IronStrike Cascade User manual

INSTALLATION AND OPERATION MANUAL
Save These Instructions
For Future Reference
Pellet Stove
Model Cascade®
Free-Standing
Pellet Stove
P/N 900107-00, Rev. NC, 02/2014
A French manual is available upon request. Order P/N 900108-00.
Ce manuel d’installation est disponible en francais, simplement en faire la demande. Numéro de la pièce
900108-00.
This appliance must be properly installed and operated in order to prevent the possibil-
ity of a house fire. Please read this entire manual before installation and use of this
pellet fuel-burning room heater. Failure to follow these instructions could result
in property damage, bodily injury or even death. Contact your local building
or fire officials to obtain a permit and information on any installation
requirements and inspection requirements in your area.
WARNING
•
Hot! Do not touch! The glass and surfaces of this appliance will be
hot during operation and will retain heat for a while after shutting off
the appliance. Severe burns may result.
•
Carefully supervise children in the same room as appliance.
•
IHP pellet-burning appliances are designed for use as a supplemental
heater. They are not intended for continuous use as a primary heat
source.
Report No. 050-S-23-2
US
Portland
P900107-00

2
1. DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE CON-
NECTED TO ANOTHER APPLIANCE.
2. Do not connect this appliance to air ducts or any air distribu-
tion system.
3. DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING
SYSTEM OF THIS APPLIANCE.
4. Do not use class B venting intended for gas appliances as a
chimney or connector pipe on a pellet fired appliance.
5. The minimum clearances must be maintained for all com-
bustible surfaces and materials including; furniture, carpet,
drapes,clothing,wood,papers,etc.Donotstorecombustibles
within this clearance space (see Clearances on Page 5).
6. INSTALLATIONDISCLAIMER-Thisstove’sexhaustsystemworks
with negative combustion chamber pressure and a slightly
positive chimney pressure. Therefore, it is imperative that the
exhaust system be gas tight and installed correctly. Since IHP
has no control over the installation of your stove, IHP grants no
warranty,impliedorstatedfortheinstallationormaintenanceof
yourstove,andassumesnoresponsibilityforanyconsequential
damage(s).
7. Burning any kind of fuel consumes oxygen. If outside air is
not ducted to the appliance, ensure that there is an adequate
source of fresh air available to the room where the appliance
is installed.
8. The appliance will not operate using natural draft, nor without
a power source for the blower and fuel feeding systems.
9. Never use gasoline, gasoline-type lantern fuel, kerosene,
charcoal lighter fluid, or similar liquids to start or “freshen up”
a fire in this heater. Keep all such liquids well away from the
heater while it is in use.
10.The authority having jurisdiction such as municipal build-
ing department, fire department, fire prevention bureau, etc
shouldbeconsulted beforeinstallationtodeterminetheneed
to obtain a permit.
11.APPROVED FUEL: This appliance is designed specifically
for use only with pelletized wood fuels only. This appliance
is designed and approved for the burning of wood residue
pellets with up to 2% ash content. This appliance is NOT
approved to burn cardboard, nut hulls, cherry pits, corn, etc.
regardless if it is in pellet form. Failure to comply with this
restriction will void all warranties and the safety listing of
the stove. Consult with your IHP dealer for more information
on approved pellet fuels.
12.CONTINUOUS OPERATION: When operated correctly, this
appliance cannot be overfired. Continuous operation at a
maximum burn can, however, shorten the life of the electri-
cal components (blowers, motors, and electronic controls),
and is not recommended. Typical approved operation would
includerunningatthelowtomidrangesettingwithoccasional
runningon themaximum settingduring thecoldest periodsof
the winter. The blower speed control should be turned to high
when operating the stove on the high heat setting. DO NOT
OVER-FIRE THIS STOVE. Follow all instructions regarding
the proper use of this stove.
13.CAUTION:NEVERPUTFINGERSNEARAUGER. Thisappliance
isequippedwitha hopperlidswitch,whichisdesignedtostop
the auger when the hopper lid is opened. NEVER DISCONNECT
OR BYPASS THIS SWITCH FOR ANY REASON. Pellet fuel is fed to
the UltraGrate™ by a screw auger. This auger is driven by a
high torque motor. The auger is capable of causing serious
harm to fingers. Keep pellets in the hopper at all times and
keep fingers away from auger. The auger can start and stop
automatically at any time while the stove is running.
14. CAUTION: HOT WHILE IN OPERATION. An appliance hot
enoughtowarmyourhomecanseverelyburnanyonetouching
it. Keep children, pets, clothing and furniture away. Contact
maycauseskinburns.Donotlet childrentouchthe appliance.
Train them to stay a safe distance from the appliance.
15.Fly-ash BUILD-UP: For all wood pellet fuel-burning heaters,
the combustion gases will contain small particles of fly-ash.
This will vary due to the ash content of the fuel being burned.
Over time, the fly-ash will collect in the exhaust venting
system and restrict the flow of the flue gases. The exhaust
venting system should be inspected regularly and cleaned
as necessary.
16.SOOT FORMATION: Incomplete combustion, such as occurs
during startup, shutdown, or incorrect operation of the room
heater will lead to some soot formation which will collect in
the exhaust venting system. A precautionary inspection on
a regular basis is advisable to determine the necessity of
cleaning. The exhaust venting system should be inspected
regularly and cleaned as necessary.
17.DISPOSALOFASHES:Ashesshouldbeplacedinasteelcontainer
with a tight fitting lid and moved outdoors immediately. The
closed container of ashes should be placed on a noncombus-
tible floor or on the ground, well away from all combustible
materials, pending final disposal. If the ashes are disposed
of by burial in soil or otherwise locally dispersed, they should
be retained in the closed container until all cinders have been
thoroughly cooled.
18.The instructions must be strictly adhered to. Do not use
makeshift methods or compromise in the installation.
19.Do not abuse the door glass by striking, slamming or similar
trauma. Do not operate the stove with the glass removed,
cracked or broken.
20.SAVE THESE INSTRUCTIONS.
21.See the listing label on the appliance.
IMPORTANT SAFETY AND WARNIING
INFORMATION
READ THIS MANUAL IN ITS ENTIRETY AND UNDER-
STAND THESE RULES TO FOLLOW FOR SAFETY.
WARNING
Do not attempt to alter or modify the construction of
the appliance or its components. Any modification
or alteration may void the warranty, certification
and listings of this unit.
WARNING
Improper installation, adjustment, alteration, ser-
vice or maintenance can cause injury or property
damage. Refer to this manual. For assistance or
additional information consult a qualified installer,
service agency or the gas supplier.

