
The LA - Series Remote Operator is a secondary control unit that, when
companioned with Standard Controller, permits the same level of control for
an appliance or secondary outlet device as the primary or master control unit
without the necessity to provide a second power supply. The standard 7000
Series unit features a black “OPERATE” ON key switch and a red OFF or
“STOP” button. The operators function independently from the primary
control unit. However, an alarm notification signal input to the primary
controller or the striking of the primary’s Panic Button will disable this unit.
Only after withdrawal of the alarm signal, reset at the primary controller, and
finally the engaging of this unit’s “OPERATE” switch will the output circuit
be restored.
The 8000 Series provides for custom modifications. This series standard is
provided with a maintained push button ON switch with a key reset. The unit
can be configured so that the panic button will interrupt operation of this sole
unit or a master control unit.
INSTALLATION, OPERATION &
MAINTENANCE INSTRUCTIONS
Warranty:
ISIMET will repair or replace any defective parts or workmanship of this product for a period of one year from date of installation.
The P.C. Board has a two year limited warranty. Damage caused by incorrect installation or improper usage is not warranted. Failure
to follow recommended installation, operation, and/or maintenance procedures listed in this manual may void product warranty.
Recovery rights shall be limited to the total sum of the amounts paid for the product by the purchaser.
Limits of Liability:
ISIMET's liability shall be limited to costs of repair or replacement parts. The Laboratory Service Panel and Utility Controller are not
intended for usage other than those expressly described in this manual. ISIMET shall not be liable for damage or injury caused by the
improper use of the product.
ISIMET does not warrant against or assume liability for failure of operation or lack of notification to secondary integrated monitoring
systems. The system should be thoroughly tested and adjustments made at time of initial operation. Periodic testing should be
conducted by the user to assure that all components function and operate according to specifications.
Care should be taken in the installation of this product. ISIMET shall not be liable for damage or injury caused from the improper
installation of the product.
Specifications:
Control Panel - Stainless Steel 16 gauge
Wall Box –16 gauge plated sheet metal
LA –7000 5.0 X 5.0 X 3.0
LA –8000 5.0 X 7.0 X 4.0
Output Voltage Configuration:
The Remote Operator may be configured to
provide either a 24-vac output circuit or as
dry-contacts to operate the line leg of a 120-
vac circuit. Pilot duty rating of the unit is
1.5 amps.
Caution: Attention should be given to total
output rating of the integrated LA Series
Master Controller to assure no overload of
24-vac systems occurs.
ISIMET 103 C.J. Wise Pkwy Naples, TX 75568 (903) 897-0737 (903) 897-0740 fax