Jedia JEU-211AU User manual

WWW.JEDIA.COM
EMERGENCY UNIT
JEU-211AU

AUTION AVIS
FEATURES
SAFETY INSTRUCTIONS
RONT PANEL CONTROLS
EAR PANEL CONTROLS
C
F
R
1
1
1
2
3
4~6
MERGENCY MESSAGE CARD (선택사양)
E
FIRE!!
EMERGENCY UNIT JEU-211A
DYNAMIC Micro phone
DM-A 500
KUN HYUNG ELECTRONIC CO.,LTD.
8
9
7
YSTEM CONNECTIONS(시스템 연결 방법)
S
PECIFICATIONS
S
LOCK DIAGRAM
B
OFF ON
LEVELFAULT
LEAK 10
BUZZERBUZZER MIC

SAFETY INSTRUCTIONS
FEATURES
Read all safety instruction before operating the JEU-211AU.
1. Install equipment as follow conditions.
AUTO ALERT(ALARM) OF FIRE
The apparatus shall not be exposed to dripping or splashing and
no object filled with liquids, such as vases, shall be place on the
apparatus.
Install at the place, not bending curved.
Do not install this apparatus in a confined space such as a book
case or similar unit.
Locate this apparatus away from heat source, such as radiators
or other device that produce heat.
Do not drop objects or spill liquids into the inside of the apparatus.
2. Keep in mind the following when connecting the apparatus.
Connect the apparatus after reading of O/P manuals.
Connect each connection of amplifier perfectly, if not, it maybe
Caused hum, damage, electric shock in case of mis-connecting.
To prevent electric shock, do not open top cover.
Connect the power cord with safety after check of AC power.
This apparatus should be serviced by qualified service person.
안 전 사 항
특징
제품을 운용하기전에 모든 안전사항을 읽어 보십시오.
1. 이런 장소에 설치하여 주십시오.
화재 발생시 자동경보
진동이나 경사가 심하지 않고 바닥이 평평한 장소.
통풍이 잘되고 물기나 습기가 많지 않은 장소.
직사광선을 받지 않는 장소 또는 난방기구(발열체)에서 멀리 떨어진
장소.
인화성 물질(화학약품)이 없는 장소.
2. 설치시 이런점을 주의하십시오.
사용설명서 시스템 연결방법을 완전히 읽으신 후에 연결해 주십시오.
각종 연결선을 완전하게 연결해 주십시오.
(주전원 코드를 뽑은 상태에서 연결.)
불완전한 연결은 잡음, 제품의 손상 또는 안전사고의 원인이 됩니다.
전기적 충격 또는 감전사고의 위험이 있으므로 뚜껑을 열지 말아주십
시오.
주 교류 전원 플러그를 연결하기 전에 사용전압을 확인하신 후 안전
하게 연결하십시오.
제품을 수리시는 규정된 부품과 자격이 있는 사람이 수리를 하여야 함.
1
화재 자동 경보기와 연결하여 화재가 발생하면 자동으로 경보를 울려
주며, 화재표시 LED가 점멸하게 됩니다.
점검 및 시험운용 기능
JES-120AU, JES-120A와 연결한 후 JES-120AU, JES-120A의
스위치를 선택하면 점검 및 시험운용을 할 수 있습니다.
무인 자동방송 기능(선택사양)
E/M MESSAGE CARD를 장착하면 화재 발생시 초기에 사이렌이 방송
되고 일정시간(약10초)이 지나면 E/M MESSAGE가 무한 방송됩니다.
또한 E/M MESSAGE CARD를 장착하지 않으면 자동으로 사이렌이 계
속 방송됩니다.
It should be connected with 'five auto alam' and if fire broke out,
automatically alarming and flashing of fire indicator.
OPERATING & INSPECTION
Connect with JES-120AU, JES-120A and select S/W of
JES-120AU, JES-120A to check of this unit.
AUTO ANNOUNCEMENT WITHOUT PERSON(OPTION)
Firstly, siren ringing for 10sec and E/M message is followed
continuously by E/M message card(option).
Without E/M message card : Only siren
The apparatus shall not be exposed to dripping or splashig
and no object filled with liquids, such as vases, shall be
place on the apparatus
이 기계(장치)는 물기에 접촉(물에 적시는 정도의 접촉)해서는 안되며
꽃병과 같은 액체가 담겨진 물체를 기계 가까이 두는것을 금지하여야
합니다.
본 장비는 유럽 소방안전 규격인 EN 60849의 규정에 준하여 본장비의
주요기능을 검출하여 이상발생시 본사의 JCU-160장비에 알려주어
장비의 이상 유무 상태를 유지 관리 할 수 있는 기능을 가지고 있다.
유럽 소방안전 규격 EN60849적용
Compliance with IEC 60849
This equipment is designed for compliance with IEC 60849 standard.
So this equipment has a function to report major features of this
equipment to JCU-160.
Therefore when there is something wrong of major features of this
equipment, it can be checked by JCU-160

