Johnson Controls Unitary Products S1-CD065T01 User manual

S1-CD065T01 Central Dehumidifier
Installation Instructions
SPECIFICATIONS
Dimensions: Width: 12.5” cabinet, 13” with doors
Height: 14.5” cabinet, 18.5” with leveling feet
fully extended
Length: 22” cabinet, 27” with collars
Weight: 65 lbs.
Capacity: 65 pints/day @ 150 cfm
AHAM DH-1-2003 80°F, 60% RH conditions
Efficiency: 1.8 Liters per kilowatt hour
AHAM DH-1-2003 80°F, 60% RH conditions
Power: 115VAC, 60 Hz, 8A Operating Current
Unit equipped with 8 ft. grounded power cord
15 Amp circuit required
Airflow:
Inlet Air Operating Conditions: 60°F to 95°F, 30% RH to 99% RH
Installation Conditions: 40°F to 140°F, 0% RH to 99% RH
Evaporator Frost Sensor: 25°F +/- 5°F, circuit opens (cut-out)
55°F +/- 5°F, reset temperature (cut-in)
Filter: MERV 8, washable
WARNING
1. 120 volts may cause serious injury from electric shock. Disconnect electrical power
before starting installation. Leave power disconnected until installation is complete.
2. Sharp edges may cause serious injury from cuts. Use care when cutting plenum
openings and handling ductwork.
3. Dropping may cause personal injury or equipment damage. Handle with care.
4. Do not remove the outlet screen. The screen is required to protect from moving parts
and electrical components.
CAUTION
1. Do not use in pool applications.
2. If unit has been shipped or stored on
its side, wait 24 hours before running.
3. Do not use solvents or cleaners on or
near the circuit board.
P ("w.c.) Airflow (cfm)
0230
0.25 190
0.50 150
LOCATION CONSIDERATIONS
1. Install Unit Indoors: Do not expose to elements.
2. Drain Accessibility: If a drain is not located in the
installation area, a condensate pump may be required.
3. Power: Outlet within 8 feet of unit.
4. Filter Access: Allow for 12” clearance on one side of
the unit for removal of filter. (Figure 1)
5. Inlet: If inlet is not ducted, a minimum of 6” of open
space is required from the inlet panel to an adjacent
surface.
TOP VIEW
FILTER 12" MINIMUM CLEARANCE
FOR FILTER
(EITHER SIDE)
6" MINIMUM CLEARANCE
FOR PROPER AIR FLOW
90-1426
FIGURE 1 – Filter
Access Clearance
UNPACKING AND CONTENTS
Do not tip unit to remove from carton.
1. Open carton completely using cut line shown along bottom
perimeter of carton.
2. Remove all cardboard inner pack (top edges and duct collars).
3. See Figure 2 for opening view and contents.
a. Installation Manual
b. Owner’s Manual
c. Knob Setpoint Insert Sheet
d. Dehumidistat (mounted to inlet panel)
e. Bag with Dehumidistat Cover Plate, Screws (2), Anchors (2)
f. Outlet with Back Flow Damper
g. 8 ft. Grounded Power Cord
h. Wiring Access Panel
i. Condensate Pan
b
a
cd
e
f
gh
i
FIGURE 2 – Carton
Opening & Contents
90-1464
Johnson Controls
Unitary Products

SET-UP
The dehumidifier can be installed as shipped, with the supply collar
on the outlet panel, or if space is restricted, the supply collar can be
relocated to the top of the unit.
TOP MOUNT SUPPLY COLLAR (FIGURE 3)
1. Remove the four screws securing the supply collar (with backflow
damper) and screen to the outlet panel.
2. Remove the four screws securing the top mounted outlet cover plate.
3. Attach screen and supply collar with damper to the top of the unit.
4. Attach outlet cover plate to the outlet panel.
SUPPLY COLLAR FIGURE 3 – Top Mount Supply Collar
The dehumidistat mounted to the dehumidifier can remain on the unit
or be removed and mounted in the living space. Attic installations
require that the dehumidistat be moved to the living space.
