J.Schneider AKKUTEC 2412 VdS User manual

User manual
AKKUTEC 2412 VdS
Document page 1 / 16
0812G01B02-160422.docx
J. Schneider Elektrotechnik GmbH
Helmholtzstraße13, 77652 Offenburg · Postfach 2327, 77613 Offenburg · Werner-von-Siemens-Straße 12, 77656 Offenburg
Tel +49 (0) 781 206 0 · Fax +49 (0) 781 253 18 · [email protected] · www.j-schneider.de · Amtsgericht Freiburg HRB 470458
Geschäftsführer: Dipl.-Betriebswirtin (BA) Bettina Schneider · Dipl.-Wirt,-Ing. (FH) Rolf Anti · UST-Ident-Nr. DE142532740
DC-USV
NBPA0812G01***
VdS-Nummer G209169
0786-CPD-20873
page
1. General......................................................................................................................2
1.1 General safety notes
1.2 Short description
2Transportation and storage.....................................................................................3
3Installation and connection.....................................................................................3
3.1 Installation
3.2 Connection
3.3 Connection lead accumulator
3.4 Connection of mains voltage
3.5 Connection load
3.6 Signal contacts
3.7 Circuit diagram
4Start-Up .....................................................................................................................9
4.1 Display and messages
5Operation ..................................................................................................................9
5.1 Mains operation
5.2 Back-up operation
5.3 Deep discharge protection
5.4 Accumulator circuit monitoring
5.5 Accumulator test
5.6 Temperature tracking (optional)
5.7 Shut-Down
5.8 Acoustic alarm transmitter (optional)
6Master/Slave-operation at parallel connection .....................................................11
6.1 Connection at Master/ Slave-operation
6.2 Signalisation at Master/Slave-operation:
6.3 Shutdown at Master/Slave-operation
6.4 Configuration Master/Slave
7Servicing ..................................................................................................................13
7.1 Testing the lead accumulators
7.2 Exchanging the lead accumulators
8Decommissioning....................................................................................................14
9Disposal ...................................................................................................................14
10 Norms and regulations ...........................................................................................14
11 Technical Data.........................................................................................................15
12 Accessories .............................................................................................................16

User manual
AKKUTEC 2412 VdS
Document page 2 / 16
0812G01B02-160422.docx
1. General
The accumulator buffered DC supply guarantees a safe backup of the DC supply in case of a mains failure.
Every other use is strictly excluded.
The operating instructions must be read prior to use or installation; all instructions have to be considered!
Commissioning and maintenance may only be performed by qualified specialist personnel.
All warranty and guarantee claims could be lost in case of non-observance or unauthorised modifications!
This power supply is only a built-in unit with VdS certification. For a proper VdS installation the external power
supply must be installed in a housing with protective system IP30 or better. Furthermore the temperature sen-
sor which is optionally available must be installed for temperature tracking
1.1 General safety notes
NOTE
The operating instructions must be read prior to installation or use of the unit. The instructions
must be observed. All warranty claims could be lost in case of non-observance!
DANGER
Only specialised electricians are authorized to commission and maintain the unit. Improper han-
dling with voltage procedures or lead accumulators can lead to electric shock and severe burns.
DANGER
All work on the unit may only be performed in de-energized state!
The five safety rules must be observed.
Input and output lines must be sufficiently dimensioned and fused!
Never open the housing. Repair may only be done by the manufacturer!
Non-observance can lead to fatal electric shocks.
CAUTION
For use in a controlled environment refer to chapter 11 Technical Data for environmental condi-
tions.
NOTE
In case of malfunction we recommend to send the unit to the manufacturer
The unit has been developed for protection class I and has the degree of protection IP20. Operation is only
admissible in dry rooms. The operation is only allowed in closed housings. This device is designed for pollu-
tion degree 2. The applicable VDE regulations, in particular VDE 0100 and EN 60204, must be observed!
The admissible ambient temperature range must be observed!
The DC output circuit must be fused externally in order to avoid overload! (See section 3.2)
The two energy sources (mains and lead accumulator) must be separated in order to de-energize the unit on
the output side!
Only the lead accumulator types specified for the unit must be used! The change of lead accumulators must
only be performed when the unit is de-energized! (see section 7.2). If external buffer accumulators are used,
accumulator safeguarding must be performed by the user! For safety reasons, the safeguarding element
(overload and short circuit protection) must be arranged in close proximity to the accumulator set! If lead ac-
cumulators are used, sufficient air flow must be provided according to VDE 0510, part 2.
Never interconnect new and used lead accumulators, or lead accumulators of different types or from different
manufacturers.
Used lead accumulators must be disposed carefully.