3
PACKAGING LIST
The assembled pellet stove model Cascade®, is packaged with an
accessory package which contains the following:
One - Installation and operation instructions manual
One - Warranty
One - Power cord
One - Grate scraper
One - 5/32" Allen wrench
TESTING / LISTING
USING THIS MANUAL
Please read and carefully follow all of the instructions found in this
manual. Please pay special attention to the safety instructions provided
in this manual.
PRODUCT IS SUBJECT TO CHANGE WITHOUT NOTICE
PLANNING YOUR INSTALLATION
WARNING
Check all local building and safety codes before
installation.Theinstallationinstructionsandappro-
priate code requirements must be followed exactly
andwithoutcompromise.Alterationstothestoveare
not allowed. Do not connect the stove to a chimney
system serving another stove, appliance, or any air
distribution duct. Failureto followthese instructions
will void the manufacturers warranty.
The installation of this appliance must conform to local codes and appli-
cable state and federal requirements. Familiarity with these requirements
before installation is essential. Important considerations to discuss with
local building officials include:
1. Applicable codes (i.e. Uniform Mechanical Code, State or Regional
Codes).
Electrical codes:
In USA, NEC, ANSI/NFPA 70 – Latest Edition
In Canada, CSA C22.1 – Latest Edition
Listing: The listing laboratory is OMNI-Test Laboratories, Inc., Portland,
Oregon. The report number is 050-S-23-2 for model Cascade pellet
stove.
Testing: In accordance with the specifications and procedures
• ListedandtestedtoASTME1509andULCC1482/ULCS627for
installations as a freestanding room heater
• The safety/listing label is located on an inside hopper surface of the
pellet stove. Please read this safety label carefully. It contains important
information about installation and operation of this appliance.
• This appliance is tested and listed for residential and commercial
installation according to current national and local building codes as:
• AFree-StandingRoomHeater
• AManufacturedHomeHeater
EPA (Environmental Protection Agency)
Status: EPA Exempt - Pellet appliances that are designed with the com-
bustion air supply exceeding the 35 to 1 (by weight) ratio are exempt
from EPA regulations and are “non-affected facilities.”
CONGRATULATIONS!
When you purchased your new pellet stove, you joined the ranks of
thousands of individuals whose answer to their home heating needs
reflects their concern for aesthetics, efficiency and our environment.
We extend our continued support to help you achieve the maximum
benefit and enjoyment available from your new pellet stove.
Thank you for selecting a IHP stove as the answer to your supplemental
home heating needs.
TABLE OF CONTENTS
Important Warnings ...........................Page 2
Packaging List ................................Page 3
Testing / Listing, EPA . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3
Using this Manual ............................. Page 3
Planning Your Installation .......................Page 3
Selecting a Location............................ Page 4
Floor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5
Installation Tips ...............................Page 6
ManufacturedHomeInstallation . . . . . . . . . . . . . . . . . . Page 7
Installation ..................................Page 7
Damper Adjustment ............................Page 8
Venting Requirements ..........................Page 9
Care and Operation ............................ Page 17
Fuel ........................................Page 19
Routine Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 20
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 25
Component Definitions .........................Page 26
Wiring Diagram ...............................Page 27
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 28
Replacement Parts List and Diagrams . . . . . . . . . . . . . . Page 29
Optional Accessories ...........................Page 32
Safety / Listing Label ...........................Page 33
Warranty ....................................Page 35
Product Reference Information ................... Page 36
This installation and operation manual will help you obtain a safe, effi-
cient, dependable installation for your appliance and vent system.
PLEASE READ AND UNDERSTAND THESE INSTRUCTIONS
BEFORE BEGINNING YOUR INSTALLATION
Questions To Ask Local Building Official
A correct installation is critical and imperative for reducing fire hazards and
perilous conditions that can arise when wood pellet burning appliances
are improperly installed. The installer must follow all of the manufactur-
ers’ instructions.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
4
CAUTION
The body of these appliances are very heavy. The
use of a heavy duty escalara (stair step hand truck)
is recommended for lifting the appliance body.
WARNING
Electrical grounding instructions: This appliance is
equipped with a three-prong (grounding) plug for
your protection against shock hazard and should
be plugged directly into a properly grounded three-
prong receptacle. Do not cut or remove the ground-
ing prong from this plug. Do not route power cord
under or in front of appliance.
Surge Protectors
A surge protector is recommended to ensure the stove’s electrical com-
ponents are not damaged due to a surge in the electrical supply. Only
highqualityprotectorslistedtoUL1449shouldbeused-lowquality
protectors do not provide the protection needed.
Smoke Detectors
Since there are always several potential sources of fire in any home, we
recommend installing smoke detectors. If possible, install the smoke
detector in a hallway adjacent to the room (to reduce the possibility of
occasional false activation from the heat produced by these appliances).
If your local code requires a smoke detector be installed within the same
room, you must follow the requirements of your local code. Check with
your local building department for requirements in your area.
Installation / Maintenance Standards
National Fire Protection Association – The primary NFPA standard that
refers to installation and maintenance of pellet appliances and venting
is NFPA 211 – Latest Edition: Chimneys, Fireplaces, Vents, and Solid
Fuel appliances.
This appliance requires noncombustible floor protection (the hearth pad
or alternate floor protection material does not require a thermal rating).
A noncombustible floor protector must fully cover the area beneath the
appliance as illustrated in Figure 1.
If the floor protection is to be stone, tile, brick, etc., it must be mortared
or grouted to form a continuous noncombustible surface. In Canada, if a
chimney connector / venting extends horizontally over thefloor, protection
must also cover the floor under the connector / venting and at least 2”
(51 mm) to either side (recommended but not required in the US). See
ClearancesandHearthProtectionshowninFigure 1.
The design of your home and where you place your stove will determine
its value as a source of heat. This type of appliance depends primarily on
air circulation (convection) to disperse its heat, and therefore, a central
location is often best. There are other practical considerations, which
must be considered before a final selection of locations is made. Some
of which includes:
SELECTING A LOCATION
FLOOR PROTECTION
NEGATIVE PRESSURE WARNING
This appliance is not designed to be operated in a negative pressure envi-
ronment. In very airtight homes with large kitchen exhaust fans, furnace
cold air returns, fresh air exchange systems and any other air system in
close proximity to the heating appliance may create a negative pressure
in the same room as the heating appliance. This can create dangerous
condition, drawing combustion by-products into the home. Be sure your
home has adequate makeup air to eliminate negative pressures caused
by the above-mentioned sources. Outside air connected to the appliance
probably will not resolve such a problem as the stove is not the source
of negative pressure. IHP accepts no liability for damages resulting from
negative pressures described here.
VentilationRequirements- Provide adequateair for combustion. The fresh
air requirements of this appliance must be met within the space where it
will be installed. Ventilation is essential when using a solid-fuel-burning
heater. In well insulated and weather tight homes, it may inhibit the rate
the exhaust flows through the venting system (caused by a shortage of
air in the home). The lack of air is caused by many common household
appliances which exhaust air from the home (such as a furnace, heat
pump, air conditioner, clothes dryer, exhaust fans, fireplaces, and other
fuel burning appliances). Also, the combustion process of this heater
uses oxygen from inside the dwelling. If the available fresh air delivery
in the dwelling is insufficient to support the demands of these appli-
ances, problems can result (i.e. excessive negative pressure will result
in performance problems. To correct this problem it may help to open
a window (preferably on the windward side of the house) or install an
outside combustion air duct to the appliance.
2. Local amendments
3. Is a permit required - cost. You may wish to contact your insurance
company to ask if they require this.
4.Ifoutsidecombustionairisrequired
5. Rooms where the installation is not allowed
Power Supply Requirements
These requirements must be met unless otherwise specified by state or
local authorities.
• Power Cord - The power cord must be plugged into a standard, 120
Volt,60Hzgroundedelectricaloutletwithpropergroundandpolarity.
The power cord must be routed to avoid contact with any of the hot
or sharp exterior surface areas of the stove.
• Power Supply - The approximate power requirement is 250 watts.
• Manufactured Home Installations - When installed into a manufac-
tured home, the appliance must be electrically grounded to the steel
chassis of the manufactured home (see Page 7, Manufactured Home
Requirements).
• ExistingChimneys
• PelletFuelStorage
• AestheticConsiderations
• RoofDesign(rafterlocationsandroofpitch)
• RoomTrafc
• ProximitytoCombustibles
• ElectricalWiring