Note: Any dry contact, normally open humidity control can be
used as the controlling device for the dehumidifier, thermostat
S1-TTSCC01 is recommended. For removal and relocation of the
dehumidistat or if using a S1-TTSCC01 thermostat, see the WIRING,
ONBOARD DEHUMIDISTAT WALL MOUNT INSTALLATION and
S1-TTSCC01 WIRING sections.
WALL MOUNT LOCATION
• Mount approximately 5 feet above the floor on an inside wall of the
living space.
• Do not locate dehumidistat in the direct path of drafts from open
doors and windows.
• Do not install where operation might be affected by lamps, outside
sources of humidity (i.e. shower), fireplace, registers, or radiators.
DEHUMIDISTAT LOCATION
90-1425
Supply collar
mounted to
top of unit
Outlet cover
plate moved to
outlet panel
2-1/8" CLEARANCE
FOR LEVELING FEETVIBRATION ISOLATORS
FILTER ACCESS DOOR
OUTLET INLET
5-1/8"
MECHANICAL INSTALLATION
Run vinyl or pvc tubing from the 3/4” drain outlet on the dehumidifier inlet to a floor drain. Make sure the drain line has a constant downward
slope and is not kinked. Refer to local codes to determine if a p-trap is required. In attic installations the supplied condensate pan with a field
supplied float switch is required. See Condensate Pan and Float Switch section for installation and wiring instructions.
DRAIN
FIGURE 4 – Suspended Installation
If hanging the unit, use 1/4” threaded rod and two unistruts to
support the base just inside the leveling feet. It is recommended that
vibration isolators be placed between the unistruts and dehumidifier
base. See Figure 4. Do not position threaded rods over filter access
doors. There must be a minimum clearance of 12” on one side of the
unit to allow for removal of the filter.
SUSPENDED INSTALLATION
90-1427
OUTLET VIEW
2

The dehumidifier is supplied with two 8” round collars. An integral backflow damper is installed in the outlet collar. In a ducted installation, the
dehumidifier pulls air from the living space or HVAC return duct and supplies the dehumidified air to the HVAC supply duct (See Figures 5, 6 & 7).
DUCTED INSTALLATION
• Move supply collar to the desired location, if necessary. (See Supply Collar in SET-UP section.)
• The unit can be ducted to the supply or both the return and supply. The dehumidifier inlet ducting must be a minimum of 6” upstream of the
HVAC system air cleaner and the outlet must be ducted a minimum of 6” downstream of the cooling coil.
An additional option is to duct the dehumidifier inlet and outlet to the return duct. This installation must include wiring the dehumidifier to
activate the HVAC blower during dehumidification. (See Wiring to HVAC System in WIRING section.)
• Use the least amount of ductwork possible. To ensure best performance, do not exceed a total of 50 feet of duct installed in accordance with
SMACNA Standards. UL approved, 8” diameter, insulated duct is recommended for all connections.
• All joints and seams must be sealed.