User manual
AKKUTEC 2412 VdS
Document page 3 / 16
0812G01B02-160422.docx
L1
N
AKKUTEC 2412
IO-2
Betrieb /Operation
BatOK
Störung /Fault
Netz/MainsOK
MadeinGermany
www.j-schneider.de
IO-1
1
2
3
4
5
6
7
8
9
Netz/
MainsOK
BatOK
Störung
/Fault
1
2
3
4
5
6
7
Temp
Temp
+Shut
-Shut
CS
Sync
Eingang /Input
Bat
Ua
RS232
1.2 Short description
The accumulator buffered DC supply works according to the standby parallel principle and guarantees, in con-
nection with a lead accumulator and for a certain time interval, a safe upkeep of the DC supply in case of a
mains failure. The overall output current is split up between consumer supply and lead accumulator charge.
The power supply is characterized by the following properties:
Switching power supply with I/U charging characteristic
aktiv power factor correction (PFC)
Micro-controller supported lead accumulator management
RS232 for monitoring and parameterization
Temperature adjustment of the charging voltage by an external sensor
2 Transportation and storage
The transportation of the unit may only be carried out in the original packaging. During transportation and stor-
age the environmental conditions must be observed (see section 11 Technical Data). The units must be pro-
tected against humidity and direct sunlight. If lead accumulators are included, they must be recharged at least
each half year in case of longer storage.
3 Installation and connection
3.1 Installation
The unit must be installed in a way that the necessary cooling is guaranteed. A minimum distance of ≥ 75mm
must be kept to neighbouring units or assemblies in the area of the ventilation slots.
The installation must always be performed in a way that sufficient air circulation through the unit is ensured. All
fixing points must always be used for fixing the unit.
The specific environmental temperature must not be exceeded. The maximum mounting height without load
reduction amounts to 2000 m above sea level.
The power supply features protective system IP20, but the VdS guidelines recommend protective system
IP30. To fulfill this requirement, the power supply must be installed additionally in a housing or wall housing
with the corresponding protective system.
NOTE
If swarf could fall onto or into the unit, it must be
covered during installation. (Danger of short-
circuit!)
NOTE
The unit is a built-in unit. Operation is only per-
missible in closed cabinets or housings. The
unit is designed for pollution degree 2
Mounting height: 155.0mm
mounting width: 95.0mm
mounting depth: 183.0mm (without terminals)

User manual
AKKUTEC 2412 VdS
Document page 4 / 16
0812G01B02-160422.docx
3.2 Connection
Prior to connection, the DC voltage supply values must be checked for compliance with the values given on
the label. Connect according to the designations of the connection terminals (see terminal assignment, sec-
tion 3.7 Circuit diagram). Not used connection screws must be tightened.
NOTE
The external energy supply must be connected to a power circuit with its own, individually identi-
fied fuse (16A).
From that fusing, there must be only one more fusing up to the low voltage side supply point on
the electric mains (service entrance box).
The interruption of the power circuit to the external energy supply caused by switching off other
equipment must be excluded.
NOTE
In case of overload, the DC output current is composed of the maximum charge rectifier cur-rent
and the lead accumulator current. The DC output circuit must be fused externally in order to
avoid overload!
If the external power supply is installed as a part of a fire alarm system, the following regulations must be ob-
served in their currently valid version:
DIN 14675 “Fire detection and alarm systems - design and operation”
DIN VDE-0833, part 1 + 2 “Alarm systems for fire, intrusion and hold up“
DIN VDE-0800 “Construction and operation of telecommunication facilities including
information processing facilities”
DIN VDE-0165 “Construction of electrical systems in areas with risk of
explosion”
Guideline VdS-2095 “VdS Guidelines for automatic fire detection and alarm systems,
Planning and Installation”
VDE 0100 “Installation of power circuits
with nominal voltages up to 1000 V”
EN 60204 “Safety of machinery - Electrical equipment of
machines“
DANGER
The unit is prepared for degree of protection I (protective earthing). It is obligatory to connect to
operational earth. In case of non-observance, touchable parts may be live. Danger of fatal
electric shocks.