FRONT PANEL CONTROLS (전면기능)
2
1. 화재 표시 LED
1. FIRE LED
When fire break out, fire LED will be flashing.
2. BUZZER ON/OFF SWITCH
You can monitor situations microphone faults by buzzer sound like short,
disconnection of mic cable, microphone unit fault, connector fault.
If buzzer ON/OFF switch is off position, buzzer does not make warning
sound. So, strongly recommand to always switch"on".
3. FAULT LED
Fault LED will be flashing in case of cable disconnection, short, microphone
unit fault, connector fault.
4. MIC VOLUME CONTROL
Increases volume to the clockwise and decrease volume to the
clockotherwise. Volume level will be kept on even volume control is
decreased completely to the clockotherwise.
5. MICROPHONE & CONNECTOR
Microphone is unidirectional dynamic microphone.
Push the switch in the side when you use it.
If unplug connector or microphone fault, buzzer will make warning
sound with LED flashing.
화재가 발생시 화재를 표시하는 LED로서 점멸하게 됩니다.
2. 부저 ON/OFF 스위치
마이크 결함(케이블 단선, 쇼트, 마이크 유니트 고장, 콘넥터 접촉불량
등)이 발생할 경우에 부저가 울리게 됩니다.
스위치를 "OFF"로 할 경우에는 마이크 결함이 발생하여도 부저가 울리지
않게 됩니다. 항상 "ON" 위치로 놓고 사용하십시오.
3. FAULT LED
마이크 결함(케이블 단선, 쇼트, 마이크 유니트 고장, 콘넥터 접촉불량
등)이 발생할 경우에 LED가 깜박입니다.
4. 마이크 음량 조절
마이크 음량을 조절하는 볼륨으로 시계 방향으로 돌리면 음량이 증가
하며, 반대 방향으로 돌리면 음량이 감소합니다.
볼륨을 반 시계 방향으로 끝까지 돌리더라도 일정레벨이 출력됩니다.
5. 마이크 및 연결 콘넥터
단일 지향성 다이나믹 마이크 입니다.
사용하고자 할 때는 측면의 스위치를 누르고 방송하면 됩니다.
콘넥터가 연결되지 않았거나 마이크에 결함이 발생하였을 때 부저가
울리고, LED가 깜박이게 됩니다.
BUZZER MIC
EMERGENCY UNIT JEU-211AU
OFF ON
FIRE!!
LEVELFAULT
LEAK 10
1
4
2
35
DYNAMIC
Micro phone
DM-A 500
KUN HYUNG ELECTRONIC CO.,LTD.