DUCTING
HVAC / FURNACE
115 VAC
CIRCUIT
DEHUMIDIFIER
SUPPLY DUCT
RETURN
DUCT
A-COIL
DEHUMIDIFIED AIR IS SUPPLIED
DOWNSTREAM FROM A-COIL TO
MINIMIZE EVAPORATION OFF A-COIL
AIR IS PULLED
FROM MAIN
RETURN DUCT
DEHUMIDISTAT WITH
SET POINT KNOB
CONDENSATE HOSE
(TO COMMON DRAIN OR OUTSIDE)
NOTE: DO NOT BLOCK
FURNACE ACCESS
FIGURE 5 – Basement Installation
90-1423
MAIN RETURN
DUCT
DEHUMIDIFIER
MAIN SUPPLY DUCT
CONDENSATE
HOSE
(TO COMMON
DRAIN OR
OUTSIDE)
PRINCIPAL
LIVING SPACE
115 VAC
CIRCUIT
HVAC/FURNACE SYSTEM
SHOWN IN HORIZONTAL
ORIENTATION
DEHUMIDIFIED AIR IS SUPPLIED
DOWNSTREAM FROM EVAPORATOR COIL
TO MINIMIZE EVAPORATION OFF COIL
HVAC EVAPORATOR COIL
RELOCATE DEHUMIDISTAT
TO LIVING SPACE
AIR FILTER ACCESS DOOR
CONDENSATE PAN
AND FLOAT SWITCH
FIGURE 7 – Attic Installation
90-1423
DEHUMIDIFIED AIR IS SUPPLIED
DOWNSTREAM FROM A-COIL TO
MINIMIZE EVAPORATION OFF A-COIL
115 VAC
CIRCUIT
A-COIL
SUPPLY DUCT
HVAC / FURNACE
CONDENSATE HOSE
ON DEHUMIDIFIER
(TO COMMON DRAIN
OR OUTSIDE)
DEHUMIDIFIER
NOTE: DEHUMIDIFIER
DRAWS AIR FROM
LIVING SPACE THROUGH
RETURN GRILL
FIGURE 6 – Equipment Room/Closet Installation
90-1423
Note 1: Attic installations require the following.
1. The dehumidistat must be removed from the
unit and relocated in the living space. An
insulated cover plate is provided to cover the
dehumidistat opening.
2. The dehumidifier must be installed in the
supplied condensate pan with a field supplied
float switch.
Note 2: Vibration isolators placed under the
dehumidifier feet are recommended when the
dehumidifier is installed on ceiling joists.
CAUTION
Ensure return grill in door is not obstructed so dehumidifier
does not pull from HVAC system.
3

STAND ALONE INSTALLATION
In a free standing installation, the dehumidifier pulls air from the installed space and returns the dehumidified air back to that space. See Figure 8.
• Place unit in area with drain access and within 8’ of an outlet.
• Unit can also be ducted to pull and return to a single living space. See Figure 9.
OUTSIDE AIR
TO HOUSE
LIVING SPACE
SUPPLY DUCT
RETURN DUCT
FLOOR DRAIN
DEHUMIDIFIER
115 VAC
CIRCUIT
RELOCATE
DEHUMIDISTAT
TO LIVING SPACE
CONDENSATE HOSE
(TO COMMON DRAIN OR OUTSIDE)
FIGURE 9 – Stand Alone, Ducted
90-1423
The feet can be adjusted to level the unit and/or to accommodate
a p-trap. Leveling is required to ensure proper drainage from the
dehumidifier. See Figure 10.
LEVELING
WIRING
The dehumidifier can be wired to activate the HVAC blower during dehumidification. This is recommended because it offers better circulation
and balancing of the indoor air conditions. Note: Running the HVAC blower during dehumidification does not affect moisture removal efficiency.
If the unit is not wired to the HVAC system, air is pulled through the unit, dehumidified, and circulated solely by the dehumidifier blower.
WIRING TO HVAC SYSTEM
DEHUMIDIFIER
CIRCUIT BOARD
TERMINALS
HVAC EQUIPMENTTHERMOSTAT
G
R
C
G
W
YY
W
C
R
G STAT
R HVAC
G HVAC
HVAC WIRING INSTRUCTIONS
1. Disconnect power to the HVAC system using disconnect switch or fuse/breaker.
2. Unplug the dehumidifier.
3. Remove wiring access panel on the dehumidifier outlet panel.
4. Run a 3-wire cable from the dehumidifier to the furnace/air handler.
5. Unplug the G-STAT, R-HVAC, & G-HVAC terminals. Make the connections shown
in Figure 11.