User manual
AKKUTEC 2412 VdS
Document page 5 / 16
0812G01B02-160422.docx
3.3 Connection lead accumulator
Capacity
Max. load current
during charging (ImaxA)
Rated current
of the power supply (ImaxB)
2x lead accumulator 12 V / 26 Ah
10.70 A
12 A
2x lead accumulator 12 V / 38 Ah
10.10 A
2x lead accumulator 12 V / 40 Ah
10.00 A
2x lead accumulator 12 V / 45 Ah
9.75 A
2x lead accumulator 12 V / 65 Ah
8.75 A
4x lead accumulator 12 V / 65 Ah
5.50 A
2x lead accumulator 12 V / 85 Ah
7.75 A
4x lead accumulator 12 V / 85 Ah
3.50 A
The lead accumulators are connected to the accumulator cables of the external power supply. The lead accu-
mulators are connected to the terminals “+Bat” and ”-Bat”. If two 12 V lead accumulators are present, they
must be connected in series (plus pole of one accumulator to minus pole of the other).
If external buffer accumulators are used, accumulator safeguarding must be performed by the user! For safety
reasons, the safeguarding element (overload and short circuit protection) must be arranged in close proximity
to the accumulator set itself! If lead accumulators are used, sufficient air flow must be provided according to
VDE 0510, part 2.
NOTE
Only use VdS approved lead accumulators. Never use different lead accumulator types, nor lead
accumulators of different manufacturers, nor old and new accumulators together.
CAUTION
Protect, i. e. insulate the poles when connecting lead accumulators. In case of short-circuits
there is the danger of severe burns by arcs or hot parts.
CAUTION
Hydrogen is generated during the charge of lead accumulators, forming dangerous oxyhydro-
gen. Ensure proper ventilation.
CAUTION
The lead accumulator voltage must correspond to the rated voltage of the charge rectifier! Never
confuse the polarity of lead accumulators and never short-circuit lead accumulators!
In case of non-observance there is the danger of severe burns by arcs or hot parts.
NOTE
The lead accumulators must be fixed properly.
Never install unsecured lead accumulators into the unit; danger of short-circuits!
NOTE
If the AKKUTEC is connected in parallal (Master/Slave-operation) the 24 V accumulator lines
must be connected to each other. It is not at all permissible to connect an accumulator line at the
master and the other accumulator Iine only at the slave.
A connection from the plus to the corresponding negative pole is absolutely necessary.
NOTE
Used lead accumulators must be disposed

User manual
AKKUTEC 2412 VdS
Document page 6 / 16
0812G01B02-160422.docx
3.4 Connection of mains voltage
The input voltage of the external energy supply must correspond to the mains voltage at the distribution. The
mains voltage must be disconnected and secured against unintended powering up.
The voltage-free mains cable must be connected to the mains connection terminal provided for this, taking into
account the phase. Mains connection must be performed to the terminals “L1”, “N” and PE ( ).
It is obligatory to connect to operational earth.
3.5 Connection load
When connecting the load , the polarity “+” and “-” must be considered.
If the mains voltage is disconnected, and if the minimum input voltage is fallen short of, the external energy
supply changes over to buffer operation.
NOTE
In case of overload, the DC output current is composed of the maximum charge rectifier cur-
rent and the lead accumulator current. The DC output circuit must be fused externally in order
to avoid overload!
3.6 Signal contacts
The status of the external energy supply can be forwarded to a superior central
unit via signal contacts. The relay contacts are linked to the LED’s with the same
name. Thus, the illumination of an LED effects the corresponding relay.
3.7 Circuit diagram
Connection
Terminal
Mains connection
L, N, PE
DC output(load)
+Ua, -Ua
Lead accumulator
+Bat, -
Bat
Temperature sensor
(Optional)
IO-2: 1,2
Control input
Shut-Down
IO-2: 3,4
Control input
safety monitoring
IO-2: 7
Current-share-bus (only at
connection in parallel)
IO-2: 5
Signal contact
Terminal
Mains operation
IO-1:
COM=4; NO=5; NC=6
Bat-OK
IO-1:
COM=1; NO=2; NC=3
General fault signal
IO-1:
COM=7; NO=8; NC=9
Sync
(only at parallel connection)
IO-2: 6
(The LED’s are linked tot he message contacts with the corresponding names.)
IO-1
Netz /
Mains OK 4
5
6
7
8
9
1
2
3
Bat OK
Störung /
Fault
30V DC/
0,5A
30V DC/
0,5A
30V DC/
0,5A

