IAI3002B-01 Page 5 of 9 07/18
•Refer to the Control Board LED Checklist below if the actuator is not functioning.
Control Board LED Checklist
Note: During normal operation, LED's 4-9 are not lit. If any are flashing or lit, refer to
chart below to troubleshoot.
Check power supply and verify wiring.
Board may be damaged. Send back to factory
for inspection.
Flashing or lit
(Applies to 24V models only)
Confirm that the voltage is within nominal
operating range (20.4-26.4V DC).
Confirm that the input signal is the same as dip
switch setting. Refer to "Dip Switch Setting"
section in this manual.
Check that setting is correct; might be set to 2-
10V input, but supply is 4-20mA.
The setting is set to 2-10V, but the input signal
is over 13.5V.
Flashing or lit means Motor
thermostat turns OFF
Frequency is too high for rated duty cycle.
Motor thermostat is not connected.
Flashing: Output signal short
circuit
Check wiring on terminals #11 and #12, should
be: #11 "-" and #12 "+".
Lit: The 2-10V input signal is
not connected properly
Check wiring on terminals #6 and #7, should be:
#6 "-" and #7 "+".
Flashing or lit means that
motor current is excessive
Frequency is too high for rated duty cycle.
The motor rotor is jammed.
Flashing or lit means that it is
in setting mode
Press "SET" once to exit the settings menu.