6. Plug terminals back into circuit board.
7. Replace the wiring access panel when wiring is complete.
FIGURE 11 – DEH/HVAC Wiring Instructions
90-1424
OUTSIDE AIR
TO HOUSE
SUPPLY DUCT
RETURN DUCT
FLOOR DRAIN
DEHUMIDIFIER
115 VAC
CIRCUIT
CONTROL
CONDENSATE HOSE
(TO COMMON DRAIN OR OUTSIDE)
HVAC / FURNACE
AIR IS PULLED FROM
INSTALLED SPACE
DEHUMIDIFIED AIR
IS SUPPLIED TO
INSTALLED SPACE
FIGURE 8 – Stand Alone, Non-Ducted
90-1423
CAUTION
Ensure air circulation is maintained in installed space so dehumidifier
does not pull from HVAC system.
7/8" MINIMUM
4" MAXIMUM
90-1498
FIGURE 10 – Leveling
4

KNOB A
COVER B
BASE PLATE D
DEHUMIDISTAT C
ANCHOR F (x2)
SCREW E (x2)
BASE PLATE D
CUT WIRES
4”
-
6” LENGTH
ONBOARD DEHUMIDISTAT WALL MOUNT INSTALLATION
(FIGURE 12)
1. Gently pull knob (A) from the dehumidistat cover (B). The cover is
held in place by snap clips. Remove the cover by pulling carefully.
Do not touch the sensing element on the dehumidistat (C).
2. Remove 4 screws in base plate (D) and save for attaching the
provided cover plate in place of the dehumidistat.
3. Pull dehumidistat off unit until 4”- 6” of wire is outside of unit.
4. Cut wires and use metal tape to secure leads to inside of unit,
preventing contact with blower.
5. Remove the gasket from the base plate. This will be used with the
insulated cover plate installed in the next step.
6. Using the screws removed in Step 2, install the provided insulated
cover plate with gasket over the dehumidistat opening on the unit.
7. Remove the wiring access panel on unit outlet panel.
8. Unplug the REMOTE terminals from the circuit board, remove the
two wires and cut off bare leads. Once cut, the wires may remain
in the unit.
9. Run a 2-wire cable (18-22AWG) from the dehumidifier to the wall
mount location.
10. Connect cable at the dehumidifier to the REMOTE terminals. Plug
terminals into the circuit board and replace wiring access panel.
See Figure 13.
11. Use the dehumidistat base as a template to mark mounting holes
and wire access location on the wall.
12. Drill two 3/16” holes at mounting locations and a 3/8” hole at
desired wire access location.
13. Pull 2-wire cable from the dehumidifier through the wire access
opening in the wall.
14. Strip wire ends coming from the dehumidistat and dehumidifier
and connect with small, field supplied wire nuts.
15. Push excess wire and wire nuts through the access hole in the
wall. Use the supplied screws (E) and wall anchors (F) to attach
the base plate (with dehumidistat) to the wall using the top
centered hole and bottom centered slot.
16. Reassemble dehumidistat cover by snapping in place on base
plate and press on knob.
FIGURE 12 – Wall Mount
90-1466
FIGURE 13 – Dehumidistat to Unit Wiring
90-1465
5

If the dehumidifier is installed in an attic or an area requiring leak protection, the unit must be placed the supplied condensate pan with a field
supplied normally closed condensate overflow safety switch (float switch). The float switch should be wired to the FLOAT SWITCH terminals on
the circuit board on the outlet panel. The compressor is disabled when the float switch is open.
CONDENSATE PAN AND FLOAT SWITCH
MODEL 065
DEHUMIDIFIER
LEVELING FEET (4)
2" MIN.
CONDENSATE PAN
FLOAT SWITCH
(FIELD SUPPLIED)
2"
2"
2"
2"
FIGURE 15 – Install Dehumidifier
in Condensate Pan
90-1475
TO FLOAT SWITCH
FIGURE 16 – Wiring Float Switch
to Dehumidifier Control Board
90-1475
FLOAT SWITCH INSTALLATION AND WIRING
1. Install a float switch (field supplied) on any side of the condensate
pan. Refer to the instructions provided with the float switch for
proper installation.