3
1. 전원 입력 및 E/M ALL IN 단자
이 단자는 JES-120AU, JES-120A의 TO JEU-211AU콘넥터와 연결하십시오.
2. 사이렌 음량조절
사이렌 신호의 크기를 조절하는 볼륨입니다.
4. BLANK PANEL
E/M MESSAGE CARD를 미장착시, 사용하는 BLANK PANEL 입니다.
5. E/M MESSAGE 음량조절 (선택사양)
E/M MESSAGE의 음량을 조절하는 볼륨입니다.
적당한 레벨로 조절하십히오.
6. E/M MESSAGE CARD (선택사양)
화재 발생시 무인 자동 방송을 하기 위한 E/M MESSAGE CARD로서
RECORDING TIME은 16입니다.
이 카드를 장착하면, 화재가 발생하여 항목1의 E/M ALL IN 단자에 +5V가
인가되고, 초기에 사이렌 경보가 방송되고 일정시간(약 10SEC)이 지나면
E/M MESSAGE CARD의 ROM에 저장된 메세지가 자동으로 무한 방송됩니
다. 또한, E/M MESSAGE CARD를 장착하지 않으면 자동으로 사이렌 경보
음이 계속 방송됩니다.
3. 오디오 출력단자
오디오 출력단자로서 바란스 타입입니다. JRG-220AU, JRG-220A의
EMERGENCY CARD의 E/M AUDIO IN 단자와 연결하십시오.
1. POWER INPUT & E/M IN CONNECTOR
This connector should be connected with JES-120AU.
REAR PANEL CONTROLS (후면기능)
DC24V power input connector. Check polarity(+,-) before use.
24VDC POWER
If you select the S/W of JES-120AU, JES-120A or when fire breaks
out, JEU-211AU is operated.
E/M ALL IN
직류 24V전원 입력 단자입니다. +, - 극성에 주의하여 연결하십시오.
24DC POWER
JES-120AU, JES-120A의 스위치를 선택하거나 화재 발생시 +5가
인가되면 JEU-211AU가 동작하게 됩니다.
E/M ALL IN
Standard -16SEC.
RECORDING TIME
①. Fire broke out.
②. +5V permission in E/M all in connector.
③. Siren ringing.(about 10sec)
④. E/M message is followed continuously.
(By memoried ROM IC of E/M message card)
SITUATION FLOW
This is volume for siren, check and adjust volume.
2. LEVEL CONTROL OF SIREN
This is output connector of valance type.
This is connector should be connected with E/M audio in of E/M card.
(JRG-220AU, JRG-220A)
3. E/M AUDIOOUTPUT CONNECTOR
This is for mounting without E/M message card.
4. BLANK PANEL
This is volume control for E/M message.
Check and adjust volume.
5. E/M MESSAGE VOLUME CONTROL (OPTION)
This card is for auto-announcement without person.
6. E/M MESSAGE CARD (OPTION)
7. 주요기능 상태출력 단자
본장비의 주요기능을 검출하여 본사의 JCU-160의 입력단자에
연결하는 출력단자입니다.
JCU-160입력단자와 연결시 JCU-160의 CHECK SIGNAL 선택스위치를
출력펄스와 같게 설정하여 주십시요.
(CHECK SIGNAL선택스위치 설정 방법은 JCU-160메뉴얼 참조.)
1
2
EMERGENCY MESSAGE CARD
LEAK 10
5
6
3
LEVEL
LEAK 10
MODEL.: JEU-211AU
EMERGENCY UNIT
MADE IN KOREA
CAUTION
RISK OF ELECTRIC SHOCK
DO NOT OPEN
WARNING:
TO REDUCE THE RISK OF FIRE
OR ELECTRIC SHOCK DON'T EXPOSE THIS
EQUIPMENT TO RAIN OR MOISTURE.
FROM
JES-120A
BAL
1.23V 600
SERIAL NO.:
E/M ALL IN
24V
GND IN
E/M AUDIO
OUTPUT SIREN
FAULT CHECK
(NON PULSE)
FIRE CHECK
(NON PULSE)
7
7. OUT TERMINAL FOR THE STATUS OF MAJOR FEATURE
This is output terminal to be connected with input terminal of JCU-160
in order to report the status of major features of equipment it self.
when connecting to JCU-160, please set "check signal" switch of
JCU-160 to be matched with output pulse of this equipment.
( Please refer to the setting method of check signal switch in the
operating manual of JCU-160)

