K-BUS BTIRF-02/00.2 User manual

KNX Gateway for IR _V1.2
KNX Gateway for IR,Flush mounted,2-Fold
BTIRF-02/00.2
KNX Gateway for IR,Ceiling
BTIRC-01/00.2
KNX/EIB Home and Building Control System
User manual

Attentions
1. Please keep devices away from strong magnetic field, high temperature,
wet environment;
2. Do not fall the device to the ground or make them get hard impact;
3. Do not use wet cloth or volatile reagent to wipe the device;
4. Do not disassemble the devices.

Contents
Chapter 1 General ..........................................................................................................................................1
Chapter 2 Technical Data .............................................................................................................................. 3
2.1 KNX Gateway for IR,Flush mounted,2-Fold (BTIRF-02/00.2) ............................................................... 3
2.2 KNX Gateway for IR,Ceiling (BTIRC-01/00.2) ...................................................................................... 4
Chapter 3 Dimension and Connection Diagram ............................................................................................. 5
3.1 Dimension diagram ............................................................................................................................. 5
3.2 Connection diagram ............................................................................................................................ 6
Chapter 4 Project design and Application ......................................................................................................7
Chapter 5 Parameter setting description in the ETS ...................................................................................... 9
5.1 Parameter window “DCA Note” ........................................................................................................... 9
5.2 Parameter window “General setting” .................................................................................................10
5.3 Parameter window “Channel x ” (x=1, 2) ........................................................................................... 12
5.3.1. Parameter window “Universal IR control setting” ......................................................................12
5.3.2. Parameter window “Air-condition control setting” ....................................................................15
5.4 Parameter window “Sequence mode setting” ....................................................................................23
5.5 Parameter window “Current detect setting” ...................................................................................... 26
Chapter 6 Communication Object Description .............................................................................................28
6.1 “General setting” communication object ........................................................................................... 28
6.2 “Universal IR code control” communication object ............................................................................29
6.3 “Air-condition control” communication object .................................................................................. 29
6.4 “Sequence mode” communication object ..........................................................................................31
6.5 “Current detect” communication object ............................................................................................ 32

KNX/EIB KNX Gateway for IR
1
Chapter 1 General
KNX Gateway for IR is mainly used to store the IR code learned by the IR learner. Then sending the
control telegrams to make KNX Gateway for IR send IR code via KNX device, to perform actions by
controlling IR remote control devices such as fan, Air-condition,TV, DVD and etc.
KNX Gateway for IR includes KNX Gateway for IR,Flush mounted,2-Fold (BTIRF-02/00.2) and KNX
Gateway for IR,Ceiling (BTIRC-01/00.2). Each product has 2 IR emission channels which can be set as
universal IR control or Air-condition control, up to store 300 different IR codes. In addition, KNX
Gateway for IR,Flush mounted also has 1 fold current detection function, which can confirm the on or
off status of controlled device via current status, and avoid false triggers if On and Off are controlled by
the same IR code. KNX Gateway for IR,Ceiling supports for a 360° all-round emitted.
Meanwhile, we provide configuration software tool (KNX Gateway for IR configuration)or DCA for
KNX Gateway for IR, is used for auxiliary IR code to learn, test, configure, and download the IR code to
the device. KNX bus can control IR device after ETS configuration. Note: KNX Gateway for IR
configuration is PC software running independently in the computer, and DCA is an APP plug-in of
ETS. The detailed operation please refer to the tool user manual.
In addition, auxiliary tool-- IR Learner(BTIL-01/00.2) is connected with PC by USB, is used for
learning the button function codes of IR remote control devices, such as Fan, Air -condition, TV and etc.,
and saved them in configuration tool. The IR learner can learn more than 95% IR remote control devices
in the market. The learning process is realized via operating configuration software tools, and at the
same time the IR detector of remote controller should get as close as possible to the IR learner’s, to
avoid learn failure. The IR learner has both IR receiving and sending function, test and verify whether the
learned function code is correct.
This manual provides specific technical information about KNX gateway for IR for users, as well as
assembly and programming details, and explains how to use the device by the application examples.

KNX/EIB KNX Gateway for IR
2
The functions of KNX gateway for IR are summarized as followed:
Support Universal IR control, up to 30 IR codes can be configured for each channel
Support Air-condition control, up to 266 IR codes can be configured, control functions
include: ON/OFF, temperature, mode, fan speed, swing
Support current detection function, up to 10A, can be associated to the transmitting
channel (Only KNX Gateway for IR,Flush mounted supports the function)
Support up to 16 sequence controls, each sequence supports up to 4 IR commands to be
transmitted by step
Support transmit with several times or delay time
KNX Gateway for IR,Flush mounted and KNX Gateway for IR,Ceiling only powered from KNX bus. It
is available to assign the physical address and configure the parameters by engineering design tools
ETS with .knxprod ( support edition ETS5.7 or higher ).