2. The wires from the float switch are to be routed through the wiring
access panel in the back of the dehumidifier (see Figure 15).
Remove the wiring access panel and pull the FLOAT SWITCH
terminal block off the circuit board. Remove the float switch jumper
wire and wire the float switch to the FLOAT SWITCH terminals.
Plug the terminal block back into the circuit board (see Figure 16).
CONDENSATE PAN INSTALLATION
1. Raise the unit so that the bottom of the dehumidifier drain
tube is at least 2” off the floor (see Figure 15) and so that the
dehumidifier is level front to back and side to side.
2. Install the dehumidifier so that all four sides of the dehumidifier
and the drain tube are inside the condensate pan (see Figure 15).
S1-TTSCC01 WIRING
1. Repeat steps 1-8 in the ONBOARD DEHUMIDISTAT WALL MOUNT INSTALLATION section.
2. See Figure 14 to wire the S1-TTSCC01 thermostat and S1-CVENTDEH01 to the dehumidifier.
TERMINALS
DEHUM
CLS
COM
OPN
OPN
COM
B
C
R
A
A
R
C
BB
C
R
A
FLOAT
SWITCH
REMOTE
G-STAT
R-HVAC
G-HVAC
TOUCH SCREEN
COMMUNICATING
CONTROL
S1-CVENTDEH01
VENT CONTROL
DEHUMIDIFIER
CIRCUIT BOARD
FIGURE 14 – S1-TTSCC01/ S1-CVENTDEH01 to Unit Wiring
90-1537
6

as desired for comfort or economy. This will vary depending on
location and conditions. Moving the knob toward “MORE DRY”
will increase the amount of time the dehumidifier runs, making
conditions dryer. Moving the knob toward “LESS DRY” reduces the
amount of time the dehumidifier runs, allowing for higher humidity
levels. See Figure 18 for knob setpoint.
START UP/SYSTEM CHECKOUT
1. Check the wiring and restore power to the HVAC equipment
(if applicable).
2. Plug in the dehumidifier and turn on/off switch ON.
3. Check LED indicators located below the wiring access panel. Verify
the green LED is on. The green LED is on when power is applied to
the system.
4. Rotate the dehumidistat knob fully clockwise to ON position.
5. If setup is correct, the dehumidifier blower, and HVAC fan
(if applicable) will turn on. The compressor will turn on after
the dehumidifier blower has run for 3 minutes. Refer to the
TROUBLESHOOTING GUIDE if the dehumidifier blower and/or
compressor do not activate.
6. Check LED indicators. Green should remain on. If Red LED is on,
refer to the TROUBLESHOOTING GUIDE. The red LED turns on
when a fault condition is active. Possible fault conditions include
open float switch or open high temperature switch.
7. After verifying operation, rotate the dehumidistat knob counter-
clockwise to set the dehumidifier to the desired dryness level. Start
at 2-1/2 as the initial setpoint for economy, property protection
and upper end of comfort range. Change dryness level up or down
FIGURE 18 – Dehumidistat Setpoints
90-1490
WIRING SCHEMATIC
Compressor
C
Sred
org
red
brn
org
Run Capacitor
for Compressor
Control PCB Assy
Humidity Controller
brn
Impeller
Screw ground terminal
to electrical plate. 10 MFD capacitor
Power Cord
Screw Gnd to Base
On-Off Switch
blk
blk
blk
blu
brn
grn/yel
ylw
brn
blk
wht
grn
blk
blk
blk
wht
blu
blu
Rbrn
LEDs – HVAC
DEH
COMPR
23
4
5
7
6
1
FIGURE 17 – Wiring Schematic
90-1602
Item Description QTY
1Compressor Harness 1
2High Temp Cutout Switch 1
3Cutout Switch, Low Temp 1
4Control Harness 1
Item Description QTY
5Jumper Wire 1
6Impeller Jumper Wires 1
7Transformer 1
7

Johnson Controls
Unitary Products
5005 York Drive, Norman, OK 73069
Form 665507-UIM-A-0311
10009029 B2205176B 3.11
TROUBLESHOOTING GUIDE
SYMPTOM POSSIBLE REASON/TROUBLESHOOTING PROCEDURE
Red LED On
Blower & compressor not running.