5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
*NOTE: Refer to vent manufacturer's installation instructionsfor minimum
vent clearances.
Figure 1 - Floor Protection Requirements
*NOTE: When installed at clearances less than 6”, floor protection is only
required to extend to the wall. Refer to Page 4 for chimney/venting floor
protection requirements and recommendations.
Standard residential, commercial or manufactured home installation.These
appliances require the following minimum clearances to combustibles.
Figure 2
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
NE PAS ENLEVER CETTE ÉTIQUETTE DÉGAGEMENT MINIMUM POUR LES
MATÉRIAUX COMBUSTIBLES
Freestanding Stove Installation / Installation Du Poêle Autonome
Manufactured (Mobile) Home, Residential or Commercial Installation /
Installation Résidentielle Ou Dans Une Maison réfabriquée (Mobile)
A - Sidewall to unit 4” / 102 mm
B - Backwall to unit 1” / 25 mm
C - Sidewall to unit Corner 1” / 25 mm
D - Max. Depth of Alcove
u
24” / 610 mm
E - Flue to Wall
v
3" / 76mm
F - Ceiling Height above stove top 21-1/2” / 522 mm
u
· Alcove Measurements (see Figure 4): Height, Minimum – 49” (1245
mm), Width Minimum – 32” (813 mm), Depth Maximum – 24” (610 mm)
vSee vent manufacturer to verify clearances
Table 1
Rear Wall or Alcove - Clearance to Combustibles
Corner - Clearance to Combustibles
Combustible
Combustible
Combustible
A
E*
A
B
D
Combustible
Combustible
C
E*
C
Figure 3
Rear Wall or Alcove - Clearance to Combustibles
F
Figure 4
24”
Max.
49”
Min.
32”
Min.
AA
Up to * 6”(153mm)
minimum
6”
(153mm)
minimum
6”
(153mm)
minimum
6” (153mm)
minimum
Floor Protector
CLEARANCES
IMPORTANT
•Minimum clearances specified may not allow
for ease of operation and maintenance (please
take this in to account when planning the instal-
lation). If installed to the minimum clearances,
removal of the appliance may be necessary for
servicing.
•Recommended clearancezone fromthe frontof the
appliance to combustibles is 4 feet minimum.
•Clearances to combustibles for the appliance
can only be reduced by means approved by the
regulatory authority.

6
INSTALLATION TIPS
GOOD INSTALLATION *
Horizontal Installation
(Direct Vent - Outside Wall)
No natural draft. Wind
pressures may affect operation
PLEASE REVIEW THIS ENTIRE
INSTALLATION AND OPERA-
TION MANUAL FOR ADDITIONAL
INSTRUCTIONS.
BETTER INSTALLATION
Vertical and Horizontal Installation
(Up and Out)
Some natural draft aids venting. Wind
pressures may still affect operation
BEST INSTALLATION
Vertical Installation
(Straight Up)
Natural draft improves operation and
negative effects from wind
VENTING TYPE
a: PL-Vent Pipe / Pellet Vent (w/stainless inner liner)
b: Stainless Steel flex liner may be used inside existing flue
or chimney (woodstove replacement applications)
CAUTION: Do not use Type B-Vent Pipe
REQUIRES 3”
DIAMETER STANDARD
PL-VENT / PELLET PIPE
With listed termination kit. If
installation requires in excess of
11’ of pipe, it is recommended a
4”diameterpipebeused.
MANUFACTURED
HOME
Requires outside air for com-
bustion. Use a galvanized or
stainless steel pipe for duct.
Minimumductsize1-5/8”dia.
CLEARANCES TO
COMBUSTIBLES
Ensure all clearances are main-
tained in accordance to instruc-
tions contained on product
safety label and in compliance
with pipe/venting requirements.
POWER SUPPLY
Must have proper polarity and
be grounded.
NOTE: Use of an extension
cord may adversely effect the
performance of your unit.
Seal All
Venting Joints:
Use RTV
(high temp silicone)
INSTALLATION TIPS
Select Your Installation Type
* In horizontal vent installations It is recommended that when an appliance is vented directly through a wall, a minimum of 6 feet (1.83 M) of vertical pipe is
installed to create some natural draft. This will reduce the possibility of smoke or odor entering the dwelling during appliance shutdown or loss of power.

7
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
Removing Appliance From Pallet
1. After removing the packaging from the stove, lift the hopper lid, and
remove any pre-packaged items that were shipped in the hopper. Also
open the door assembly and remove any pre-packaged items.
2. Using a 1/2" socket or open end wrench, remove the four nuts from
inside the stove legs that secure the stove to the pallet braces.
Figure 6
Back
Front
Door Assembly
In addition to the standard installation instructions, the following instruc-
tions may be required by local, state or federal building codes:
• InstallationshouldbeinaccordancewiththeManufacturedHomeand
SafetyStandard(HUD),CFR3280,Part24.
• Thestovemustbepermanentlyboltedtotheoorusingfour1/4"Lag
screws. The lag screws must be an adequate length to extend through
the hearth pad and into the floor as shown in Figure 5. Install the lag
screws as shown in Figure 5. A minimum of two lag screws must be
used.
• Connecting the Cascade™ stove to outside combustion air is required
in manufactured home installations and when requiredby local building
codes. An outside air inlet must be provided for combustion and be
unrestricted while unit is in use. Use a galvanized or stainless steel
pipefortheduct(theoutsideairinletonthestoveis1-5/8”diameter).
The air intake on the exterior of the home should always be located
aminimumof18"belowtheuetermination.TheInletshallremain
free of obstruction while unit is in operation and constructed in a
manner so as to prevent material from dropping into the inlet or into
the area beneath the dwelling. The inlet shall also have a screen with
openingsnotlargerthan1/4"topreventrodentsfromentering.
• Stovemustbepermanentlyelectricallygroundedtothesteelchassis
ofthemanufacturedhomeusinga8GAcopperwireandaserrated
or star washer (to penetrate paint or protective coating to ensure
grounding). The location selected for ground attachment to the stove
must be dedicated for this purpose. Grounding must comply with
NFPA-70-latest edition standards, CSA C22.1-latest edition in Canada,
as well as any local codes.
• SeePages 9 through 16 for additional information on venting require-
ments.
• WARNING: DO NOT INSTALL THIS STOVE IN A SLEEPING ROOM IN
A MANUFACTURED HOME.
• CAUTION: THE STRUCTURAL INTEGRITY OF THE MANUFACTURED
HOME FLOOR, WALLS, CEILING/ROOF MUST BE MAINTAINED.
Bolt
Figure 5 Chassis Grounded to Steel
Chassis
Floor
Protector
Floor
MANUFACTURED HOME INSTALLATION
INSTALLATION
Remove 4 nuts inside stove legs.
Manufactured Home Exhaust Vent Pipe Installation Guidelines
This stove is approved for venting with Type L and Type PL pellet vent
pipelistedtoUL641andULCS609.Thepipeshouldextendatleast3
feet above the part of the roof through which it passes. The top of the
pipe should be at least 2 feet above the highest required elevation of any
part of the manufactured home within 10 feet of the pipe (see Page 12,
Manufactured Home Chimney Height Requirements).
If the exhaust vent exits the manufactured home at a location other than
the roof, and exits at a point 7 feet or less above the ground level on which
the manufactured home is position a guard or method of enclosing the
pipe shall be provided at the point of exit for a height of up to 7 feet. The
openings,ifany,inthisguardshallnotallowa3/4”rodtopassthrough.
A 1/2” rod could pass through but should not be able to touch the pipe
wheninsertedthroughtheopeningadistanceof4inches.
Bolt locations
Pallet