4
1. BLANK PANEL의 SCREW를 풀고 BLANK PANEL를 떼어낸다.
1. Detach the blank panel of rear.
INSTALLATION OF E/M MESSAGE CARD
2. Insert at CN2, with 5P CON ASS'Y.
3. Insert the E/M MESSAGE CARD into rear.
2. 5P CON ASS'Y를 CN2에 삽입한다.
3. E/M MESSAGE CARD를 BLANK에 삽입하고 SCREW로 고정한다.
EMERGENCY MESSAGE CARD
LEAK 10
U4
CN2
LEVEL
LEAK 10
MODEL.: JEU-211AU
EMERGENCY UNIT
MADE IN KOREA
RISK OF ELECTRIC SHOCK
DO NOT OPEN
WARNING:
TO REDUCE THE RISK OF FIRE
OR ELECTRIC SHOCK DON'T EXPOSE THIS
EQUIPMENT TO RAIN OR MOISTURE.
FROM
JES-120A
BAL
1.23V 600
SERIAL NO.:
E/M ALL IN
24V
GND IN
E/M AUDIO
OUTPUT SIREN
FAULT CHECK
(NON PULSE)
FIRE CHECK
(NON PULSE)
CAUTION

APPEARANCE (외관)
NOMENCLATURE (각부명칭)
①MIC/LINE Input Jack.
②MIC/LINE Selection Switch.
③Recording Input Level Volume.
④Signal Indicator.
⑤Clip Indicator.
⑥H.P and Output Level Volume.
⑦Headphone Output Jack.
⑧Connector For Connect JEU-211AU.
⑨PLAY/REC Selection Switch.
⑩Auto/Manual Selection Switch.
⑪STOP Button.
⑫START Button.
⑬Operating Indicator.
OPERATING
1. HOW TO RECORDING
LEAKLEVEL
EMERGENCY MESSAGE
10
MIC/LINE
START
OPERATING
CLIP
SIG VR1
REC
VR2
LEVEL
MIC/LINE
AUTO/MANUAL PLAY/RECSTOP
CN2
CONTROL
AUDIO
E/M IN
GND
+24V
H.P
COMPONENT SIDE VIEW
FRONT VIEW
6
1
7
8
3
245
10111213
FEATURES
1. Easy-to-use single-chip voice record/playback solution.
2. High-quality, natural voice/audio reproduction..
3. Operation of manual switches.
4. Recording time of 60-second.
5. Zero-power message storage (No backup battery).
6. 100-year message retention (typical).
7. 100,000 record cycles (typical).
1. 녹음 및 재생방법이 쉽고 간편함.
2. 음질이 우수하며 자연음 재생가능.
3. 수동 스위치로 동작 가능.
4. 최대 녹음 시간 60초.
5. 녹음된 메시지 영구보존가능(백업 배터리 없음).
6. 100년간 메시지 보존가능.
7. 100,000번까지 재녹음 가능.
NOTES
To replace an existing announcement by a new one, the
memory location must not be deleted before.
The previous announcement is an automatically overwritten.
중요사항
현재 녹음된 메시지를 새로운 메시지로 교환하고자 녹음할 때는
전에 녹음된 메시지는 지울 필요가 없으며 자동으로 덮어 씌워집니다.
1) Set the switch AUTO/MANUAL to "MANUAL".
2) Set the switch PLAY/REC to "REC".
3) Set the switch MIC/LINE according to the input signal used:
For a microphone to position "MIC".
For a unit with line level (e.g cassette recorder, CD player) to
position "LINE".
4) Connect the microphone or the unit to the jack MIC/LINE INPUT
If an input signal is available, the LED SIG lights up.
5) Adjust the recording volume with the control REC LEVEL so
that the LED CLIP just does not light up.
6) Start the recording with the button START.
While recording the LED OPERATING lights up.
7) At the end of recording stop the recording by pressing the
button STOP.
The LED OPERATING extinguishes.
1) AUTO/MANUAL 스위치를 "MANUAL" 위치에 설정하십시오.
2) PLAY/REC 스위치를 "REC" 위치에 설정하십시오.
3) 사용하고자 하는 입력신호에 따라 MIC/LINE 스위치를 설정하십시오.
예를 들면, 마이크 신호 입력시 "MIC" 위치에 라인 레벨(카세트, CD)
신호 입력시 "LINE" 위치에 설정하십시오.
4) MIC/LINE 입력 잭에 마이크나 장비를 연결하십시오.
입력신호가 들어오면 SIG LED가 켜집니다.
5) CLIP LED가 켜지기 직전의 레벨로 REC볼륨을 조절하십시오.
6) START 버튼을 누르면 녹음이 진행되며 OPERATING LED가 켜집니다.
7) 녹음을 정지하려면 STOP 버튼을 누르면 녹음이 정지되며
OPERATING LED가 꺼집니다. 또한, 사용 가능한 메모리 용량을
(1분) 모두 소모하면 자동으로 정지합니다.
사용방법
1. 녹음방법
특징
5
EMERGENCY MESSAGE CARD JEU-211AMA(option)
9