User manual
AKKUTEC 2412 VdS
Document page 7 / 16
0812G01B02-160422.docx
L1
N
DC/DC
Control
IO-1
Betrieb / Operation
Störung / Fault
Netz / Mains OK
Bat OK
IO-2
Current Share CS
Temp.
Sensor 1
2
3
4
5
6
7
COM1
TxD
RxD
2
3
5
RS232
µP
Ua
Control
Shut-
Down
Netz / Mains OK 4
5
6
7
8
9
1
2
3
Bat OK
Störung / Fault
Batt
+
-
+
-
-
Sync
Eingang
/ Input
(Master/Slave)
Mains
(Master/Slave)
DC-Output
Accumulator
connection
30V DC/
0,5A
30V DC/
0,5A
30V DC/
0,5A
AKKUTEC 2412 VdS

User manual
AKKUTEC 2412 VdS
Document page 8 / 16
0812G01B02-160422.docx
Fuse board
Fuse boards can be plugged in directly into the power supply or separately mounted on T-rail. Each output is
separately monitored. In case of fuse blow, the corresponding LED goes out and a general error signalizes
the fuse blow to the AKKUTEC. The AKKUTEC transmits the error if it is adjusted correspondingly.
The fuse boards are modular and expandable.
Connection
Terminal
+UA1 / -UA1 … +UA10 / -
UA10
Output terminals 1…10
Fuse F1 … F10
Ubat+ / Ubat-
Accumulator terminal
Temp
Temperature sensor
Remark: With the new generation of the fuse board (NBP21248G10001) only one type exists.
For extension however an equal fuse board is used.
Kunden-
anschluß
Netz
NPE PE
L1
+
-+
-
Kundenanschluß
Kundenanschluß
Kundenanschluß
L1
N
BE-PSU12-CF
IO-2
Betrieb / Operation
Bat OK
Störung / Fault
Netz / Mains OK
IO-1
1
2
3
4
5
6
7
8
9
Netz /
Mains OK
Bat OK
Störung
/ Fault
1
2
3
4
5
6
7
Temp
Temp
+Shut
-Shut
CS
Sync
Eingang / Input
Bat
Ua
RS232
AkkuTEC 2412
Temp
TempTemp
Sicherungs-
Überwachung
Fuse Watch
Kundenanschluß
Optionale
Erdung
Batt.-
Sicherung