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
8
Installation Check List
It is strongly recommended that you have an authorized IHP dealer install
your stove. If you install your stove yourself, you should review your
installation plan with an authorized IHP dealer.
Check list:
Check off each item as you proceed with the installation process.
qRead the ENTIRE stove installation section first.
qDetermine the appropriate measurements and locations for your
installation.
qFollow the general installation directions under Installation.
qBe sure to pre-fit all items before you install, fasten, or set up the
stove permanently.
qMeasure for exhaust (also outside air tube when applicable) and mark
the location. Place the unit in place to make sure it's correct before
cutting holes in your wall.
Prior to lighting your appliance:
qReview the Important Warnings section (see Page 2).
qReview Fuel Specifications (see Page 19).
qReview and follow instructions in the Care and Operation Section (see
Pages 17 through 19).
qPlug power cord connector into corresponding connector on the back
of appliance.
After you have begun operation of your appliance:
qReview the routine cleaning / maintenance information.
qEnjoy the warmth from your new IHP pellet appliance!
Damper Location and Adjustment
The damper is a plate that helps control the amount of airflow supplied
for combustion. With the damper pulled out all the way, the airflow is
at its maximum. As the damper is pushed in, the amount of air that is
allowed to flow is reduced.
It is very important to preset your damper prior to burning your pellet
stove. The damper rod is located on the right side of the stove as shown in
Figure 7. The damper should be pulled all the way out to the full open
position during initial operation. It may need to be manually adjusted
inward depending on the type of pellet fuel being burned. Adjustin1/4”
increments until optimum combustion air flow is achieved. The damper
control adjusts the amount of combustion air to the UltraGrate™. When
the damper has been correctly adjusted, you will observe a brisk, yellow-
to-whitish flame. Fuel should not “pile-up” in the grate. The proper air
settings will vary from stove to stove due to installation, altitude, and
the fuel being burned.
Front
Damper Rod
Top View of Stove
Push in for less air
Pull out for more air
Figure 7 - Damper Control
It will be necessary to monitor the appearance of the flame during the first
4-8bagsofpellets.Iftheameissmokyredororangewithevidenceof
soot at the top of the flame, the damper will need to be adjusted to deliver
more combustion air (see Figure 7). If the flame is “short” at the higher
burn rates and appears to burn the pellets out of the UltraGrate™ faster
than they can be resupplied, or there are significant variations of flame
height within a single burn setting, the damper may need to be adjusted
to deliver less combustion air.
After the damper is adjusted, re-evaluate the appearance of the flame. It
may be necessary to continue adjusting the damper in increments until
proper combustion is achieved (the flame should become a brighter
yellow and begin to “dance”).
Once the damper has been properly set, and if the routine maintenance
is performed as needed, the damper should not require re-adjustment
unless you are changing from a premium grade pellet to a standard or
high ash pellet, in which case the damper may need to be moved outward
to help prevent the accumulation of ash or clinkers in the UltraGrate™.
Damper Adjustment Guideline
Lack of Combustion Air: By opening the damper, this will increase com-
bustion air delivery. Symptoms of insufficient combustion air include;
unburned fuel, lazy smoky or red / orange flame, excessive ash or soot,
excessive buildup on glass, fuel may “pile-up.“
Contributing factors:
• HighAltitude–Lackofoxygen
• Restrictive Venting (elbows, horizontal runs, cold external
chimneys, etc.).
• Dirty/PoorQualityFuel.
• LackofMaintenance
NOTE: Excessive amounts of Fly-ash built-up in the grate, clinkers
in the grate or leakage of air (if the grate is not properly seated) will
starve the fire for air. See Routine Maintenance, on Pages 20 through
24 for information on cleaning requirements.
Excessive Combustion Air: Adjusting the damper to a more closed posi-
tion will reduce the combustion air delivery. Symptoms of excessive air
include; fuel burns too quickly (results in smoking or smoldering pellets),
white to yellow flame, etc. If the damper is open too far, the burning pellets
will lift off the grate and fly up into the air much like popping corn does.
Another flame characteristic of a damper that is open too far is a flame
that has significant variation in height on any single burn setting.
NOTE: Excessive combustion air reduces efficiency.
Contributing factor:
•· Ventingsystemprovidingexcessivedraft.
• Dry,hotburningfuel
CorrectCombustion Air /Proper Burn Characteristics:When the damper
is correctly set, the burning pellets should move (wiggle) around slightly
and the flame should be bright yellow.
Outside Air Installations
Connecting the Cascade™ pellet stove to outside combustion air is
optional, except in manufactured (mobile) home installations and when
requiredbylocalbuildingcodes.Thestove’sairintakewillaccept1-5/8”
ID pipe to accommodate outside air installations. The air intake on the
exteriorofthehomeshouldalwaysbelocatedaminimumof18"below
the flue termination and must remain free of obstruction. The inlet must
alsohaveascreenwithopeningsnotlargerthan1/4"topreventrodents
from entering.
Initial Setting - Pull damper
out to the full open position,
then adjust in 1/4” increments
until optimum combustion air
flow is achieved.

9
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
VENTING REQUIREMENTS
It is recommended that only an IHP dealer install your pellet stove. The
specified installation requirements must be followed to ensure conformity
with both the safety listing of the appliance and local building codes. All
clearances, installation instructions and precautions specified by the vent
manufacturer must be followed.
Selecting a Location
Review the appliance clearance requirements before installing the
venting system (see Page 5). Position the appliance far enough away
from walls to allow adequate room for servicing. Choose the appliance
location with the least amount of interference with the house framing,
plumbing, wiring, etc.
Preferred Vent Configuration
For the best performance, we recommend a vent run design which runs
vertically and terminates above the roof line. This design will allow natural
draft to improve the flow of flue gases and will aid in combustion and
stove performance.
Type of Pipe
This stove is approved for venting with Type L and Type PL pellet vent
pipe(sometimesreferredtoas“L-Ventpelletvent”,listedtoUL641or
ULCS609).Connect the pellet vent pipe or the “tee” to the flue collar
using a minimum of three screws and seal as specified in “Pipe/Liner
Joint Requirements” on this page. Do not use class B gas chimney or
single wall chimney as a substitute.
Size of Pipe
These pellet appliances are approved for use with the following vent sizes:
3”(75mm)standard,or4”(100mm),seePage 13 - for determining
correctsizevent.When4”pipeisused:forhorizontalventinstallations
usea3”(75mm)to4”(100mm)adaptor-availablefromventmanu-
facturer. Forverticalinstallations usea3”(75 mm)to4”(100mm)
“tee” - available from vent manufacturer.
Offsets
In every installation, a single or double clean-out “tee” is recommended
for every ninety-degree offset (this tee will help collect ash residue and
will allow for routine cleaning without the need to disconnect sections
of pipe).
Pipe Clearances/Requirements
See pipe manufacturers instructions forinstallation of venting components
and clearances. Follow pipe manufacturers installation precautions for
passing pipe through a combustible wall or ceiling (i.e. use an approved
thimble).
NOTES:
•Offsets and horizontal runs accumulate fly-ash and soot which reduces
the exhaust flow and performance of the stove.
• TotalOffsetsinventingsystemshouldnotexceed270°totalindirec-
tion change.
• MaximumVerticalVent-30feet(9.14M)
• HorizontalRuns-Themaximumtotalhorizontalrunmustnotexceed
10feet(3.1meters).
• Horizontalrunofpiperequires1/4”(7mm)riseperfoot.
• Pelletventpiperequires3”(75mm)clearancefromoutsideofpipe
unlessotherwisespeciedbyventmanufacturer-alldiameters:3”(75
mm)and4”(100mm).Asupportbracketmustbeinstalledevery4
feet(1.2m)ofpelletventpipeontheexteriorwallofthehouseunless
otherwise specified by vent manufacturer.
• Itisnotrecommendedtoterminateexhaustventontheprevailing
wind side of the house.
• InCanada,wheretheventingmaypassthroughawall,orpartition
ofcombustiblematerials,theinstallationshallconformtoCAN/CSA-
B365.Wheninstallingthewallthimbleandotherventingcomponents,
follow the vent manufacturers instructions. Maintain an effective
vapor barrier at the location where the chimney or other component
penetrates to the exterior of the structure.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
10
Pipe/Liner Joint Requirements
Silicone sealant and three screws are required to secure the first vent
connection to the appliance flue collar. Secure the remaining vent sec-
tions using (3) three screws minimum per section, unless otherwise
specified by vent manufacturer's instructions. ALL horizontal joints
must be sealed gas-tight (air tight, sealed connection). Use RTV high
temperature silicone or Interam, if necessary, to provide a complete seal
between vent sections.
Connection to Masonry Chimney through a Wall
Be sure to verify the construction of a masonry chimney, as it may have
combustible framing.
Approved liner when relining Masonry or Factory Built Fireplaces is
2100HT(degreeF.)linerlistedtoUL1777orULCS635.
Connection to an Existing Class A Chimney
A chimney adaptor can be used to make the connection from 3” (75
mm)or4”(100mm)pelletventpipe(listedtoUL641orULCS609)to
existing UL chimney system. Verify with the pipe manufacturer that your
pipe brands will interconnect.
Horizontal Vent Installations
On all horizontal vent installations (short, horizontal runs with no vertical
pipe); care should be taken when choosing a location for terminating the
vent. It is not recommended to directly vent the exhaust on the prevailing
wind side of the house. It is recommended that when an appliance is
venteddirectlythroughawall,aminimumof8feet(2.5m)ofvertical
pipe should be installed to create some natural draft. This will reduce
the possibility of smoke or odor entering the dwelling during appliance
shutdown or loss of power.
Vent Termination
Do not terminate vent in an enclosed or semi-enclosed area such as:
carports, garage, attic, crawl space, under a deck, porch, narrow walkway,
closely fenced area, or any location that can build up a concentration of
fumes such as a stairwell, covered breezeway etc.
Vent surfaces can get hot enough to cause burns if touched. Adults
should supervise children when they are in the area of a hot stove.
Non-combustible shielding or guards may be required.
Termination Cap
The termination of the outside chimney of the pellet stove shall be located
in accordance with the following:
A.Higherthan3feet(.92m)aboveanyforcedairinlet(airconditioner,
etc.) located within 10 feet (3 m).
B.Notlessthan4feet(1.2m)below,4feet(1.2m)horizontallyfromor
1 foot (3.1 m) above any gravity air inlet (door, window, etc.) which
flue gases could reenter the dwelling.
C.Notlessthan2feet(.6m)fromcombustiblematerialssuchasan
adjacent buildings, fences, protruding parts of the structure, roof
overhang, plants and shrubs, etc. and not less than 7 feet (2.1 m)
above grade when located adjacent to the public sidewalks (access).
The final termination of the exhaust system must be configured so that
flue gases do not jeopardize the safety of people passing by, overheat
combustible portions of nearby structures or enter the dwelling.
D. The distance from the bottom of termination to grade is 12” (305 mm)
minimum unless otherwise specified by the vent manufacturer. This
is conditional upon plants and nature of grade surface: Be careful to
choose a location for the vent termination which does not expose
people or shrubs to high heat from the exhaust gases. The exhaust
gases are not hot enough to ignite grass, plants and shrubs located
in the vicinity of the termination although they should be a minimum
of3feet(.92m)away.Thegradesurfaceundertheterminationmust
not be a lawn.
E. Since sparks may escape from the exhaust pipe of any stove, use
caution when positioning the vent pipe. Refer to vent Manufacturer’s
instructions when installing and terminating the exhaust. The vent pipe
should be horizontal and never run the pipe in a downward direction
(recommenda1/4”[7mm]riseperfoothorizontal).

