Jakka Pro User manual

KEYPAD AND PANEL DESCRIPTIONS
1. ON—OFF OPERATIONS
Use the key to Opening/Closing operaons.
When pressing the buon once, the device will switch
on or o.
3. SETPOINT SETTING
Use the ▲ and ▼ keys
to adjust the setpoint. If
the keys are pressed
one me, setpoint will
be changed 1 °C. Use
the ▲ key to increase
the setpoint, use the ▼
key to decrease the set-
point. Seng range 5 °
C—30 °C.
O Posion On Posion
2. OPERATION MODE SETTINGS
While the device is in the On Posion, operaon mo-
de can be changed with key.
Note: The acve mode icon ashes on the panel.
Heang or Cooling Mode Venlaon Mode
4. MONITORING DIFFERENT TEMPERATURES
Setpoint Seng
On/O Key
Mode Key
Fan Key
▲ ▼ Increment/Decrement Key
WARNING !!
Parts that need to be considered in the screen shots are
taken into the circle. Please noce the screenshots.
The sensor values, which is measured by main control-
ler, are displayed alternately on the panel. In this appli-
caon “Room Temperature, Supply Air Temperature,
Outdoor Air Temperature, Exhaust Air Temperature”
sensors can be measured by main controller.
Note 1: If Room Temperature Sensor is not connected to
main controller, Temperature Sensor value of the panel is
measured.
Note 2: Supply Air Temperature and Room Temperature
value are measured by same input. If user wants to get the
Supply Air Temperature value, ChangeReturntoSupply para-
meter ( Service Menu 11. parameter, BMS 344. parameter )
must be set to “1”. Aer doing this changing, room tempe-
rature value is measured by panel.
Note 3: If Outdoor Air Temperature Sensor is connected and
necessary sengs are made, electrical heater is controlled
by the Outdoor Air Temperature. Electrical Heater control is
performed by the Return Air Temperature sensor value by
default.
Heating Electrical Heater Stages
Room Tmp
Setpoint
Home İcon
Supply Air Fan Speed
Auto-5-4-3-2-1Exhaust Air Fan Speed
1-2-3-4-5-Auto
Air Quality
Sup. Air Tmp
Cooling Ventilation
Out. Air Tmp
Alarm Notification
Auxiliary Digits
Days
Auto
Main Digits
Keylock
Exh. Air Tmp
MANUAL for JAKKA PRO CONTROLLER

Supply Air Temperature
Room Temperature
Exhaust Air Temperature
Outdoor Air Temperature
5. FAN SPEED SETTINGS
Fan speed can be set to one of 1-2-3-4-5-Auto values.
Supply Air Fan Speed Seng :
When pressing the FAN key once, Supply Air Fan icon
ashes on the panel. While icon ashing, fan
speed can be changed by ▲ and ▼ key.
Exhaust Air Fan Speed Seng :
When pressing the FAN key twice, Exhaust Air Fan
icon ashes on the panel. While icon ashing,
fan speed can be changed by ▲ and ▼ key.
Note: When one of the heang or cooling mode is selected,
automac fan speed is acvated. If the automac fan
speed is selected, fans operates according to the “Air Qua-
lity or Carbon Dioxide Sensor” value. If sensor is not con-
nected, fan speed is decreased to a minimum value.
Supply Speed Seng Exhaust Speed Seng
6. FAN LOGIC SETTING
While the device is in the On posion, if pressing FAN
key for 5 seconds, fan logic is changed.
Connious Fan : Displayed as
“Cont” on the panel. Fans will
work as long as the device is in
the On posion. ( Default )
Auto Fan : Displayed as “Auto”
on the panel. Fans will be acve
while heang or cooling. In other
cases the fan output is closed.
7. CLOCK SETTINGS
When pressing the MODE key for 6-7 seconds, hour
digit ashes on the panel. While digit ashing, hour
can be changed by ▲ and ▼ key.
MODE key is pressed once again, minute digit ashes
on the panel. While digit ashing, minute can be chan-
ged by ▲ and ▼ key.
Hour Seng Minute Seng
8. SCHEDULE OPERATIONS
Aer seng minutes, to enter the schdule menu, press
the MODE key one mes.
While in the "On" or "OF" menu, hour can be changed
by ▲ and ▼ key.
1. Press MODE key to enter the "On" menu. Hour can
be changed by ▲ and ▼ key. "On" menu shows the
opening day and time.
2. Press MODE key to enter the "OF" menu. Hour can
be changed by ▲ and ▼ key. "OF" menu shows the
closing day and time.
Press MODE key (one or more mes) to select the
schedule day.
MANUAL for JAKKA PRO CONTROLLER