KNX/EIB KNX Gateway for IR
3
Chapter 2 Technical Data
2.1 KNX Gateway for IR,Flush mounted,2-Fold (BTIRF-02/00.2)
The extremely compact design enables the KNX gateway for IR to be inserted into a conventional
80mm or 86mm wiring box.
Attention: the Infrared emitter of the KNX gateway for IR must be installed in range that the IR
device can detect normally, to avoid no action.
Power supply
Bus voltage
21-30V DC, via the KNX bus
Bus current
<6.5mA, 24V
<6mA, 30V
Bus consumption
<180mW
Dynamic current
<9.5mA, 24V
<8mA, 30V
Current Detection
Current detection range
50mA-10A
Current detection
accuracy
50mA-500mA ±20mA
500mA-10A ±5%
Output
Channel
2 independent channels
Max. Transmitting
distance
2m
IR wavelength
940nm
IR emission receiving
angle
<45°
Connection
KNX
Bus connection terminal(Red/Black)
Load
(For Current Detection)
Screw terminals, Wire Range, Multi-core
0.2-1.5mm2
Single core 0.2-2.5mm2, Torque 0.4N-m
IR detector extension
cable
<10m
Operation and
display
Programming button and
Red LED
For assigning the physical address
Green LED flashing
For displaying application layer running normally
Temperature
Operation
– 5 °C ... 45 °C
Storage
– 25 °C ... 55 °C
Transportation
– 25 °C ... 70 °C
Ambient
Humidity
<93%, except dewing
Installation
Mounting
In wiring box, 80×80mm or 86×86mm
Dimension
φ53×23.5mm
Weight
0.04kg

KNX/EIB KNX Gateway for IR
4
2.2 KNX Gateway for IR,Ceiling (BTIRC-01/00.2)
The extremely compact design enables the KNX Gateway for IR to be mounted in the ceiling. 360°
full direction transmitting.
Attention: the Infrared emitter of the KNX gateway for IR must be installed in range that the IR
device can detect normally, to avoid no action.
Power supply
Operation voltage
21-30V DC, via the KNX bus
Bus current
<8mA, 24V
<7mA, 30V
Bus consumption
<210mW
Dynamic current
<14mA, 24V
<12mA, 30V
Output
IR wavelength
940nm
Radius distance
<3m
Installation
Height
<4m
Connections
KNX
Bus connection terminal(Red/Black)
Operation and display
Programming button and
Red LED
For assigning the physical address
Green LED flashing
For displaying application layer running normally
Temperature
Operation
– 5 °C ... 45 °C
Storage
– 25 °C ... 55 °C
Transportation
– 25 °C ... 70 °C
Ambient
Humidity
<93%, except dewing
Dimension
91 × 76 × 82.25mm
Weight
0.05kg

KNX/EIB KNX Gateway for IR
5
Chapter 3 Dimension and Connection Diagram
3.1 Dimension diagram
Fig.3.1(1) KNX Gateway for IR,Flush mounted,2-Fold (BTIRF-02/00.2)
Fig.3.1(2) KNX Gateway for IR,Ceiling (BTIRC-01/00.2)

KNX/EIB KNX Gateway for IR
6
3.2 Connection diagram
Fig.3.2(1) KNX Gateway for IR,Flush mounted,2-Fold (BTIRF-02/00.2)
①Programming LED
②Programming button
③KNX bus connection terminal
④Device load connection terminals, if require current detection
⑤Connectors for Infrared emitter cable
Fig.3.2(2) KNX Gateway for IR,Ceiling (BTIRC-01/00.2)
①KNX bus connection terminal
②Programming button
③Programming LED
④Installation height: <4m
⑤Transmit radius: <3m
⑤
④
R
H

KNX/EIB KNX Gateway for IR
7
Chapter 4 Project design and Application
General Setting
General setting includes device In operation setting and channel function setting. In operation
setting is used for indicating whether the device application layer running normally. Channel function
can be configured Universal IR control or Air-condition control, up to set 2 channels. But only one of the
channels is supported to Air-condition control. That is when Channel 1 is used for Air-condition control,
and Channel 2 is only used for Universal IR control; if Channel 1 is used for Universal IR control, and
Channel 2 can be used for Air-condition control.
Universal IR control
Each channel up to support 30 IR code configurations is used for universal control, such as Fan, TV,
DVD and etc. You can set the object datatype 1bit or 1byte, the object value, the corresponding IR code,
and the status feedback to trigger the IR code to emit. Each IR code can set emission time and sending
count.
In addition, KNX Gateway for IR,Flush mounted also supports whether to connect with current
detection status, and you can decide whether to emit IR code according to the current switch status
after connecting.
Application
Max.number of
communication
objects
Max. Number of
group address
Max. number of
associations
KNX Gateway for IR,Flush mounted,2-Fold/1.0
KNX Gateway for IR,Ceiling/1.0
167
500
500