EMERGENCY MESSAGE CARD JEU-211AMA(option)
RECORDING CONNECTION (녹음 결선도)
SPECIFICATIONS (규격 및 성능)
2. HOW TO REPLAYING 2. 재생방법
중요사항
녹음이 완료된 후 JEU-211AU,JEU-211A에 장착할 때는 반드시
AUTO/MANUAL 스위치를 "AUTO"위치로, PLAY/REC 스위치를 "PLAY"위치로
설정해 주십시오.
E/M 상황이 발생하면 10초간 사이렌이 방송되고난 후 녹음된 E/M
메세지가 무한 반복 방송됩니다.
중요사항
헤드폰이 연결되어 있는 동안은 방송이 JEU-211AU로 출력되지 않습
니다.
1) Set the switch AUTO/MANUAL to "MANUAL".
2) Set the switch PLAY/REC to "PLAY".
3) To replay the announcement, press the button START.
While replaying the announcement, the LED OPERATING lights up.
4) Adjust the volume with the volume control LEVEL.
5) To finish the announcement before the end, press the button
STOP. The LED OPERATING extinguishes.
1) AUTO/MANUAL 스위치를 "MANUAL" 위치에 설정하십시오.
2) PLAY/REC 스위치를 "PLAY" 위치에 설정하십시오.
3) START 버튼을 누르면 재생이 진행되며 OPERATING LED가
켜집니다.
4) LEVEL 볼륨을 사용하여 출력 레벨을 조절하십시오.
5) STOP 버튼을 누르면 재생이 정지되며 OPERATING LED가 꺼집니다.
3. HEADPHONES 3. 헤드폰 사용법
The announcement can be checked with headphones while replaying. 재생 진행중 방송 내용을 모니터하기 위해 헤드폰을 사용할 수 있습니다.
CD PLAYER, Cassette Recorder
Microphone
Headphone
VR2
LEVEL
MIC/LINE
CN2 BLK
BRN
RED
ORG
YEL GND POWER SUPPLY
+24V
CONTROL
AUDIO
E/M IN
GND
+24V
H.P
BLK
OR
BRN
RED
ORG
YEL
From JEU-211AU, JEU-211A
Inputs MIC : -50dB/600 Unbal
LINE : -10dB/10k Unbal
Operating Voltage +24VDC
Current Consumption NOR 30mA / MAX 70mA
Message Recording Time Max 60sec
Dimensions 130(W) x 30(H) x 153(D)mm
5.1(W) x 1.2(H) x 6.0(D)inch
Weight 190g / 0.42lbs
Outputs Audio Output : 0dB/600
Headphone Output : 24mW 32
Frequency Response MIC : 300Hz~3.4kHz ( =8kHz)
LINE : 100Hz~3.4kHz ( =8kHz)
NOTES : When you install E/M message card to JEU-211AU,
JEU-211A, be sure to place switch of AUTO/MANUAL to
"AUTO" position and place switch of PLAY/REC to "PLAY" position.
Stored E/M message is announced endless repeately after 10
seconds siren warning incase of E/M situation.
NOTES :
Announcement will not come out to JEU-211AU.
While headphone is plug in.
1) Connect the headphones with the jack HEADPHONES.
2) Adjust the volume with the volume control LEVEL. 1) 헤드폰 잭에 헤드폰을 연결하십시오.
2) LEVEL 볼륨을 사용하여 헤드폰 레벨을 조정하십시오.
6

