4. Product description
The device is:
• intended for measurement in building
installations, on distribution units, circuit
breakers and busbar trunking systems.
• suitable for installation in fixed
and weatherproof switchboards.
• usable in 2, 3 and 4-conductor networks
and in TN and TT networks.
• provided with external ../1 A or ../5 A
current transformers for current
measurement.
• only suitable for measurements in medium
and high-voltage networks via current and
voltage transformers.
• suitable for use in residential and industrial
applications.
• suitable for residual current monitoring
(RCM) via external residual current
transformers with a rated current of 30 mA.
• suitable for measuring measured voltages
and measured currents that derive from
the same network.
The measurement results can be displayed,
saved, read out and further processed
via the device's interfaces.
4. 1 Measuring process
The device:
• measures continuously and calculates
all effective values over a 200 ms interval.
• measures the real effective value (TRMS)
of the voltages and currents connected
to the measurement inputs.
4. 2 Usage concept
You can program and call up the measured
values via many routes using the device:
• directly on the device via 6 buttons
and the display.
• using the GridVis® programming
software.
• using the device homepage.
• using the Modbus protocol. You
can modify and call up the data using
the Modbus address list. The list can
be called up from www.janitza.de.
This operation manual only describes how
to operate the device using the 6 buttons.
The GridVis® network analysis software
has its own "online help".
4. 3 GridVis® network analysis software
You can use the GridVis® network analysis
software that is available at www.janitza.
de to program the device and read out
data. To do this, a PC must be connected
to the device via a serial interface (RS485/
Ethernet).
You can use the GridVis® network analysis
software to:
• program the device.
• configure and read out recordings.
• analyse the read out data according
to EN 61000-2-4.
• save the data to a database.
• display measured values graphically.
• program customer-specific applications.
cc
CAUTION!
Malfunctions due
to incorrect connection
If the device is connected incorrectly,
incorrect measured values may be returned.
Therefore, note the following:
• Measured voltages and measured
currents must derive from the same
network.
• Do not use the device to measure
DC current.
• Earth active switchboards.
cc
CAUTION!
Risk of injury due
to electric voltage
Residual current monitoring monitors residual
currents via external current transformers
and can trigger a warning impulse
when a threshold value is exceeded.
The device is therefore
not anindependent protective device
against electric shocks.