User manual
AKKUTEC 2412 VdS
Document page 9 / 16
0812G01B02-160422.docx
4 Start-Up
The power supply is switched on by the activation of the mains voltage (230 V AC).
DANGER
Check the correctness of the connections prior to the first activation!
Establish electrical connections only in de-energized status!
In case of non-observance, touching live parts can result in death or serious injury.
Two seconds after connection to the mains the connected consumers are supplied. The charge of the lead
accumulators is carried out as well. The charging time is increased if simultanously to the charging current a
high load current is needed, too.
The first lead accumulator test is performed after 60 seconds.
4.1 Display and messages
Four LEDs are installed to indicate the the status of the unit:
Display
Significance
operation
LED green illuminates:
- as long as the output voltage is present.
mains-OK
LED green illuminates:
- at mains operation UE> UEmin
- and Tint < Tintmax
Bat-OK
LED green:
- illuminates:
at UBat > 21.6 V DC
- goes out:
- at UBat < 21.6 V DC
- if the accumulator circuit is interrupted (test interval 1 min)
- if the lead accumulators are reverse poled
- if the Ri accumulator internal resistance is too high (test interval 10 min.)
Error
LED yellow illuminates:
- at back-up operation
- if the accumulator circuit is interrupted
- if the lead accumulator is reverse poled
- if the accumulator internal resistance is too high
- in case of a fuse blow on the fuse board (if activated)
(The LED’s are coupled to the signal contacts which have the corresponding names.)
5 Operation
5.1 Mains operation
Mains operation is indicated with the illumination of the green LED Mains-OK and the green LED Operation.
5.2 Back-up operation
By removing the mains voltage respectively by the underrun of the minimum input voltage, the unit switches
over to back-up operation. The back-up operation is indicated with the illumination of the LED Operation. The
LED Mains-OK does not illuminate.
5.3 Deep discharge protection
Deeply discharged lead accumulators can cause irreversible damage. The final discharge voltage specified by
the manufacturer must never be underrun. In case of a mains failure, the external energy supply continuously
monitors the discharge of the lead accumulators. If the final discharge voltage is reached, the consumers are
automatically disconnected from the lead accumulators by load rejection.

User manual
AKKUTEC 2412 VdS
Document page 10 / 16
0812G01B02-160422.docx
5.4 Accumulator circuit monitoring
In order to ensure the buffer capacity of the external energy supply, the accumulator circuit is tested in cycles
of 60 seconds; the first test is performed 60 seconds after connection to the mains. This test allows the detec-
tion of a possible interruption resp. high resistivity of the accumulator circuit.
In mains operation, a defective accumulator circuit is indicated by the LED Bat-OK going out, and the illumina-
tion of the LED Error.
5.5 Accumulator test
A cyclic lead accumulator test which is performed during mains operation each 10 minutes, stresses the bat-
tery with simultaneous voltage measurement. This allows to give a statement about the internal resistance of
the accumulator.
A severely aged lead accumulator is indicated by the LED Bat-OK going out and the illumination of the
LED Error in mains operation.
NOTE
The lead accumulator test serves to detect severely aged lead accumulators. In order to be able
to make a statement about the buffering ability of the lead accumulators in the present system, a
manual check of the lead accumulators is necessary in regular intervals! (See section 7)
When the AKKUTEC 2412 VdS is delivered it is configurated for three different accumulator dimen-
sions. Herewith the limiting value for the measurement of the internal resistance is adjusted as follows:
1: 7 Ah -18 Ah 225 mΩ
2: 26 Ah -85 Ah 175 mΩ
3: >65 Ah and at Master/Slave operation 125 mΩ
NOTE
The Windows-Software paraTEC VdS is available for the configuration of AKKUTEC for special
requirements.
Special characteristics: Voltage, current, temperature monitoring, adaptation of internal re-
sistance threshold for different lead accumulator sizes, activation/deactivation for external fuse
board.
5.6 Temperature tracking (optional)
Lead accumulators have a temperature coefficient of approximately - 3 mV per °C and per cell.
For the usage without temperature sensor the final charging voltage of the external power supply is selected in
the way that charging the lead accumulators is ensured in a temperature range of 15 °C to 40 °C.
In applications with frequent and strong temperature variations, the charging voltage should be adjusted in
order to obtain maximum life duration of the lead accumulators. A temperature adjustment should be ensured
as well in particular in case of very low ambient temperatures (Tu< 15 °C) in order to ensure sufficient lead
accumulator charge. The temperature tracking is activated automatically by connecting the external tempera-
ture sensor (optional module) to terminal 1and 2of the terminal strip IO-2. Depending on the ambient temper-
ature variation of -10 to 50 °C, the deep discharge voltage (and thus, also the output voltage) varies in a range
of 28.6 V to 26.4 V DC (27.36 V at 25 °C).
A lead accumulator temperature above 45 °C is registered by the power supply and forwarded to the monitor-
ing software paraTEC. The power supply however does not monitor this condition.
NOTE
To ensure a satisfyinglife duration of the lead accumulators, the operating temperature
of the lead accumulators should not exceed 20 °C. Higher temperatures lead to a drastic
decrease of the life duration resp. service life!
NOTE
Die VdS-regulation instructs a temperature tracking. For VdS conform operation a tem-
perature sensor must be connected to the power supply!