11
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
Vent Termination Locations
A = Refer to vent manufacturer's installation instructions
for the required clearance above grade, veranda, porch,
deck, or balcony.
B = Clearance to window or door that may be opened (min.
12”/30cmabove-48”/1.2mbelowandtotheside)
C = Clearance to permanently closed window *(min.
12”/30cm)
D = Vertical clearance to ventilated soffit located above
the terminal within a horizontal distance of *(min.
24”/60cm)fromthecenterlineoftheterminal(min.
22”/55cm) check with local code.
E = Clearance to unventilated soffit *(min. 12”/30cm)
F = Clearance to outside corner *(min. 12”/30cm)
G = Clearance to inside corner *(min. 12”/30cm)
H= Nottobeinstalledaboveameter/regulatorassembly
within*(min.36”/90cm)horizontallyfromthecenter-
line of the regulator.
J = Clearance to service regulator vent outlet *(min.
72”/1.8m)
K = Clearance to non-mechanical air supply inlet to build-
ing or the combustion air inlet to any other appliance
*(min.48”/1.2m)
L = Clearance to a mechanical air supply inlet *(min.
120”/3.1m)
M = **Clearance above paved sidewalk or a paved driveway
locatedonpublicproperty*(min.84”/2.1m)
N = ***Clearance under veranda, porch, deck, or balcony
(min. 12”/30cm)
NOTE:
* Local codes or regulations may require different clear-
ances.
** Aventshallnotterminatedirectlyaboveasidewalkor
paved driveway which is located between two single
family dwellings and serves both dwellings.
***Onlypermittedifveranda,porch,deck,orbalconyis
fully open on a minimum of two sides beneath the floor.
Vent Terminal
Area Where Terminal Is Not Permitted
(From Eave)
Vertical Terminal
Vertical Terminal
Fixed Closed
Able To Open
A
A
B
B
B
B
C
D
E
F
G
H
J
K
L
M
N
24”
(610mm)
B
Air Supply Inlet
24”
(610mm)
Figure 8
NOTE: Vent requirements are in
accordance with NFPA 211 and CAN/
CSA-B365-M standards
USA - 1' Min.
CANADA - 3' Min.
USA - 1' Min.
CANADA - 3' Min.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
12
*Min. 2 ft. clearance
is required to com-
bustibles (i.e. cedar
shake roof, etc.)
Figure 10 - Manufactured Home Chimney Height Requirements
Chimney Height Requirements - Site Built Residential Home
The vent termination height required is - USA, 1-foot minimum; Canada
3-feet minimum above the roof penetration point as illustrated below
(Ref. USA - National Standard, NFPA 211 and Canada National Standard
CSA B365-01). Check with your local building ofcial for additional
requirements for your area.
Figure 9 - Site Built Residential Home Chimney Height Requirements
Less than
10 Feet (3 m)
10 Feet
(3 m)
3 Feet (914 mm)
Minimum
2 Feet (610 mm) Min.
3 Feet
(914 mm)
Min.
m = meter
mm = millimeter
Requires A Listed Termination Cap * Top Of Flue Must Be
3’ Higher Than High-
est Point Of Roof
Penetration
Top Of Flue Must Be 2’
Higher Than Any Part Of
Roof Within 10’ Horizontal
Chimney Height Requirements - Manufactured Homes
Thechimneymustextend3’(.92m)abovethelevelofroofpenetration
anda minimumof2’ (.61m)higher than anyroof surface within 10’
(3m) (see below). Check with your local building officials for additional
requirements for your area.
To pass inspection in nearly any jurisdiction, the chimney must meet both
safety and exhaust flow requirements. The (3’ by) 2’ by 10’ rule applies
to both masonry and factory built chimneys
* Ref. USA - National Standard, NFPA 211-latest edition and Canada
National Standard CSA B365-01-latest edition. Vents installed with a
listed cap shall terminate in accordance with the terms of the cap’s
listings.
Termination When Connected to Masonry Chimney or Existing
Class A Chimney
A flexible corrugated chimney liner has much greater resistance to the
flow of flue gases than does a rigid liner. For this reason we recommend
thatalarger,4”linerbeusedonverticalrunsexceeding15feetorthat
rigid venting be used . See Figure 11.
If a flexible corrugated chimney liner is used, it must be fully extended
to eliminate any sagging and to improve the exhaust flow.
Figure 11 - Existing Chimney Termination
Listed Pellet Vent
Termination Cap
Chase Cover
1’ Section of PL Vent
(listed to UL 641 or
ULC S609)
3” or 4” liner
(listed to UL 1777
or ULC S635)
Termination When
Connected to Masonry
Chimney or Existing
Class A Chimney
Termination height is
measured above the
highest point where
it passes through the
roof surface.
Termination Cap
Must Be Listed To
UL 641 or ULC S609
USA 1 Foot Minimum
CANADA 3 Feet Mini-
mum

13
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
Determining Size Of Pipe To Install
Todeterminewhatdiameterpipetouseinaninstallation(3”or4”),rst
find the “equivalent pipe length” using the following guidelines, then plot
the number and the altitude on the installation chart (Figure 12).
Fill out the installation chart, and calculate your total equivalent pipe
length. After you have the total equivalent pipe length, use the Pipe
SelectionChart (Figure 12) to determine if your installation requires 3”
or4”exhaustpipe.
Installation Chart
Figure 12 - Pipe Selection Chart
Figure 13 - See Sample Installation Chart
A- 90 Degree Elbow
B- 1’ Horizontal Pipe
C- 45 Degree Elbow
D- Standoff Braces
E- 8’ Vertical Pipe
F- 2’ Horizontal Pipe
G- 90 Degree Tee
H- Wall Thimble
NOTE: Allequivalentpipestyles
shown are standard for all free-
standing models.
A
E
F
H
G
B
C
D
Type of Pipe # of Elbows or
Feet of pipe Equivalent Feet Total Equivalent
Feet
90° Elbows /
Tee (A & G) x 5 Ft. (1.5 m)
45° Elbows
(C) x 3 Ft. (1 m)
Horizontal
(B & F) x 1 Ft. (.3m)
Vertical(E) x .5 Ft. (.15m)
Table 2
Sample Installation Chart
Type of Pipe # of Elbows or
Feet of pipe Equivalent Feet Total Equivalent
Feet
90° Elbows /
Tee (A & G) 2 x 5 Ft. (1.5 m) 10 (3m)
45° Elbows
(C) 1 x 3 Ft. (1 m) 3 (1m)
Horizontal
(B & F) 3 x 1 Ft. (.3m) 3 (1m)
Vertical (E) 8 x .5 Ft. (.15m) 4 (1.2m)
Total Equivalent Feet = 20
Table 3 - Sample Chart for Figure 13
4" Diameter Only
3 or 4”
Diameter
Altitude x 1000 Feet
Equivalent Pipe Length (Feet)
30
20
10
0
012345678910

