IR-Tec PPU-300 User manual

PPU-300, PPU-301
Power Pack & Controller
INSTALLATION
OVERVIEW
WIRE DESCRIPTION
The PPU-300/301 power pack is designed to supply
24V DC power for the operation of low voltage
occupancy sensors, and switch the line voltage for the
connected load control via its heavy-duty isolated relay
in response to the signals from connected occupancy
sensors. This power pack can be attached to the
existing junction box with 1/2” knockout or mounted
into fixture cable trays.
The PPU-300/301 is an isolated class 2 switching
mode power supply device for parallel sensor
connection up to maximum 0.15A capacity. Check
power consumption data of all connected sensors for
the maximum number of sensor connection.
With the PPU-300, the load can be turned ON and OFF
automatically when it receives signal input from
connected occupancy sensor, timer, BAS control
and/or manual switch. Various control modes can be
achieved by different wiring connections.
INSTALLATION INSTRUCTIONS
PPU-300
PPU-301
Low voltage wires
PPU-300 : 6 wires
PPU-301 : 3 wires
Line voltage
Load switching
Color Description Function Gauge
White
Black
Red
Red
Neutral
Line
24VDC
DC
Sensor signal
Manual button
Hold ON
Hold OFF
DC power
supply
Sensor
& control
signal
inputs
Load
switching
Line
voltage
Relay
contacts
18 AWG
14 AWG
22 AWG CLASS 2
Red
Black
Blue
*Grey
*Orange
*Brown
*Only with PPU-300
Low voltage wire
P/N: 058-30024-007 Printed in Taiwanwww.irtec.com
This product may be covered by one or more U.S. patents or patent applications.
Please visit www.irtec.com for more information.
COUPER LE COURANT AU DISJONCTEUR AVANT D'INSTALLER
BLOCS D’ALIMENTATION.
Risque de choc électrique – Plus d'un interrupteur peut être
nécessaire pour mettre hors tension le matériel avant l'entretien.
Utiliser homologation UL fils pour toutes les connections de
câblage. Basse tension connection de câblage doit utiliser au
moins 22 fils de AWG. Commutation de charges connections de
câblage doit utiliser au moins 14 AWG. Tension de la ligne de
courante alternative connections de câblage doit utiliser au moins
18 fils de AWG. Brancher tous les circuits de classe 2 à l'aide de
types CL3, CL3P, CL3R, ou conducteurs équivalent. Pour les
plafonds de retour de plénum, utiliser UL câbles ignifuges
approuvés énuméré.
Toujours vérifier les codes de constructions nationaux, étatiques et
locales pour le respect nécessaire et conformité. Après le câblage
initial est terminé, assurez-vous de vérifier que tous les fils basse et
haute tension sont connectés correctement avant d'appliquer la
puissance. Un câblage incorrect pourrait causer des dommages
permanents à la batterie d'alimentation, système d'éclairage, aux
détecteurs de présence ou autres dispositifs de commande.
AVERTISSEMENT & PRUDENCE
TURN POWER OFF AT CIRCUIT BREAKER BEFORE INSTALLING
POWER PACKS.
Risk of Electric Shock – More than one disconnect switch may be
required to de-energize the equipment before servicing.
Use UL listed wires for all wiring connections. Low voltage wiring
connection should use at least 22 AWG wire. Load switching wiring
connection should use at least 14 AWG. AC power line voltage
wiring connection should use at least 18 AWG wire. Wire all Class 2
circuits using types CL3, CL3P, CL3R, or equivalent conductors.
For plenum return ceilings, use UL listed plenum-approved cables.
Always check national, state and local building codes for
necessary compliance. After initial wiring is complete, ensure to
verify all the low and high voltage wires are correctly connected
before applying the power. Incorrect wiring could possibly cause
permanent damage to the power pack, lighting system, occupancy
sensors or other control devices.
WARNING & CAUTION
ONLY QUALIFIED
ELECTRICIANS
SHOULD INSTALL
THIS DEVICE.
Indoor dry location use only
Utilisation a L'interieur Uniquement

Line Black
White
Red
Red
Black
Green
White
Red
Black
Blue
Red
Neut
Relay
Relay
DC24V
DC
DC+
DC
COM
NO
Occupancy
IR-TEC
Sensor
Control
Manual
Hold ON
Hold OFF
Load
Line
120/277V
Neutral
Low Voltage
Line Black
White
Red
Red
Black
Green
White
Red
Black
Blue
Red
Neut
Relay
Relay
DC24V
DC+
COM
NO
Occupancy
IR-TEC
Sensor
Control
Manual
Hold ON
Hold OFF
Line
120/277V
Neutral
N
Ground
L
Low Voltage
DC
DC
G
Black
White
Red
Red
Black
Blue
Grey
Orange
Brown
Red
Black
Blue
Grey
Orange
Brown
Red
Neut
Line
Relay
Relay
DC24V
DC+
COM
NO
Control
Manual
Hold ON
Hold OFF
Line
Neut
Relay
Relay
DC24V
Control
Manual
Hold ON
Hold OFF
Load
Line
120/277V
Neutral
Black
White
Red
Red
Load
Line
120/277V
Neutral
IR-TEC Push Button(A)
IR-TEC Push Button(B)
Occupancy
IR-TEC
Sensor
Low Voltage
Red
Black
Green
White
DC
DC
DC
Line Black
White
Red
Red
Neut
Relay
Relay
DC24V
DC+
DC
COM
NO
Control
Manual
Hold ON
Hold OFF
Load
IR-TEC Push Button
Line
120/277V
Neutral
Occupancy
IR-TEC
Sensor
Low Voltage
DC
Orange
Grey
Brown
Red
Black
Blue
Red
Black
Green
White
Line Black
White
Red
Black
Orange
Red
Neut
Relay
Relay
DC24V
COM
NO
PLC/Timer/Control
Control
Manual
Hold ON
Hold OFF
Load
It overrides sensors control on input.
Line
120/277V
Neutral
DC
Line Black
White
Red
Black
Brown
Red
Neut
Relay
Relay
DC24V
COM
NO
PLC/Timer/BAS
Control
Manual
Hold ON
Hold OFF
Load
It overrides sensors control
and hold on input.
Line
120/277V
Neutral
DC
LED INDICATION
WIRING DIAGRAMS 4. Hold OFF
5. Bi-level control with Manual ON
1. Sensor control ON/OFF
2. Manual ON, Sensor control OFF
The RED LED indicates DC power supply status, ON
means power normal, OFF means no DC power.
The BLUE LED indicates relay contact status, ON means
closed, OFF means open.
3. Hold ON
4ZS9
E358259
Power Pack Unit
UL 2043 Plenum Rated
ENCLOSED ENERGY MANAGEMENT EQUIPMENT
(PPU-300 only)
(PPU-300/301)
(PPU-300 only)
(PPU-300 only)
6. Sensor control ON/OFF, Receptacle Control
(PPU-300/301)
(PPU-300 only)
SPECIFICATIONS
Power supply
DC output
Control input
Load control
Op. humidity
Op. temperature
Dimensions
120/277VAC, 50/60Hz
24V, 150mA max.
Control, Active Low
*Hold ON, Active Low
*Hold OFF, Active Low
*Manual, Active Low
Ballast-20A, 120/277VAC
Resistive-20A, 120/277VAC
Motor-1 Hp, 120/240VAC
95% RH max.
-20°C~50°C (-4°F~122°F)
75x45x45mm (3˝x1.8˝x1.8˝)
*Only with PPU-300
This manual suits for next models
1