User manual
AKKUTEC 2412 VdS
Document page 11 / 16
0812G01B02-160422.docx
5.7 Shut-Down
Buffer operation can be interrupted early in order to avoid a discharge of the lead accumulator up to the deep
discharge limit. This can be done by connecting a +24 V DC control voltage to the terminal 3(+Shut) and 4(-
Shut) of the terminal strip IO-2.
5.8 Acoustic alarm transmitter (optional)
An alarm transmitter with VdS approval is available for emitting an acoustic warning signal if a general error
occurs.
6 Master/Slave-operation at parallel connection
This operational mode is only valid in case of parallel connection of two power supplies to double the total
power rating.
6.1 Connection at Master/ Slave-operation
To increase the power rating respectively for redundant operation it is possible to connect two power supplies
in parallel.
The temperature tracking is only carried out by the Master.
Master: IO-2:1,2
The fuse monitoring is also only carried out by the Master.
Master IO-2:7 to fuse board
The Sync-connection is necessary for the functions of the accumulator test. A lack of the signal results
in a wrong measurement of the internal resistance of the accumulator.
Master IO-2:6 to Slave: IO-2:6
The CS (Current-Share-Bus) is used to share the load between both power supplies. A lack of this
signal results in the overload of the Master unit.
Master IO-2:5 to Slave IO-2:5
The signal contact mains operation is at both power supplies active. They must be connected in se-
ries, to detect a mains failure of both units.
Master IO-1:4,5,6 and Slave IO-1:4,5,6
The signal contact Bat-OK is only active at the Master
Only Master IO-1:1,2,3
The signal contact General Fault is active at both power supplies. They must be connected in series.
Master IO-1:7,8,9 and Slave IO-1:7,8,9
Kundenanschluß
Netz
L1 N PE
5 6
4PE
+
-+
-
+
-
+
-
Kundenanschluß
Kundenanschluß
Kundenanschluß
Kundenanschluß
Kundenanschluß
Kundenanschluß
Kundenanschluß
L1
N
BE-PSU12-CF
IO-2
Betrieb / Operation
Bat OK
Störung / Fault
Netz / Mains OK
IO-1
1
2
3
4
5
6
7
8
9
Netz /
Mains OK
Bat OK
Störung
/ Fault
1
2
3
4
5
6
7
Temp
Temp
+Shut
-Shut
CS
Sync
Eingang / Input
Bat
Ua
RS232
L1
N
BE-PSU12-CF
IO-2
Betrieb / Operation
Bat OK
Störung / Fault
Netz / Mains OK
IO-1
1
2
3
4
5
6
7
8
9
Netz /
Mains OK
Bat OK
Störung
/ Fault
1
2
3
4
5
6
7
Temp
Temp
+Shut
-Shut
CS
Sync
Eingang / Input
Bat
Ua
RS232
Temp
AkkuTEC 2412
AkkuTEC 2412
Te
m
p
Te
m
p
Te
m
p
Te
m
p
Kundenanschluß
Optionale
Erdung