"On" Menu "OF" Menu
9. ALARMS
All outputs are closed
except Status Out and By-
pass Damper O. The Pa-
nel locked. Contact must
be in the closed posion to
eliminate the alarm.
9.1 AL:01 FAN CONTACT ALARM (NC)
Fans run at maximum
speed during alarm. The
Panel locked. The device
resumes normal operaon.
Contact must be in the
opened posion to elimi-
nate the alarm.
9.2 AL:02 HUMIDITY SENS. CONTACT ALARM (NO)
If contact is in the closed
posion or when device
worked up to the AirFilter-
TimerLimit, alarm hap-
pens. Device is connuing
normal operaon during
alarm.
If the Alarm number is 04
(AL:04) and the air lter alarm is caused by AirFilterTi-
merAlarm, the related parameter (BMS 331., Service
Menu 8. parameter) must be set to 0 to reset the
alarm.
9.4 AL:04 AIR FILTER ALARM (NO)
If contact is in the opened
posion, alarm happens.
Electrical heater outputs
are closed. Fans run at
maximum speed. The Pa-
nel locked. Contact must
be in the closed posion to
eliminate the alarm.
9.5 AL:05 ELEC. HEATER OVER HEAT ALARM (NC)
If Outdoor Air Temperatu-
re < -8 and Exhaust Air
Temperature <= 2 alarm
happens.
Electrical Heater 1. stage
opens during alarm.
When Exhaust Air Tempe-
rature > 2 and me passed
up to the OutdoorTempFrostOutTimerLimit (BMS 331.
parameter), alarm is eliminang.
9.6 AL:06 OUTDOOR TEMP. SEN. FROST ALARM
9.3 AL:03 FIRE CONTACT ALARM (NO)
If contact is in the closed
posion or Room Tempe-
rature > SetFireA-
larmTemp (BMS 343.,
Service Menu 44. para-
meter), alarm happens.
Supply air fan is closed, Exhaust air fan runs at maxi-
mum speed. All outputs are closed except Status Out
and Entrance Damper. The Panel locked. Eliminang
the alarm and disconnect the power of the device to
return to normal operaon.
Note 1: Aer the device restarted, press together MODE and
▲ buon unl unlock the device.
Note 2: SetFireAlarmTemp parameter default value: 50 °C
7. ÖZEL KONTROL FONKSİYONLARI
7.1 HAVA KALİTESİ VEYA CO2 KONTROLÜ
0-10V air quality or CO2
sensor must be connected
properly. Operaon mode
must be set to other than
venlaon (heang or
cooling) and fan speed
must be set to Auto.
When these condions are met, the fan speed is cont-
rolled according to the air quality or CO2 sensor value.
10. SPECIAL CONTROL FUNCTIONS
10.1 AIR QUALITY OR CO2 CONTROL
MANUAL for JAKKA PRO CONTROLLER

10.5 REMOTE CONTROL
The remote On/O funcon. This contact can be used
to control the device via building automaon/PLC/
External Switches.
To use this feature, selected scenario must be contain
remote control contact.
10.2 ELECTRICAL HEATER CONTROL
1. Controlled Depending on Room Temperature :
Electrical heater is controlled by sensor on the panel or
return air temperature sensor. Control is acve without
any adjustment. ( Default Control Type )
2. Controlled Depending on Outdoor Temperature: If
outdoor temperature value less than value set in the
service menu, the heater stages is acvated.
Note: Control according to the outdoor air temperatu-
re to be acve, parameter sengs must be made of
appropriate. (See. Service Menu Operaons)
10.4 ENTRANCE DAMPER CONTROL
Fresh air and/or exhaust air damper motors are cont-
rolled. Damper motor is controlled considering the ne-
cessary delays ( The device On/O moments, alarm
moments... ).
10.3 BYPASS DAMPER CONTROL
The working condions of the bypass damper is as fol-
low;
Fan Mode;
Bypass damper is always closed.
Heang Mode;
1. Outdoor Air Temp. < Room Temp. + 3 and
Setpoint < Room Temp. + 2 and
Outdoor Air Temp. > 15 °C
damper is open,
2. Outdoor Air Temp. > Room Temp. - 3 and
Setpoint > Room Temp. - 2 and
Outdoor Air Temp. < 35 °C
damper is open, closed in the other condions
Cooling Mode;
1. Outdoor Air Temp. > Room Temp. + 3 and
Setpoint > Room Temp. - 2 and
Outdoor Air Temp. < 32 °C
damper is open,
2. Outdoor Air Temp. < Room Temp. - 3 and
Setpoint < Room Temp. - 2 and
Outdoor Air Temp. > 10 °C
damper is open, closed in the other condions
11. SERVICE MENU OPERATIONS
11.1 MENU DESCRIPTION
While the device is in the O Posion, press together
MODE and ▼ key for 5 seconds.
In the service menu “Main Parameter” is replaced by
the MODE and FAN keys.
“Auxiliary Parameter” is replaced by the ▲ and ▼
keys.
Main Parameter Auxiliary Parameter
11.2 PASSWORD PARAMETER
While the device is in the O Posion, press together
MODE and ▼ key for 5 seconds.
To make changes in the parameters, password must be
entered as “137”, to 99.
parameter.
Firstly, “Main Parameter”
must be replaced as 99, by
the MODE and FAN keys.
Secondly, “Auxiliary Para-
meter” must be replaced as
137, by the ▲ and ▼ keys.
Otherwise, made changes won’ t be saved.
Note: This process is part of the entry to the Service
Menu and must be applied in all entries.
MANUAL for JAKKA PRO CONTROLLER
One relay output reserved into for damper. If there are
more damper motor, must be connected in parallel.
Note : Damper motor must be in the On/O and
spring return property.

