Power voltage
Wireless protocol
Radio frequency
Radio range
Radio Power output
Op. humidity
Op. temperature
Dimensions
230 VAC, 50/60 Hz
Modified Zigbee Light Link (ZLL)
2.4 GHz
Typical 15 m @ indoor
5.72 dBm
Max 95% non-condensation
-10°C ~ 50°C (14°F ~ 122°F)
72H x 72W x 38D mm (w/mounting plate)
The ON-PBD-815 is an optional device of IR-TEC’s OS-NET
wireless mesh network solution exclusively designed to
replace an existing wall switch/dimmer to broadcast manual
on/off/dim control commands to the assigned group lighting,
while also function as a network node.
This sleek, low profile OS-NET device can be mounted into a
standard EURO wall box, operated by line voltage power, and
provide wireless control to the grouped lighting as required.
Each ON-PBD-815 can be assigned to control up to 4 lighting
groups via a 2-way handheld remote programmer, SRP-281.
A screwless snap-on wall plate is supplied to create a
modern, high-end appearance for all spaces. By grouping the
ON-PBD-815 with OS-NET sensors, you can effortlessly
achieve an energy-efficient, code-compliant smart lighting
control through a state-of-the-art wireless sensor mesh
network with manual controls capability for presentation or
special event.
Line Voltage OS-NET Button
INSTALLATION INSTRUCTIONS
OVERVIEW
P/N: 058-81500-002www.irtec.com
This product may be covered by one or more U.S. patents or patent applications.
Please visit www.irtec.com for more information.
ON-PBD-815 series
Lead the wires and strip the insulation with proper
length for connecting.
Connect the wires with the device according to the
wiring diagram shown above.
NOTE: The ON-PBD-815 requires connecting neutral
wire for operation. To replace the existing wall switch
with no neutral wire, you may substitute the switched
line wire for the neutral of lighting in accordance with
electrical codes and regulations.
Carefully set the wires and mount the device into the
wall box with screws provided.
NOTE: Do NOT mount the device upside down.
INSTALLATION
1.
2.
3.
INDOOR USE ONLY
Utilisation a L'interieur Uniquement
AVERTISSEMENT & PRUDENCE
WARNING & CAUTION
Turn power OFF at circuit breaker before installing .
Coupez l'alimentation au disjoncteur avant d'installer.
Unit: mm
30 86
86
72
60
72
54
DIMENSIONS
WIRING DIAGRAM
L
230VAC
N
N L
SPECIFICATIONS
IR-TEC International Ltd. warranties this product to be free
of defects in materials or workmanship for a period of five
years from date of shipment. There are no obligations or
liabilities on the part of IR-TEC International Ltd. for
consequential damages arising out or in connection with
the use or performance of this product or other indirect
damages with respect to loss of property, revenue, profit, or
cost of removal, installation or reinstallation.
WARRANTY
ON
(Ramp UP)
OFF
(Fade down)
www.irtec.com
NOTE: You may skip this section and start grouping the
device if the target network has been created.
To create a new OS-NET network, you can use EZ-GROUP to
group two OS-NET devices with the same group within 1
minute. More details are available from the OS-NET
Programming Guide.
CREATE A NEW OS-NET NETWORK
NOTE: The button will automatically exit configuration mode
after grouping successfully. If grouping fails, the button will
remain in the configuration mode for another 90 seconds. If
no configuration has been conducted within 90 seconds, the
OS-NET Button will automatically exit configuration mode.
To exit configuration mode manually, press and hold the
UPPER and LOWER parts of button for more than 3 seconds.
After complete the installation, each
OS-NET Button should be grouped and
linked with the OS-NET network to enable
group control. An ungrouped OS-NET
Button is functionless.
NOTE: For the first time configuration, please learn the basic
operation of SRP-281 from the OS-NET Programming Guide.
CONFIGURATION OPERATION
Programming Guide
DEVICE ACKNOWLEDGEMENT
The OS-NET Button will acknowledge setting success or
failure with different indications by device LED.
DEVICE LED ACKNOWLEDGEMENT REMARKS
Slow blinking (once
per 2 seconds) in
BLUE.
The button is unlinked. IR communication disabled.
Blinks twice per
second in BLUE.
The button is in
configuration mode but
not grouped.
IR communication enabled.
Device will exit configuration
mode after 90 seconds if no
configuration is performed.
Blinks irregularly
in BLUE or GREEN.
Receiving commands
from the remote.
GREEN means the device is
network linked. BLUE means
the device is unlinked.
Fast blinking only appears
during network linking.
Exit configuration mode
automatically.
Device will exit configuration
mode after 90 seconds if no
configuration is performed.
Fast blinking in
GREEN and
BLUE intermittently.
Scanning for an open
network and linking.
Lit for 2 seconds in
GREEN.
Grouping completed.
Blinks twice per
second in GREEN.
The button is linked and
in configuration mode.
Every installed OS-NET Button should be assigned with its
controlled group(s) to enable group control. For an
ungrouped OS-NET Button, please follow the instructions
below for initial grouping.
1. Enter Configuration Mode
Press and hold the UPPER and LOWER parts of the button
for more than 3 seconds to enter the configuration mode.
The LED indicator of OS-NET Button will blink twice per
second in BLUE (ungrouped).
2. Assign to the group(s)
Conduct EZ-GROUP process and assign to the group(s) via
the OS-NET Remote Programmer (SRP-281) as below
shown. Refer to the EZ-GROUP instructions of Programming
Guide for more details.
INITIAL GROUPING
To change the group assignment of an OS-NET Button,
follow the instructions below;
1. Enter Configuration Mode
Press and hold the UPPER and LOWER parts of the button
for more than 3 seconds to enter the configuration mode.
The LED indicator of OS-NET Button will blink twice per
second in GREEN (grouped).
2. Change to the new group(s)
Input the new group number(s) on the EZ-GROUP setting
page. Assign the OS-NET Button to the new group(s) in the
same was as INITIAL GROUPING.
CHANGE GROUP
Hold the remote
close to the OS-NET
Button as shown to
conduct grouping.
Press and
hold for
more than
3 seconds.
A short press at upper/lower part of the button will transmit
a command to turn on/off the lighting of groups assigned.
Press and hold at upper/lower part of the button will
increase/decrease the output level of grouped lighting
respectively.
1. Turn On the light
A SHORT press (≤0.5 second) at the UPPER part of button
will transmit a command to turn on the grouped lighting.
Light will stay on as long as the grouped sensor(s) detects
the occupancy, and the grouped sensor will resume control
after the area is vacated.
2. Turn Off the light
A SHORT press (≤0.5 second) at the LOWER part of button
will transmit a command to turn off the grouped lighting.
The grouped sensor will resume control after the delay time
elapsed.
3. Ramp up the light
A LONG press (≧0.5 second) at the UPPER part of button
will enter into dimming adjustment mode to increase the
output level of grouped lighting. Intermittent press on the
button during dimming control mode will adjust the output
level step by step. The device will exit from dimming
adjustment mode 2 seconds after the last button operation.
4. Fade down the light
A LONG press (≧0.5 second) at the LOWER part of button
will enter into dimming adjustment mode to decrease the
output level of grouped lighting. Intermittent press on the
button during dimming control mode will adjust the output
level step by step. The device will exit from dimming
adjustment mode 2 seconds after the last button operation.
NOTE: After changing the dim level, allow the LED bar to
turn off before trying to switch on/off.
When the OS-NET Button is in configuration mode, all
operation through the button will be void.