User manual
AKKUTEC 2412 VdS
Document page 12 / 16
0812G01B02-160422.docx
6.2 Signalisation at Master/Slave-operation:
The signal contacts for mains failure of the Master and the Slave must be connected in series to detect an
error signal from both units.
At the Slave the signal and the signal contact Bat OK are not active. (neither on the contact Fault, the master
takes over this function completly). If one unit switchs off because of overvoltage at the output, it is signalized
with the signal contact Mains-OK (at Master and Slave). Afterwards the mains voltage must be switched off
for a short time. (storing protection function).
6.3 Shutdown at Master/Slave-operation
The Shutdown is carried out at the Master as described in section 3.7, the mains voltage must be switched off
before.
6.4 Configuration Master/Slave
Configuration for Master-operation:
All power supplies also the replacement devices which are delivered from the factory are preset as
Master. Complete switch cabinets with Master/Slave configuration are adjusted correctly in the factory.
If a Slave must be replaced, the replacement unit must be adjusted as Slave.
Configuration for Slave-operation:
The unit must be completely switched off. On the upper side of the unit a double dip switch can be
seen through the grid. Press the dip with the indication 2in the direction of the board. (ON). Verifica-
tion for example by the switch on of the unit outside the system. The output voltage amounts to ap-
proximately 22 V.
NOTE
During operation Master and Slave must be connected via ground at any time (Ua- or Bat-). A
separation of the wiring during operation is not allowed.
A lack of the signal Sync results in wrong measurement of the internal resistance of the accumu-
lator, the LED Fault illuminates herewith at the Slave.
A lack of the signal CS results in the overload of the Master, then the Slave only supplies ap-
proximately 22 V.
All load and all accumulator lines must be connected in parallel each with and connected with
separate lines at both AKKUTEC-units.

User manual
AKKUTEC 2412 VdS
Document page 13 / 16
0812G01B02-160422.docx
7 Servicing
In order to ensure the buffering ability of the power supply, the lead accumulators should be tested for their
buffering capability in regular intervals of 3 to 6 months.
The housing must be cleaned at least once per year depending on the degree of contamination.
7.1 Testing the lead accumulators
Start a forced buffer operation by disconnecting the mains. The lead accumulators must keep the required
autonomy time under nominal conditions. When the deep charge limit is reached, the external energy supply
switches off automatically.
7.2 Exchanging the lead accumulators
If not stated otherwise in the VdS approval certification, the lead accumulators must be exchanged once every
four years after the manufacturing date. Removal and installation of the lead accumulators may only be per-
formed by qualified personnel.
It must be performed as follows:
Removal of lead accumulators:
Perform the putting out of operation as decribed in section Fehler! Verweisquelle konnte nicht ge-
funden werden.
Remove electrical connections from the lead accumulators (2-Pol CombiCon, Ubat)
Loosen the accumulator bracket, retain lead accumulator at the same time.
Remove lead accumulators
Installation of lead accumulators:
The installation is performed as described above only in reverse order.
Take care to ensure correct polarity. In case of a reverse polarity of the lead accumulator, the func-
tions “lead accumulator charge” and “Accumulator release during mains failure” remain blocked, the
simultaneous illumination of the LED-Mains-OK and the LED-Error will indicate the reverse polarity.
CAUTION
Take care to ensure the correct nominal voltage and the correct polarity when installing the lead
accumulators.
In case of non-observance there is the danger of severe burns by arcs.
CAUTION
Protect, i. e. insulate the poles when connecting lead accumulators. In case of short-circuits
there is the danger of severe burns by arcs or hot parts.
NOTE
Ensure the correct fixing of the lead accumulators after re-installation!
NOTE
Only use VdS approved lead accumulators. Never use different lead accumulator types, nor lead
accumulators of different manufacturers, nor old and new accumulators together.

User manual
AKKUTEC 2412 VdS
Document page 14 / 16
0812G01B02-160422.docx
8 Decommissioning
The decommissioning is performed by the removing of the mains voltage. In order to avoid subsequent buffer-
ing, the accumulator must be interrupted by activating the Shut-Down-signal or by removing the accumulator
fuse.
The LED Mains-OK and the Error must go out in this case.
NOTE
During operation the disconnection or connection of electrical connections is not allowed! In case
of non-observance danger of arcs, which may lead to severe burns!
9 Disposal
This symbol indicates, that the product must not be disposed with normal house waste. Please
dispose it professionally as electronic scrap. So the materials are separated and recycled ac-
cording to their characteristics. This is a big contribution to protecting the environment.
NOTE
Used lead accumulators must be disposed of properly!
10 Norms and regulations
Power supplies for fire alarm systems are subject to rigorous regulations; the power supply unit of the fire
alarm system is tested according to the European Product Standards EN 54-4 and VdS 2541. The power sup-
ply is VdS approved and is listed under No.: G209169.
EMV
EN 55011, limit value class B
EN 62040-2, limit value class C1
EN 61000-6-2
EN 61000-6-4
EN 50130-4+A1+A2
Overall unit
2014/30/EU+A1+A2
EN 50178
EN 54-4+A1+A2
EN 12101-10+B1
VdS 2541
VdS 2344
Optocoupler for guaranteeing a safe primary /
secondary separation
EN 60747-5-1, fulfills SELV / PELV
Power HF-transmitter to ensure the safe separa-
tion of primary and secondary.
EN 61558 2-16, fulfills SELV / PELV