7. ÖZEL KONTROL FONKSİYONLARI
11.4 SETPOINT LIMIT OPERATIONS
Minimum Limit: Firstly,
“Main Parameter” must be
replaced as 2, by the MODE
and FAN keys.
Secondly, “Auxiliary Para-
meter” can be selected in
the range of 5-35 °C, by the
▲ and ▼ keys. (Default
value: 05 °C)
Maximum Limit:
Firstly, “Main Parameter”
must be replaced as 3, by
the MODE and FAN keys.
Secondly, “Auxiliary Para-
meter” can be selected in
the range of 5-35 °C, by the ▲ and ▼ keys.
(Default value : 30 °C)
Note 1: Minimum Limit can not be greater than maxi-
mum limit.
Note 2: Maximum Limit can not be lower than mini-
mum limit.
11.3 BMS ADDRESS SETTING
After logging into the servi-
ce menu, using the MODE
and FAN keys, select the 00.
parameter.
Use the ▲ key to increase
the address, use the ▼ key
to decrease the address.
Seng range 0-247.
11.5 ELECTRICAL HEATER CONTROL SETTINGS
Electrical heater can be controlled according to the
two dierent temperature value.
01 : Controlled Depending on Room Temperature :
Electrical heater is controlled by the sensor on the pa-
nel or return air temperature sensor. Control is acve
without any adjustment. ( Default )
02 : Controlled Depending on Outdoor Temperature:
Electrical heater is controlled according to the
“Outdoor Air Temperature Sensor” connected on the
main controller. Enter the service menu to acvate the
control according to the outdoor air temperature.
Outdoor Control Acvate:
Firstly, “Main Parameter”
must be replaced as “9”, by
the MODE and FAN keys.
Secondly, “Auxiliary Para-
meter” must be replaced as
“2”, by the ▲ and ▼ keys.
11.6 DATE SETTINGS
1. Firstly, “Main Parameter”
must be replaced as 12, by
the MODE and FAN keys.
Secondly, “Auxiliary Para-
meter” must be set to the
desired day value.
2. Firstly, “Main Parameter”
must be replaced as 13, by
the MODE and FAN keys.
Secondly, “Auxiliary Para-
meter” must be set to the
desired month value.
3. Firstly, “Main Parameter”
must be replaced as 14, by
the MODE and FAN keys.
Secondly, “Auxiliary Para-
meter” must be set to the
desired year value.
Note: When the specied steps are correctly completed,
device will choose day of week correctly.
Setpoint Seng:
Firstly, “Main Parameter”
must be replaced as “10”,
by the MODE and FAN
keys.
Secondly, “Auxiliary Para-
meter” must be selected in
the range of 0-20 °C, by the ▲
and ▼ keys.
(Default value : 15 °C)
Note: If outdoor air temperature value lower than
value set in the service menu, the heater stages is
acvated.
Set
Control Activate
This parameter used to correct changes made by mista-
ke.
Firstly, “Main Parameter”
must be replaced as 15, by
the MODE and FAN keys.
Secondly, “Auxiliary Para-
meter” must be replaced as
1, by the ▲ and ▼ keys.
When the device returned factory defaults, parameter
value is set to "0" automacally. (Default value = 0)
11.7 FACTORY DEFAULT
MANUAL for JAKKA PRO CONTROLLER

1) Use standart juncon box.
Hole distance must be 60mm
center to center.
Use 68mm hole saw.
2) Remove the
front panel
using a thin-
blade at
screwdriver.
3) Secure the
rear panel by
screwing screws.
Necessary
screws are in the
box.
4) Make the
cable connec-
ons as shown
below to termi-
nals on the front
panel.
5) Aach the clip
at the top rst,
and then aach
the clip at the
boom.
13. CONTROL PANEL CABLE CONNECTIONS
(2 x 2 x 0,34...0,75mm²)
Shielded, Twisted Pair, RS485 Data Com-
municaon Cable must be used.
Note : Press the terminal buons with
the help of a ne-pped pen as shown
in the gure. Don't apply extreme
pressure.
NOTE: DON’T USE THE SCREWDRIVER
12. MOUNTING INFORMATION
MANUAL for JAKKA PRO CONTROLLER
Table of contents
Other Jakka Controllers manuals
Popular Controllers manuals by other brands

Advantage Controls
Advantage Controls MegaTron Series Technical manual installation maintenance

high pointe
high pointe RocketRAID 2840A user guide

THORLABS
THORLABS PCS-6000 Series user guide

Siemens
Siemens SIMOVERT MASTERDRIVES MC Series Product information

Atlantic
Atlantic TWVSC-73933 product manual

Graco
Graco LineLazer 25A493 quick start guide