Open Float Switch
• If float switch not installed, confirm jumper installed at FLOAT SWITCH terminals.
• If float switch installed, confirm switch is not open.
• Clear obstruction in drain pan/tubing.
Red LED On
Blower is on but compressor not running.
High System Pressure/High Discharge Line Temperature Due to Lack of Airflow or Excessive
Inlet Temperature
• Check dehumidifier air filter and wash or replace.
• Check for blocked ductwork and clear.
Dehumidifier blower is running but little
or no airflow.
Pressure Drop Across Dehumidifier is Higher than 0.8” w.c.
• Check dehumidifier air filter and wash or replace.
• Check for blocked ductwork and clear.
• Check if back flow damper is blocked or stuck and remove obstruction.
Blower is running but compressor is not. Coil Frosting
• Lack of or reduced airflow, check/clean filter.
• Inlet air conditions too low (below 60°F), turn down dryness setting.
Blower 3 Minute Minimum “ON” Time
• Wait 3 minutes. Compressor will not start until blower has run for 3 minutes.
Dehumidifier is not draining properly. Incorrect Drain Installation
• Check drain line for continuous downward slope.
• Verify there are no kinks, traps or debris in drain line.
• If drain trap installed, confirm trap is properly installed, clear and primed.
• Unit is not level, adjust feet.
The dehumidifier does not run. No Power to Unit – Green LED Off (15 amp circuit required).
• Check that the power switch on the dehumidifier is ON.
• Check if circuit breaker has tripped.
Dehumidistat is OFF
• Turn on dehumidistat.
Dehumidifier is loud when operating. Fan Noise
• If inlet is not ducted to HVAC return, install approximately 2’ of 8” flex duct on inlet collar.
Vibration
• Install vibration isolators under dehumidifier feet.
Dehumidifier is producing hot air. This is normal operation.
Technical Support is available Monday through Friday, 8:00 a.m. to 5:00 p.m. CST, at (877) 874-7378. Use the troubleshooting guide to help
find and correct system faults. Contact Technical Support before replacing the unit or components or for additional troubleshooting.
SEQUENCE OF OPERATION
The dehumidistat continually measures the humidity of the air in which it is located and controls to the dryness level set on the dial. When
the humidity level rises above the dial setting on the dehumidistat, the dehumidifier blower will turn on and the DEH Amber LED on the power
board (not visible unless dehumidifier cover is removed, see wiring schematic) will illuminate. The HVAC system blower, along with the HVAC
Amber LED (not visible unless dehumidifier cover is removed, see wiring schematic) will also turn on if the dehumidifier is wired to the HVAC
system. After three minutes of blower operation, the dehumidifier compressor will turn on along with the COMPR Amber LED (not visible unless
dehumidifier cover is removed, see wiring schematic). When the humidity level drops below the dial setting on the dehumidistat, both the
compressor and dehumidifier blower will turn off. If wired to the HVAC system, the HVAC blower will also turn off unless the system thermostat
keeps it running. To prevent short-cycling, the compressor will turn on 3 minutes after the blower.
The dehumidifier is equipped with an automatic defrost feature. When the evaporator coil temperature drops below the cut-out point of the frost
sensor, the dehumidifier begins the defrost cycle and the dehumidistat will turn off the compressor and the blower will continue to run. The
compressor will remain off until the evaporator coil temperature rises above the cut-in point of the frost sensor.
Table of contents