User manual
AKKUTEC 2412 VdS
Document page 15 / 16
0812G01B02-160422.docx
11 Technical Data
Nominal input voltage
230 V AC (±15%)
Input voltage range for charging operation
195.5 V … 264.5 V
Nominal frequency
47 Hz … 63 Hz
Power consumption
380 VA
Self current consumption
75 mA @ 24 V
Max. nominal input current
1.8 A
Max. inrush current
35 A / 2 ms
Max. nominal output current
12 A
Nominal output voltage (in mains operation)
24 V DC
Output voltage range (with temperature tracking)
26.4 V … 28.6 V DC ±0.4%
Charging characteristics
I/U DIN41773
Charging end voltage (without Temp.-Sensor)
26.4VDC ±0.4%
Deep discharge protection and load shedding
20.4VDC ±0.4%
Max power loss ‚worst-case‘
40 W
Efficiency
89% @ (Ue=230 V;Ua=26.4 V DC; Ia=INenn)
Voltage ripple
< 150 mV eff.
Internal device protection
2.5 A (T), 250 V
Fuse DC-output circuit (external)
15 A (T, UL-248)
Fuse DC-Battery circuit (external)
15 A (T, UL-248)
Connection in parallel
Yes
Connection in series
Yes
Max. signal contact load (Mains-OK1)
30 V/ 0.5 A
potential-free relay-contact
Max. signal contact load (Bat-OK1)
30 V/ 0.5 A
potential-free relay-contact
Max. signal contact load (General Fault1)
30 V/ 0.5 A
potentialfreier Relais-Kontakt
Max. signal voltage range (Shut-Down)
24 V DC (6-45 V DC)
floating switching input
Accumulator type
Pb-accumulator, maintenance-free, max. 170 Ah
Back-up time
Accumulator specific
Protective system
IP20
Operating temperature
-10 °C … 50 °C
Storage temperature
-10 °C … 50 °C
Rel. Humidity
≤95% no condensation
Max. installation altitude
2000 m above sea level
Dimensions (HxWxD)
155 mm, 95 mm, 183 mm
Weight
1.5 Kg

User manual
AKKUTEC 2412 VdS
Document page 16 / 16
0812G01B02-160422.docx
12 Accessories
In application cases with frequent and strong temperature variations, the charging voltage should be adjusted
in order to avoid accumulator overload (danger of gassing!). In the same way, a temperature adjustment
should be ensured in particular in case of very low ambient temperatures (Tu < 15 °C) in order to ensure suffi-
cient accumulator charge.
Temperature sensor MTIAQ33G3M01
Temperature sensor MTIAQ33G3M04
Temperature sensor MTIAQ33G3M05
Every fuse output is monitored separately. If a fuse blows, the corresponding LED goes out. A blown fuse is
notified to the AkkuTEC or the PLS with collective massage.
Fuse board NBP1248G10001
Decoupling diode set including a double Schottky diode on a potential-free cooler wiht cover against direct
touch and top hat rail clamb.
KGEK002S003M45
KGEK002S003M92
For fire alarm systems, the power supply can be equipped with an additional signal generator.
Signal generator PA100
Software for PC-aided monitoring and parametrization functions
Windows .NET Framework Software paraTEC VdS
This manual suits for next models
1
Table of contents