Jeven UV TURBO UV-CONTROL G1 User manual

JEVEN UV-CONTROL G1
Installation Guide
Dokument Nr 500-00039
Revision B

CONTENT
PRODUCT DESCRIPTION ...............................................3
SOFTWARE FEATURES....................................................3
TECHNICAL DATA .............................................................3
DELIVERY CHECK .............................................................4
ELECTRICAL INSTRUCTION ..........................................5
WIRING..................................................................................6
SETTINGS AND OPERATIONS ...............................7-21
MODBUS INSTALLATION ............................................ 22
MODBUS COMMUNICATION.................................... 23
MODBUS CHANGE IP ADRESS........................... 24-26
JEVEN UV-Control Installation 2
Rätt till ändringar förbehålles

PRODUCT DESCRIPTION
SOFTWARE FEATURES
TECHNICAL DATA
Jeven UV-Control controls and monitors UV-TurboSwing filters. With continuous monitoring of run time
and UV-light sources, the function of UV treatment is ensured.
Jeven UV-Control starts/stops all UV-Turbo filter. Operating periods for the kitchen can be set by an
weekly timer, Monday to Sunday according to the needs the user has. The system can also be run manually
or by way of external start/stop signal.
UV-Turbo filters run time is measured and emits alarms when the UV-lamp’s maximum run time is reached.
(Max run time UV-lamps 8 000 h).
Jeven UV-Control monitors the UV-lamps if they break before the maximum operating time is reached
and alarms.
When the maximum operating time is reached, there is a possibility to reset the time, if replace of an
individual UV-lamp before the maximum operating time has been reached, should not the time be reset.
Sum alarm from from Jeven UV-Control can be passed to an superior system by a potential-free contact.
• Start and stop of UV-Turbo filter is selectable between: Manual, Week timer or External signal.
• Control of operating time, alarm at reached value.
• Ability to reset operating time.
• Control of the total ampere value of the UV lamps in the system, alarm if one breaks down.
• Potential free relay output to superior system in case of alarm.
Dimension: 200x200x120mm (WxHxD)
Power supply: 230VAC, 10A
Protection: IP65
Ambient temperature: <55 ° C
Maximum number of UV-Turbo filter: 25pcs
JEVEN UV-Control Installation 3
Rätt till ändringar förbehålles

DELIVERY CHECK
Control that the insulation box and cables dosen’t have any defects. Defective material can not be assem-
bled and put into operation. Contact Jeven AB for handling of defective material.
Delivery includes:
• Jeven UV-Control • Safety switch
• Connected cables. 5m or 10 m • Jeven Plug & Playbox, 1 piece / hood
Mounted on the ceiling of the hood
4
Rätt till ändringar förbehålles JEVEN UV-Control Installation
Rätt till ändringar förbehålles

ELECTRICAL INSTRUCTION
5
Rätt till ändringar förbehålles JEVEN UV-Control Installation

WIRING
6
Rätt till ändringar förbehålles JEVEN UV-Control Installation

SETTINGS AND OPERATIONS
Jeven UV-Control has three different possibilities for start and stop of the UV-Turbo filters, monitoring
the UV-lamps and keeping track of the UV-lamps operating time. As well as the ability to adjust the alarm
limit for the ampere measurement, if for example retrofitted into one or more UV-Turbo.
7
Rätt till ändringar förbehålles JEVEN UV-Control Installation

SETTINGS AND OPERATIONS
1. CONTROL FUNCTION
1.1 Manual Start/Stop
1.2 Start/Stop with weekly timer
1.3 Start/Stop by external signal
2. RUN TIME
2.1 Read current run time
3. ALARM
3.1 Alarm UV-lamp
3.2 Alarm run time
3.3 Alarm cleaning
3.4 Sum alarm
3.5 Operation indication
4. PROGRAMMING ALARM LIMIT
CONTENT
Rätt till ändringar förbehålles JEVEN UV-Control Installation 8
Rätt till ändringar förbehålles