E/M, R/M, TEL PWR CON
L
N
E
24V/1.5A
DC OUTPUT
24V/1.5A
SWITCHED TOTAL MAX OUTPUT 7000VA. SWITCHED EACH MAX OUTPUT 3500VA.
DC 24V
EQUIPMENT
ONLY.
DC 24V OUTPUT
SERIAL NO.:
(TO JRG-220A)
(TO JEP-352)
POWER OUTPUTS DELAY SOCKET(1 6) FOR POWER AMPLIFIERS.
UNSWITCHED MAX 360VA
9 8 7
6 5 4 3 2 1
CAUTION
RISK OF ELECTRIC SHOCK
DO NOT OPEN
230V / 50Hz
24V
SWITCHED IN
PWR CONTROL IN
UNSWITCHED IN
TO OTHER
JPD-322A
WARNING:
TO REDUCE THE RISK OF
FIRE OR ELECTRIC SHOCK DO NO T EXPOSE
THIS EQUIPMENT TORAIN OR MOISTURE.
MODEL NO.: JPD-322AU
POWER CHECK
(NON PULSE)
DC OUTPUTS
T40AL 32V T40AL 32V T20AL 32V T20AL 32V T20AL 32V
CAUTION
:
IN CASE OF USING EXTERNAL
EXTERNAL
BATTERY
24V
CAUTION:TO REDUCE THE RISK OF
FIRE REPLACE ONLY WITH SAME TYPE FUSE.
SERIAL NO.:
UNSWITCHED OUT
1 2 3 4 5
EMERGENCY POWER SUPPLY
MADE IN KOREA
MODEL NO.: JEP-352U
WARNING:
TO REDUCE THE RISK OF FIRE
OR ELECTRIC SHOCK DON'T EXPOSE THIS
EQUIPMENT TO RAIN OR MOISTURE.
24V
SWITCHED OUT
PWR CONTROL OUT
(FROM JPD-322A)
CAUTION
RISK OF ELECTRIC SHOCK
DO NOT OPEN
FUSE RATING
T2AH 250V
AC 230V 50Hz 105W
BATTERY, INTERNAL BATTERY IS NOT AVAILABLE.
BE SURE NOT TO EXCEED 24A OF DC OUTPUTS
FOR USING OF INTERNAL BATTERY.
EACH
24V/32A EACH
24V/16A
POWER
CHECK
AKU 40%
CHECK
(NON PULSE)
(NON-PULSE)
USE ONLY WITH A 250V FUSE
4040 20 20 20
E M SPEAKER SELECTOR
MADE IN KOREA
MODEL NO.: JES-120AU
CAUTION
WARNING:
TO REDUCE THE RISK OF FIRE
OR ELECTRIC SHOCK DON'T EXPOSE THIS
EQUIPMENT TO RAIN OR MOISTURE.
RISK OF ELECTRIC SHOCK
DO NOT OPEN
LINK
TO JRG-220A
DATA OUT EXTENSION
20 19 18 17 16 15 14 13 12 11 10 98 7654321
S/N
TO JEU-211A
+24V
GND OUT E/M ALL OUT(+5V)
+5VDC/0.25A OUT
IN
OUT EXTENSION FIRE DETECTOR INPUT
E/M ALL OUT(+5V)
POWER CHECK
TX CHECK
(NON PULSE)
(PULSE)
EMERGENCY MESSAGE CARD
LEAK 10
LEVEL
LEVEL
LEAK 10
MODEL.: JEU-211AU
EMERGENCY UNIT
MADE IN KOREA
CAUTION
RISK OF ELECTRIC SHOCK
DO NOT OPEN
WARNING:
TO REDUCE THE RISK OF FIRE
OR ELECTRIC SHOCK DON'T EXPOSE THIS
EQUIPMENT TO RAIN OR MOISTURE.
FROM
JES-120A
BAL
1.23V 600
SERIAL NO.:
E/M ALL IN
24V
GND IN
E/M AUDIO
OUTPUT SIREN
FAULT CHECK
(NON PULSE)
FIRE CHECK
(NON PULSE)
SYSTEM CONNECTIONS (시스템 연결 방법)
LEVEL
DATAOUT
