
N/A
10
MIN
HIGH DIM
N/A
70%
70%
SmartDIM
LOW DIM
N/A
30%
30%
-
RAMP UP
N/A
SOFT
INSTANT
SOFT
FADE DOWN
N/A
SOFT
S
LOW
SLOW
SENSITIVITY
HIGH
NORMAL
NORMAL
NORMAL

OS-NET Programming Guide
OS-NETPG-EN-IRT-18R0.docx 15
4. Setting Acknowledgment Indication
The OS-NET devices will acknowledge setting status with different indications by device LEDand connected lights.
OS-NET Sensor
INDICATION ACKNOWLEDGEMENT REMARKS
Sensor LED fast blinking in GREEN
andBLUE. Sensor is scanning and linkingto the
network. The fast blinking (on and off per 0.2
second) only appears during network
linking.
Sensor LED blinks twice every
2-secondin GREENor BLUE. The sensor detects occupant’s
motion. GREENmeansthe sensorisnetwork
linked. BLUE means the sensor is
unlinked.
Sensor LED blinks twice every
2-second for 5 minutes,and then
15-secondafter power applied.
The sensor is set with daylight
sensing control. (DSVM or DSC) GREENmeansthe sensorisnetwork
linked. BLUE means the sensor is
unlinked.
Sensor short beeps twice. Receiving a single setting or control
command.
Sensorbeepsone long and two
short. Theconnected lights on
andoff 2times.
Multiple setting data (ex.grouping
upload) UPLOADsuccessful.
The connected lightson and off 2
times. 1. Factory default setting resumed.
2. SmartDIM setting completed.
OS-NET Button
INDICATION ACKNOWLEDGEMENT REMARKS
Device LED blinking Receiving commands from remote
Device LED lit for 2 seconds Groupingcompleted
Device LED slow blinking The device is unlinked Oneflashper second
Device LED fast blinking The device is scanning and linking to
the network. On and Off for every 0.2 second
Device LED blinks twice per
second Network linkage fail
Other manuals for OS-NET SRP-281
3
Table of contents
Popular Controllers manuals by other brands

Thermal Solutions
Thermal Solutions Boiler Control TSBC instruction manual

Bticino
Bticino F470/1 Instructions for use

Parker
Parker Hauser COMPAX-S Series user guide

Warner Electric
Warner Electric CBC-802 Service & installation instructions

Rockwell Automation
Rockwell Automation Samsung NX70 user manual

Aprilaire
Aprilaire Zoned Comfort owner's manual

Orbinox
Orbinox VG08 Installation, operation & maintenance manual

PERFECTPASS
PERFECTPASS MasterCraft 2007 Troubleshooting

Barco
Barco MXRT-1450 user guide

ABB
ABB REC650 ANSI Technical manual

Promation Engineering
Promation Engineering P1-12VN4 AC Installation & operation manual

Intercall
Intercall L7700 IP16 Documentation