SETTINGS AND OPERATIONS
1. CONTROL FUNKTION
1.1 Manual start/stop
To stop the UV-purification manual press
( Esc + ◄ )
9
Rätt till ändringar förbehålles JEVEN UV-Control Installation

SETTINGS AND OPERATIONS
1. CONTROL FUNCTION
1.2 Start and stop with weekly timer
To enter the program menu, press ▼then Esc.
In the program select: 1. ”Program”, 2 ”Set parameter” and 3. ”WEEKLY TIMER”.
Here you can use up to 3 different time programs D1, D2 and D3.
Example:
D1 D2
M, T, W, T, F S, S
On1 On2
07:00 10:00
Off1 Off2
16:00 14:00
Exit the program menu by pressing Esc until, time and date appear on screen,
then press arrow ▲.
10
Rätt till ändringar förbehållesRätt till ändringar förbehålles JEVEN UV-Control Installation

SETTINGS AND OPERATIONS
1. CONTROL FUNCTION
1.3 Start/Stop by external signal
Connect control cable to input I8 on Siemens LOGO! When using 230VAC signal.
Or use the 24VDC relay to activate Start/Stop by 24VDC signal.
Start of the system occurs when input I8 on Siemens LOGO! will go in “high” state over 79VAC.
Stop of system occurs when the voltage level is below 30VAC, the input I8 on Siemens LOGO! will
go in “low” state.
Internal 230 VAC
External 230VAC
Relay 24VDC External -24VDC
External +24VDC
Relay diagram
JEVEN UV-Control Installation 11
Rätt till ändringar förbehålles

SETTINGS AND OPERATIONS
2. RUN TIME
2.1 Read current run time
Current operating time is read
by simultaneously pressing:
Esc + ►
UV lamps have a lifespan of 8 000 h, then they should be replaced. The system will indicate when
the run time of 8 000 h has been reached.
JEVEN UV-Control Installation 12
Rätt till ändringar förbehålles

SETTINGS AND OPERATIONS
3. ALARM
3.1 Alarm UV-lamp
If a UV-lamp is broken, the system detects power loss and generates an alarm.
Then it needs to be physically checked which filter house the diode labeled UV does not light blue. When
it is determined which UV light is broken, byts den. The alarm is reset automatically when the current
limit returns to the normal level
3.2 Alarm run time
Jeven UV-Control has built-in control of the run time of the UV-lamp, the system will give an alarm when
8 000 h are reached, which is the lifespan of the UV-lamps. Replace all
UV-lamps and reset run time by pressing ESC + ▼
JEVEN UV-Control Installation 13
Rätt till ändringar förbehålles

SETTINGS AND OPERATIONS
3. ALARM
3.3 Alarm cleaning
There is a possibility to set a cleaning interval in the Siemens LOGO!.
The service function is OFF by default.
Set the cleaning status to ON.
Adjust the cleaning interval if necessary. Default time is set to 10h (On =+00010).
JEVEN UV-Control Installation 14
Rätt till ändringar förbehålles

SETTINGS AND OPERATIONS
3. ALARM
3.4 Sum alarm
There is a possibility of connecting to the superior system and receiving a signal when an alarm has been
triggered. Connect any voltage, Max 240VAC/VDC to the potential-free relay output Q1 (NO) on
Siemens LOGO!
Alarm
External Max 240VAC/VDC
3.4 Operation indication
It is possible to get an operation indication from Simens LOGO! Connect any voltage, Max 240VAC / VDC
to the potential-free relay output Q4 (NO) on the Siemens LOGO!
Operation indication
External Max 240VAC/VDC
JEVEN UV-Control Installation 15
Rätt till ändringar förbehålles