AUDIO OUTPUT
BAL 1.23V 600W
CHIME MIC
SERIAL NO.:
CAUTION
WARNING: TOREDUCE THE RISK OF FIRE
OR ELECTRIC SHOCK DON'T EXPOSE THIS
EQUIPMENT TO RAIN OR MOISTURE.
RISK OF ELECTRIC SHOCK
DO NOT OPEN
G
POWER
ON
OFF
REMOTEAMPLIFIER
MADEIN KOREA
MODEL NO.: JRA-051A
10
010
LEAK
JRA-051A #1
LEVEL
DATAOUT
AUDIO OUTPUT
BAL 1.23V 600W
CHIME MIC
SERIAL NO.:
CAUTION
WARNING: TOREDUCE THE RISK OF FIRE
OR ELECTRIC SHOCK DON'T EXPOSE THIS
EQUIPMENT TO RAIN OR MOISTURE.
RISK OF ELECTRIC SHOCK
DO NOT OPEN
G
POWER
ON
OFF
REMOTEAMPLIFIER
MADEIN KOREA
MODEL NO.: JRA-051A
10
010
LEAK
JRA-051A #2
G
LINK
INPUT
REMOTE AUDIO IN
REMOTE ZONE DATA OUT
AMP PRIORITY CONTROL OUT
REMOTE DATA
FROM JDR-104 / JRA-051A
FROM JSS-120A
REMOTE-1 CARD
20
19 18 17 16 15 14 13 12 11
10 9 8 7 6 5 4 3 2 1
G
DIRECT SPEAKER SELECTOR DATA IN
TELEPHONE PAGING CARD
TEL AUDIO IN
+5V OUT
10 9 8 7 6 5 4 3 2 1
20 19 18 17 16 15 14 13 12 11
UPPER JRG-220A
G
E/M DATA E/M
LINK
INPUT
G
FROM JSS-120A
TO RELAY BOX LOWER JRG-220A
FROM JPD-322A
AUDIO
IN AUDIO
OUT
N.O
COM
+24V
OUT
EMERGENCY CARD
E/M
GND
G G G G G
MADE IN KOREA
DATARECEIVER
MODEL NO.: JDR-104
TO JRG-220A
DATA OUT
SUMMING
AUDIO OUT
SERIAL NO.:
RM 4
AUDIO IN RM 3
AUDIO IN RM 2
AUDIO IN RM 1
AUDIO IN
RM 4
DATA IN RM 3
DATA IN RM 2
DATA IN RM 1
DATA IN
CAUTION
RISK OF ELECTRIC SHOCK
DO NOT OPEN
WARNING:
TO REDUCE THE RISK OF FIRE
OR ELECTRIC SHOCK DON'T EXPOSE THIS
EQUIPMENT TO RAIN OR MOISTURE.
TO JRG-220A TO JRG-220A
REMOTE ALL IN
5V~24VDC
SPEAKER SELECTOR OUT REMOTE ZONE DATA IN
SERIAL NO.:
ACTIVE SPEAKER SELECTOR
MADE IN KOREA
MODEL NO.: JSS-120A
CAUTION
WARNING: TO REDUCE THE RISK OF FIRE
OR ELECTRIC SHOCK DON'T EXPOSE THIS
EQUIPMENT TO RAIN OR MOISTURE.
RISK OF ELECTRIC SHOCK
DO NOT OPEN
JEU-211AU
(JEU-211A)
JCU-160
JSS-120A
JDR-104
JRG-220AU
(JRG-220A)
JEP-352U
(JEP-352)
JPD-322AU
(JPD-322A)
TO ÒDÓ TYPE POWER AMP
PRIORITY IN
TO ÒDÓ TYPE POWER AMP
PRIORITY CONTROL IN
JES-120AU
(JES-120A)
FIRE SENSOR
POWER CHECK
(NON PULSE)
JCU-160
IN OUT
RS-232C
UNIT NO. RESET
DC INPUT
SUM OUTPUT
24V
INPUT
CHECK SIGNAL
CH 1CH 2CH 3CH 4CH 5CH 6CH 7CH 8
CH 9
1 8
CH 10CH 11CH 12CH 13CH 14CH 15CH 16
1 8 9 169 16
NON PULSE
PULSE
CHANNEL USE
OFF
ON
7