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
14
G*
D
A
BC
E
F
A
D
Standard Horizontal Vent Installation
Installing the Cascade™ Pellet Stove
This stove is approved for venting with Type L and Type PL pellet vent
pipe listed to UL 641 or ULC S609.
1. Locate the proper position for the listed type “PL” wall thimble. Avoid
cutting wall studs when installing your pipe. Use a saber saw or keyhole
saw to cut the proper diameter hole through the wall to accommodate
the wall thimble. Use extreme caution to avoid cutting into power lines
within the wall of the home. The hole size will depend on the brand
of pellet vent that you are using. Install the wall thimble in the hole.
2. ALL INTERLOCKING PIPE CONNECTIONS MUST BE SEALED GAS-
TIGHT AND SECURED TOGETHER PER VENT MANUFACTURER
INSTRUCTIONS.
Position the stove approximately 12” (305 mm) from the wall on the
floor pad. Push the “PL” pipe through the wall thimble. Squeeze a
bead of high temperature silicone (RTV) sealer around the end of the
machinedportionofthe3”(76mm)pipeconnectoronthebackof
the stove. Firmly push on a section of “PL” pipe until inner pipe liner
pushes into the bead of RTV sealer.
3. Push the stove with pipe attached towards the wall (the pipe will go
through the wall thimble). Do not position the back of the stove closer
than 1” (25 mm) from the wall (see Clearances, Page 5).
4.Installlistedtype“PL”45degreeelbowwithrodentscreenorcapon
outside end of pipe. The Inlet shall remain free of obstruction while
unit is in operation and constructed in a manner so as to prevent mate-
rial from dropping into the inlet or into the area beneath the dwelling.
Theinletshallalsohaveascreenwithopeningsnotlargerthan1/4"
to prevent rodents from entering.
5. If the installation includes a source of outside combustion air; cut a
separate hole through the wall for the fresh air tube. This tube should
be1-5/8”(42mm)minimumdiameterI.D.,steelonly.Connectoutside
airpipetoairinletonstove.Thistubemustbeterminatedwitha45
degree elbow or hood.
NOTES:
• Combustion air may also be drawn from a vented crawl space under
the home.
• Alljointsforconnectorpipearerequiredtobefastenedtogetherperthe
ventmanufacturersinstructions.Ifventedhorizontally,jointsmustbe
madegas-tight(airtight,sealedconnection)inamannerasspecied
onthispage(seeinstruction#2).INSTALL VENT AT CLEARANCES
SPECIFIED BY THE VENT MANUFACTURER.
• Greaterbackclearancewillimprovetheeaseofserviceabilityofthe
stove.
• Theendoftheexhaustpipemustextendaminimumdistancefromthe
outside of the building. Refer to the vent manufacturer's instructions
for this clearance requirement.
uRefer to vent manufacturer's installation
instructions for minimum vent clearances.
NOTE: Connect “C”to “F”
* Connect a Metal Fresh Air Pipe - OPTIONAL
(EXCEPT FOR MOBILE HOME INSTALLATIONS)
u
A. Use RTV Here
B. Quick Disconnect Fitting
C. 3”(75 mm) PL-Vent Pipe
D. Wall Thimble
E. Hole in Wall
F. 45 Elbow or End Cap
G. Combustion Air Inlet *
u
Figure 14 - Horizontal Vent Installation
Silicone sealant and three screws required on the first vent connection.
Secure and seal the remaining vent sections PER VENT MANUFACTURER INSTRUCTIONS.

15
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
uRefer to vent manufac-
turer's installation instruc-
tions for minimum vent
clearance
Corner Through the Wall
Top View Illustration
Horizontal Vent Through the Wall
Side View Illustration
Wall
llaW
1" (25.4 mm)
Minimum 12" (305 mm)
Minimum From
Outer Wall
45 Degree
Elbow
12" (305 mm)
From Ground or
Other Surface
6" / 152 mm
Minimum
Hearth Pad / Floor Protection
Outside
Air Intake
12" (305 mm)
Minimum From
Outer Wall
Corner Through the Wall
Top View Illustration
Horizontal Vent Through the Wall
Side View Illustration
Wall
llaW
1" (25.4 mm)
Minimum 12" (305 mm)
Minimum From
Outer Wall
45 Degree
Elbow
12" (305 mm)
From Ground or
Other Surface
6" / 152 mm
Minimum
Hearth Pad / Floor Protection
Outside
Air Intake
12" (305 mm)
Minimum From
Outer Wall
Standard Horizontal Installation Configurations
Model: Cascade®
Figure 15 - Corner Through the Wall
Figure 16 - Parallel Through the Wall
Maintain minimum clearances specified by
vent manufacturer between wall and pipe.
If you vent to the furthest wall, the vent pipe
mustmaintainthespecifiedclearanceparal-
lel to the other wall.
1” (26 mm)
Minimum
Outdoors
NOTE: Horizontal run of
piperequires1/4”(7mm)
rise per foot.
NOTES:
• Itisnotrecommendedtoterminate
exhaust vent on the prevailing wind
side of the house.
u
u
u
uRefer to vent manufacturer's
installation instructions for minimum
vent clearance
Do not install back to back
elbows right off the back of the
stove in any installation.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
16
Standard Vertical Installation Configurations
Model: Cascade®
This appliance may be connected to an existing flue or by installing
type“PL”ventpipe(listedtoUL641andULCS609).Ifalinerisrunall
the way to the top of the existing chimney, the existing flue should be
sealed with a steel plate. Start a vertical run with a Tee at the back of the
stove. Other options are illustrated below. NOTE:SeeVentTermination
Requirements on Pages 9 through 11.
Preferred Installation – Vertical Vent Through the Roof
This venting configuration allows for the best stove performance. The
vertical pipe promotes natural draft and with the chimney inside the
dwelling, the flue gases stay warm, thus rising at a consistent rate.
NOTE:SeePages 9 through 11forVentTerminationRequirements.
Figure 17
Exterior
Vertical Vent
Vertical Vent
Into a
Masonry Flue
Interior
Vertical Vent
into an Exist-
ing Class A
Chimney
Vertical Vent
Through the
Roof
Figure 18 Figure 20
Figure 19
Clean-Out
Tee
Listed Rain Cap
Optional
Clean-Out
Access Door
Optional Complete
Liner and Listed
Termination Cap
Listed Rain Cap
Extend Pipe to the Top
if Existing Chimney is
Corroded or Damaged
Pipe Increaser
Existing
Chimney Pipe
Listed Rain Cap
Maintain clearances
specified by vent
manufacturer
Wall Straps
Required Every
4 Feet Minimum
Clean-Out
Tee
Maintain clearances
specified by vent
manufacturer
Flashing
Listed Rain Cap
Maintain clearances
specified by vent
manufacturer
Maintain clearances
specified by vent
manufacturer