SETTINGS AND OPERATIONS
4. PROGRAMMING ALARM LIMIT
The monitoring of the UV lamps is done by measuring the total current value of all UV-lamps in the instal-
lation. Should a UV-lamp break, the system detects the current change and displays the alarm on Siemens
LOGO! and triggers the potential-free relay output Q1 on Siemens LOGO!
Due to the low power consumption from one UV-lamp (0.1A), the current relay Finder 71.51 is program-
med with the internal power transformer for a more stable current measurement. This means that the
visual value shown on the Finder 71.51 display is only a fictional value. Jeven UV-Control is delivered
pre-programmed and calibrated for each project/kitchen.
The following is instructions for calibration of the system:
• Start the system and check all filters that the LED labeld UV lights blue, then read on the Finder
71.51 display, what the current current value is.
• Take down a grease collector in the kitchen hood closest to Jeven UV-Control, read which current
value is now displayed on the Finder 71.51 when a UV-lamp has been turned off.
JEVEN UV-Control Installation 16
Rätt till ändringar förbehålles

SETTINGS AND OPERATIONS
4. PROGRAMMING ALARM LIMIT cont.
• The alarm limit should have a value between fully operational system and when one (1) UV-lamp
is disconnected, as exemplified above: Fully functional 40A, one (1) UV lamp off 34A. The alarm
limit should then have a value of 37A.
• To check the current alarm limit and the ability to adjust it, you need to enter the Finder 71.51
programming view. Accessing the programming view is achieved by holding down the ”Set/Reset”
and ”Select” buttons at the same time for 3 seconds.
JEVEN UV-Control Installation 17
Rätt till ändringar förbehålles

SETTINGS AND OPERATIONS
4. PROGRAMMING ALARM LIMIT cont
• Screen 1: Displays us to measure alternating current AC, this must not be changed!
Press the ”SET / RESET” button to proceed.
• Window 2: Here is the value of the internal power transformer, this must not be changed!
Press the ”SET/RESET” button to proceed.
• Window 3: Here you choose if you want to measure under or overcurrent, the system should me
asure undercurrent and may not change!
Press the ”SET / RESET” button to proceed.
JEVEN UV-Control Installation 18
Rätt till ändringar förbehålles

SETTINGS AND OPERATIONS
4. PROGRAMMING ALARM LIMIT cont
• Window 4: Here you can change the alarm limit for the UV current, check which level is program
med and change if necessary. Use the ”SET/RESET” button to move the cursor in the window,
change the digits by pressing the ”SELECT” button until the correct number is on the window.
As in exemlett above we would have 37A. Press the ”SET / RESET” button to proceed.
• Window 5: Here is the value of the preprogrammed hysteresis value, this must not be changed!
Press the ”SET / RESET” button to proceed.
• Window 6: (T1) Here you program a delay of outgoing alarm when it has detected a current loss,
Finder 71.51 is programmed with a delay of 10 seconds. This value should not be changed.
Press the ”SET/RESET” button to proceed.
JEVEN UV-Control Installation 19
Rätt till ändringar förbehålles

SETTINGS AND OPERATIONS
4. PROGRAMMING ALARM LIMIT cont
• Window 7: (t2) A delay is programmed here when the Finder 71.51 starts to do the undercurrent
measurement, the delay is programmed with 10 seconds for the current to be stable before mea
surement. This value should not be changed!
Press the ”SET / RESET” button to proceed.
• Window 8: Selection of memory function, memory function should not be used.
Do not change!
Press the ”SET/RESET” button to proceed.
JEVEN UV-Control Installation 20
Rätt till ändringar förbehålles
Table of contents
Popular Controllers manuals by other brands

Rainbow Pool Products
Rainbow Pool Products CHEMIGEM DM52CHL manual

Hydro Instruments
Hydro Instruments HC-220 Operation and maintenance manual

Flycolor
Flycolor Raptor BLS-Pro-20A user manual

VLT
VLT MCD 500 operating instructions

Luxel
Luxel Radak Power Controller II Series manual

sauter
sauter AVF125S Fitting instructions