SPECIFICATIONS (규격 및 성능)
MIC
TECHNICAL
Input Sensitivity/Impedance 2.45mV(-50dBm)/1.2K Unbalanced
8
Specifications and design subject to change without notice for improvements.
(내용상의 규격 및 특징은 제품의 성능 향상을 위하여 사전 예고 없이 변경될 수 있습니다.)
NOTE
Output Level/Impedance 1.23V(+4dBm)/600 Balanced
Frequency Response Less Than -3dB(200Hz~10KHz)
Signal to Noise Ratio More Than 60dB
T.H.D Less Than 0.5%(200Hz~10KHz)
GENERAL
Power Consumption 3.5W
Power Source DC 24V
E/M MESSAGE
Recording Time Basic 16SEC(ROM#1)
Extended 32SEC(ROM#1, #2)
Sampling Frequency 16KHz
Frequency Response Less Than -3dB(200Hz~6.4KHz)
SIREN
Siren Frequency 800Hz (파상)
Dimensions
Weight(kg/lbs) 3 / 6.6
483(W) x 88(H) x 200(D)mm
19(W) x 3.5(H) x 7.9(D)inch
Condition detection mode 2 Mode (FAULT / FIRE CHECK)

9
DC POWER
24V
MIC INPUT
2.45mV
(-50dBm)
1.2Kohm
UNBALANCED
H.A GATE B.A L.A
1 : 1
OUTPUT
+4dBm
600ohm
BALANCED
+18V
V. C.O
OSC
P. T. T
E/M
INDICATOR
REG +18V
DC FUSE
LEVEL
LIMITER
SIREN
SIREN
LEVEL
E/M MESSAGE
ROM
10 SEC
DELAY
MULTI CONNECTOR
WIRING
PIN4: PTT S/W
PIN2, PIN3: GND
PIN1: MIC +
FILTER
E/M MESSAGE CARD
(OPTION)
E/M ALL IN
OSC DETECTOR BUZZER
FAULT LED
LOCK DIAGRAM (블럭도)
FAULT CHECK
(NON PULSE)
FIRE CHECK
(NON PULSE)

JEU-211AU
OPERATING INSTRUCTIONS
4M-OP207080
080106
EMERGENCY UNIT
Table of contents
Popular Security System manuals by other brands

Siqura
Siqura Ex Fixed series installation manual

AFRISO
AFRISO OM 1 operating instructions

Honeywell
Honeywell ADEMCO VISTA-40 Installation and setup guide

Teletek electronics
Teletek electronics SensoIRIS MCP150MR installation instructions

Security Cameras Direct
Security Cameras Direct ECO4IR Quick installation and setup guide

Monacor
Monacor TVSET-550 instruction manual