Other IR-Tec Home Automation manuals

IR-Tec OS-NET ON-PBD-705 Series User manual

IR-Tec

IR-Tec OS-NET ON-PBD-705 Series User manual

IR-Tec OS-NET ON-PBD-705 Series User manual

IR-Tec

IR-Tec OS-NET ON-PBD-705 Series User manual

Popular Home Automation manuals by other brands

ABB ABB-free home quick start guide

ABB

ABB ABB-free home quick start guide

Fermax VEO XS DUOX quick start guide

Fermax

Fermax VEO XS DUOX quick start guide

QOLSYS IQPanel 2 Guide

QOLSYS

QOLSYS IQPanel 2 Guide

Scolmore ClickSmart RFWB-20/G Instruction leaflet

Scolmore

Scolmore ClickSmart RFWB-20/G Instruction leaflet

Cleverio 51750 user guide

Cleverio

Cleverio 51750 user guide

HeatTrak WI-FI SMART OUTLET instructions

HeatTrak

HeatTrak WI-FI SMART OUTLET instructions

Becker Centronic VarioControl VC180 Assembly and operating instructions

Becker

Becker Centronic VarioControl VC180 Assembly and operating instructions

X10 RR501 Installation and operating instructions

X10

X10 RR501 Installation and operating instructions

ENANCER ONLY installation manual

ENANCER

ENANCER ONLY installation manual

Directed Pixbee lullabi user manual

Directed

Directed Pixbee lullabi user manual

Bticino HA4572 Instructions for use

Bticino

Bticino HA4572 Instructions for use

iDevices SWITCH user manual

iDevices

iDevices SWITCH user manual

Devolo Magic 1 LAN 1-1 manual

Devolo

Devolo Magic 1 LAN 1-1 manual

Brookstone BKSPB-BF user manual

Brookstone

Brookstone BKSPB-BF user manual

FutureSmart SuperPro series installation guide

FutureSmart

FutureSmart SuperPro series installation guide

TUYA FingerBot user manual

TUYA

TUYA FingerBot user manual

Nortek GoControl 300 Series instructions

Nortek

Nortek GoControl 300 Series instructions

Alpha Smartware RDS 61011-N Series instruction manual

Alpha Smartware

Alpha Smartware RDS 61011-N Series instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.