17
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
CARE AND OPERATION
Simple Operating Instructions
3. Priming the Auger
(Optional)
a] Fill hopper with pellets
NOTE: Use quality grade pellet
fuel
b] Move the "HEAT OUTPUT"
switch on the control panel
tothe“HIGHHEAT”position
to activate the auger.
e] When pellets begin to
drop from feed tube into
UltraGrate, turn switch to
"OFF"
1. Start
4. Stove is now ready for
start-up
5. To Start Your Stove
a] Check hopper, and fill with
pellets, if necessary.
b] Place a small amount of an
approved (non-volatile) gel fire
starter on top of the pellets in
the UltraGrate. Using a match,
light the pellets. Close Door.
b] Turn the "HEAT OUTPUT"
switch to the "LOW HEAT"
setting.
The convection blower will be
activatedwhentheHEATOUTPUT
switch in on low or high.
6. Pellets will drop into
UltraGrate and stove will
light in approximately 3
to 7 minutes
Does the Stove Light?
7. The stove will enter "heat-
ing" mode and run at the
chosen setting
8. After approx. 5 minutes
adjust damper if neces-
sary to obtain a bright
vibrant flame.
NOTES:
•If the damper is too far
inward the flame will be
lazy/sooty and the fuel will
pile up in the UltraGrate
(seePage 8).
•If the damper is too far
outward the flame might
burn erratically.
See Page 8 for further
instructions on adjusting
the damper.
No
7a.Followthetroubleshooting
section in this manual
Contact your IHP dealer for
further assistance
10. Thank you for purchasing an IHP Pellet
Stove
END
Does the Stove Light?
No
FIRST TIME USE
9. To Turn Off Pellet Stove
a] Turn the "HEAT OUTPUT"
switch to the "OFF" posi-
tion.
b] Stove goes into cool-down
mode. Pellets stop feeding
and the fire goes out within
2 minutes after the auger
is shut off, the room air
blower and exhaust blower
will automatically shut off in
approximately 15 minutes.
2. Preparation
a] Check hopper and remove
any materials from hopper
and auger
b] Check cast UltraGrate for
proper fit (ensure cast
UltraGrate is set securely in
the base - see Figure 22)
c] Check door gasket and door
latch to ensure tight seal
(see Figure 30)
d] Connect power cord to
grounded power supply
outlet
Yes
Yes
Heat Output Auger On Indicator
LENNOX
09-0594

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
18
Control Board
Heat Output Switch - TheHeatOutputswitchactivatesboththecon-
vection and combustion blowers and the auger motor. If the exhaust
does not reach operation temperature within 25 minutes, the stove will
automatically shut down. If this occurs, repeat the lighting procedure
(pre-lighting instructions).
“OFF” position - The“Off”positionontheHeatOutputswitchwillturn
the stove off by turning off the auger motor. The remaining fuel in the
grate will safely burn up. Once the stove has cooled sufficiently the
blowers will shut off automatically.
“HIGH HEAT” position - The“HighHeat”positionontheHeatOutput
switch will increase the fuel feed rate and blower speed for maximum
heat output.
“LOW HEAT” position -The“LowHeat”positionontheHeatOutput
switch will decrease the fuel feed rate and blower speed.
Auger “On” Light - The red L.E.D. light on the control panel indicates
when there is power to the auger motor. Under normal operation, this
light will blink on and off.
Fuel Feed Trim Control - The fuel feed trim control on the control panel
should be used when the damper control will not correct a poor combus-
tion problem. Turning the trim control counter clockwise will decrease
the amount of fuel entering the UltraGrate™ and turning the trim control
clockwise will increase the amount of fuel entering the UltraGrate. The
trim adjustments compensate for fuel differences. Factory set “ON” time
is1.9seconds.Thetrimrangeis1.6to4.5seconds.Factory“OFF”time
forlowisxedat4.2secondsandforhighitisxedat2seconds.
NOTE: Thiscontrolboardisnotthermostatorignitercapable.
Fuel Delivery Rate
The feed rate switch manages the fuel delivery rate by controlling the
amount of time the auger motor will run as follows:
*Feed rates are approximations only. Actual feed rate will vary depend-
ing on size, quality and length of fuel used and variations in line volt-
age.
**Estimated heat input based on fuel value of 8,400 BTU per lb. of
fuel.
NOTE: Itisnormalforsomeashtobuildupontheinnerglasssurface
at the lower burn settings.
Fuel Delivery Rate
Feed
Rate
Setting
Auger Motor
ON/OFF
Time
(seconds)
Auger “ON
Time” Trim
(seconds)
*Lb.’s per
hour fuel
delivery
**Approx-
imate BTU
per hour fuel
delivery
Burn
Time
(hours)
Low = 1.9 on / 4.2
off (+/- 5%)
1.6 to 4.5
seconds
1.5 Lb.’s
/ hr.
12,600 BTU
/ hr
40
High = 1.9 on / 2
off (+/- 5%)
1.6 to 4.5
seconds
3.5 Lb.’s
/ hr.
30,000 BTU
/ hr
17
Table 4
Initial Start-up / Empty Hopper Or Feed Tube:
During an initial start-up, or in the case where the hopper has run out of
fuel, it will be necessary to prime the auger feed system.
To prime the auger feed tube:
1. Ensure all packing material and foreign objects are removed from the
hopper. Fill the hopper with recommended pellet fuel and plug the
stove into the wall outlet.
2.MovetheHeatOutputswitchonthecontrolpaneltothe“HIGHHEAT”
position to activate the auger and blowers.
3. Look through the combustion chamber door and when you can see
the first pellets dropping into the grate, the auger is fully primed. This
will take up to 10 minutes.
Starting Your Pellet Stove
1.Aftertheaugerisfullyprimed,adjusttheHeatOutputswitchtothe
“OFF” position.
2. Place a small amount of an approved (non-volatile) gel fire starter
on top of the pellets in the UltraGrate (if chips are used as firestarter,
place chips in UltraGrate first then place pellets on top). Consult with
yourauthorizedIHPdealerforapprovedrestartingproducts).DO
NOTUSEFLAMMABLELIQUIDSTOSTARTYOURSTOVE.
3. Light the fire starter in the UltraGrate with a match and close the door.
4.Afterapproximately10seconds,movetheHeatOutputswitchonthe
controlpaneltothe“LOWHEAT”position.Youwillnoticethatthere
willbecomeactiveandtherewillbeaircomingfromtheHeatExchange
Tubes and pellets will now begin to feed into the UltraGrate.
5.Afterthereisburningwell,adjusttheHeatOutputswitchtothe
desired setting. Adjust the damper control if necessary for proper
combustion. Look for a brisk, bright yellow to whitish flame.
Remember, different brand fuels feed at different rates.
Turning Off Your Stove
MovetheHeatOutputswitchtothe“OFF”position.Thiswillstopthe
fuel feed and any remaining fuel in the grate will safely burn up. The
blowers will continue to run until the stove has cooled off sufficiently
and will then shut off automatically.
Figure 21 - Control Board WARNING
• Never empty pellets from the Burn-Pot into the hopper.
Pellets that may appear to be cool may retain enough
heat to ignite other pellets resulting in smoke or fire
damage.
• DO NOT OVERFIRE THIS STOVE. This may cause
serious damage to your stove and void your warranty.
It also may create a fire hazard in your home. IF ANY
EXTERNAL PART OF THE UNIT BEGINS TO GLOW, YOU
ARE OVERFIRING. Immediately slide the knob to the
"OFF" position on the control board.
Heat Output Auger On Indicator
LENNOX
09-0594

19
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
Fuel Specifications - Using the Ultragrate™ burn system, this appliance
has been designed to burn wood residue pellets only (with up to 2% ash
content). Agricultural pellets (i.e. corn, alfalfa etc.) are not permitted to
be burned in the stove. Dirty fuel will adversely affect the performance of
the stove. The pellet fuel should meet P.F.I. (Pellet Fuel Institute) standards
for standard grade or premium grade residential pellet fuel. If the pellet
fuel meets these standards, it will be printed on the bag. Any questions
regarding pellet fuel can be answered at the Pellet Fuels Institute (PFI),
www.pelletheat.org.
Pellet Feed/Pellet Size - The pellet feed system is designed to handle a
widerangeofpelletsizesuptoamaximumof5/16”diameter.Different
pellets may feed at considerably different rates. You may notice a differ-
ence in the burn if you change pellet fuel sizes. The longer the pellet, the
slower it will feed and vice versa. If the stove will not stay burning at the
minimum fuel feed setting, those particular pellets may not be feeding
fast enough. If this happens, reduce the amount of combustion air by
adjusting the damper. See Page 8 before adjusting the damper.
Clinkering - Silica (or sand) in the fuel, along with other impurities, can
cause clinkering. A clinker is a hard mass of silica formed in the burning
process. Clinkering is a function of the fuel, (not the stove), but adversely
affects the performance of the stove by blocking off the air passages in
the grate. Even P.F.I. approved pellet fuel may tend to clinker. A clinker
can be removed from the UltraGrate™ and placed in the ash pan with
the use of the grate scraper/ash pan tool furnished with your stove. See
Routine Maintenance (on Pages 20 through 24)for more information
on cleaning.
FUEL
CAUTION
The use of unapproved, dirty, wet and / or high salt
content fuel will void the warranty!
Filling the Hopper
To fill the hopper when stove is off:
1. Lift the hopper lid to it's full opened position.
2. Fill the hopper with pellets.
3. Check to make sure there are no remaining pellets on top of the
hopper that may prevent the hopper lid from fully closing.
4. CloseHopperlid.
To fill the hopper when stove is in operation:
1. Repeatsteps1thru4above.
2. When finished, check the red Auger “On” Light on the control panel
to verify that the stove is still in normal heating mode. The Auger
“On” Light indicates when there is power to the auger motor. Under
normal operation, this light will blink on and off.
3. If the Auger “On” Light on the control panel is off, the hopper lid
has been open too long and unit has gone into shut-down mode. To
relight, follow lighting instructions on Page 17.
CAUTION: Failure to ensure pellets in the UltraGrate remain
burning after re-fueling may result in smoke escaping from
the unit.
Lighting
Follow instructions on Page 17.
Automatic Safety Features
Power Outage: During a power outage, the stove will shut down safely.
Itwillnotautomaticallyrestartwhenthepowerisrestored.However,a
momentary power interruption may not shut your stove down.
A small amount of smoke may leak from the top of the window glass,
the hopper and from the combustion air intake, if the stove is vented
horizontally with no vertical pipe. This will not persist for more than 3
to 5 minutes and will not be a safety hazard. It may set off your smoke
alarm. To re-light the stove, follow the normal procedure for starting
your stove.
NOTE:Iftheareainwhichyouliveispronetofrequentpoweroutages,
itisrecommendedthataminimumof8feet(2-1/2meters)ofvertical
vent pipe be included in the installation to induce a natural draft in the
event of a power outage.
Overheating: A high limit thermal switch will automatically shut down the
stove if it overheats. The stove will need to be manually re-lit. Allow up to
45minutescoolingtimebeforere-lighting.Iftheoverheatingcontinues,
contact your authorized IHP dealer for more information.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
20
Ash - The frequency of removal of the ash and maintenance performed
on the stove is directly proportional to the ash content of the fuel and the
operation duration of your pellet stove. Low ash fuel may allow longer
intervals between cleaning, however, a stove burning high ash fuel may
need to be cleaned as often as everyday.
Fuel Feed Rates - Different brands of pellets will feed at varying rates
due to their size and density (length and diameter). This may require a
slight adjustment in the damper control (see Page 8) or the fuel feed
trim to compensate (see Page 18).
NOTE: SeeFuelDeliveryRateonPage 18 for burn times.
PLEASE NOTE: IHP has no control over the manufacturing of pellet
fuel and will not be held responsible for poor stove performance or any
damage caused by poor quality pellet fuels.
Pellet Fuel Storage -
• Store your wood pellets in a dry place to prevent them from absorbing
excess moisture.
• Do Not store your wood pellets within the clearance zone of the
stove.
• Do Not store your wood pellets in a place that would block removal
of the ash pan or block access to refueling the hopper.
Wood pellets manufactured to the pellet fuels institute (P.F.I.) certification
standard are available in two grades, Standard and Premium. The primary
difference between the two is the ash content of the pellets.
The P.F.I. specification for standard grade and premium grade residential
and commercial pellet fuel is as follows:
• CHLORIDES (Salt): Less than 300 p.p.m. to avoid stove and vent
rusting.
• BULKDENSITY:38to40lb./Cu.Ft.minimum
• MOISTURECONTENT:8%to10%maximum
• ASHCONTENT:<2%maximum(standardgrade)<1%maximum
(premium grade)
• FINES:0.5%to1%maximumthrougha1/8”screen
• BTUCONTENT:Thereareanumberofvariationsinpelletfuelsthatare
not included in PFI standards. For example, BTU (heat value) content
mayrangefromjustunder8,000toalmost9,000BTU,depending
upon species and region of the country and other variables.
ROUTINE MAINTENANCE
IMPORTANT CAUTIONS:
• UNPLUG POWER CORD AND ENSURE APPLIANCE IS COLD
BEFORE PERFORMING ANY MAINTENANCE WORK.
• Some brands of pellets produce more ash and clinkers than
others. Therefore the frequency of performing the following
cleaningproceduresdependstoagreatdegreeonthequality
of the pellets burned.
• Not cleaning this unit will cause it to burn poorly and will
void your warranty for this appliance.
• When removing ash build-up, use an approved ash vacuum
only.A cleaning brush can be used to loosen any ash build-up
before vacuuming. DO NOT USE A STANDARD HOUSEHOLD
VACUUM OR “SHOP VAC” AS THE FILTERS WILL LEAK THE
FINE PARTICLES OF ASH INTO THE HOME.
NOTES:
•Cleaning schedule will vary depending on quality of pellets used.
Burning high ash pellets will require more frequent cleaning.
• Usingadropclothisrecommendedassomeashmayspillontothe
floor during the cleaning process.
Cleaning
The following areas need to be inspected during routine cleaning:
•· UltraGrate™(burngrate)(Homeowner)
•· AshSlidePlates(Homeowner)
•· AshPan(Homeowner)
•· HeatExchangeTubes(Homeowner)
•· ExhaustPassagesandVentPipe(QualiedTechnicianOnly)
• Gaskets(QualiedTechnicianOnly)
• WindowWash(Homeowner)
• CleaningRearStoveCompartment(QualiedTechnicianOnly)
• BlowerCleaning(QualiedTechnicianOnly)
UltraGrate™(Burn Grate)
(Recommended Frequency of 1 – 2 days*)
Inspect the UltraGrate periodically so that the air holes don't clog with ash
or clinkers. The UltraGrate can easily be cleaned with the grate scraper
tool, or it can be removed. It is very important to monitor the ash build up
under the UltraGrate, as too much of ash will block combustion air from
entering the grate, causing pellets to pile-up in the grate. A clogged grate
will reduce the overall performance of the stove, cause dirty glass and
if not cleaned may lead to smoke escaping the stove. The ash build-up
under the grate is easily dumped into the ash pan by pulling out the ash
slides weekly (see AshSlidePlate,Figures 23 and 25).
Figure 22 - UltraGrate
Table of contents
Other IronStrike Pellet Stove manuals
Popular Pellet Stove manuals by other brands

Enviro
Enviro Mini A Technical manual

Vogelzang International
Vogelzang International VG5790 owner's manual

Enviro
Enviro EF2 Service manual

Piazzetta
Piazzetta P963 C Instructions for installation, use and maintenance

MCZ
MCZ EGO 2.0 AIR OYSTER installation guide

Palazzetti
Palazzetti EcoFire IDRO Installation, user and maintenance manual

Extraflame
Extraflame LUCIA PLUS user manual

Lopi
Lopi Foxfire AGP manual

Piazzetta
Piazzetta P963 THERMO Instructions for installation, use and maintenance

Quadra-Fire
Quadra-Fire CASTILE-MBK-B owner's manual

Piazzetta
Piazzetta P960 manual

Breckwell
Breckwell ECO-AIRE SP8000 Owner's operation and instruction manual