KNX/EIB KNX Gateway for IR
8
Air-condition device control
Support the similar control way of universal Air-condition gateway, that is built-in status save and
logic operation, can be controlled independently;
Support the function control and the status feedback: Air-condition switch, setpoint temperature,
modes, fan speed, and swing;
Set the connection with the window sensor, turn off Air-condition after delay a time when receives
the window open command, to save energy;
Set the connection with the presence sensor, turn off Air-condition after delay a time when receives
the room unoccupied command, to save energy.
Sequence sending function
Up to support 16 sequence controls. Each sequence supports 1 bit or 1byte scene value trigger, up
to support 4 IR commands binding sent, and each command can be set the delay time, the count and
the channel of emission.
Current function( Only the Flush mounted support)
Supports a current detection function of up to 10A, can be connected with emission channel. Users
can set the setpoint current threshold value (decided by the technology for the load), to define the
power on/off status of controlled device. Current detection value and switch status can be both sent to
the bus.

KNX/EIB KNX Gateway for IR
9
Chapter 5 Parameter setting description in the ETS
This chapter takes KNX Gateway for IR,Flush mounted,2-Fold as example to explain the ETS
system parameter setting of KNX gateway for IR. And the Ceiling and the Flush mounted are mainly
different in without current detection function.
5.1 Parameter window “DCA Note”
Fig.5.1 “DCA Note” parameter window
A noting message. Remote IR code learning and downloading must use IR Learner via DCA
software, you can download the DCA form MyKNX online shop or get it from the manufacture. In
order to use DCA normally, ETS must run in compatibility mode, which should be actived via ETS
Apps window in ETS5, as shown as follow figure.

KNX/EIB KNX Gateway for IR
10
5.2 Parameter window “General setting”
Fig.5.2“General setting” parameter window
Parameter “Send cycle of “In operation”telegram [1...240s, 0 = inactive]”
This parameter is for setting the time interval when this module cycle send telegrams through the
bus to indicate this module in normal operation. When set to “0”, the object “in operation” will not send
a telegram. If the setting is not “0”, the object “In operation” will send a telegram according to the set
period time with logic “1” to the bus. Options: 0...240s, 0= inactive
As to reduce the bus load as much as possible, the maximum time interval should be selected
according to actual needs.
Channel setting
Parameter “Channel x function”(x=1, 2)
This parameter is for setting the channel function of KNX gateway for IR. Options:
Disable
Universal IR control
Air-condition control
Note: When channel 1 is set as Air-condition control, and channel 2 is only set as Universal IR
control; If channel 1 is set as Universal IR control, and channel 2 can be set as Air-condition control or
Universal IR control.

KNX/EIB KNX Gateway for IR
11
Parameter “Check current status when emitting”
This parameter is visible when channel function is selected as “Universal IR control”. Set whether
to connect with current detection status. It decides the On or Off status of the controlled device
according to the current status, to avoid false triggering when the same IR code is used for On and Off.
If On and Off use different IR codes to control, no need to set connection. Options:
Disable
Local
External
Disable: No connection;
Local: local connection, the own current detection function of the device is used;
External: external connection, give the current status of external device detection to the device.
——Parameter “Monitoring period of current ON/OFF [0..255,0=inactive]min”
This parameter is visible when current detection status is selected as “External”. Set the
monitoring period of external current switch status. If current switch status from the external device is
not received during monitoring period, wrong current detection of external will be considered.
Options: 0..255, 0=inactive
——Parameter “Reply error of current detection”
This parameter is visible when the monitoring period>0. When external current detection is error,
set whether to send error telegram to the bus. Sent when status changes. Options:
None
0=no error/1=error
1=no error/0=error
None: no sending.
0=no error/1=error: when error, object “CHx-External error report” sends telegram “1” to the bus,
and no error sends “0”;
1=no error/0=error: when error, object “CHx-External error report” sends telegram “0” to the bus,
and no error sends “1”.

KNX/EIB KNX Gateway for IR
12
Function setting
Parameter “Sequence mode function”
This parameter is for setting whether to enable sequence mode function, display the relevant
window after selected.
Parameter “Current detection function”
This parameter is for setting whether to enable current detection function, display the relevant
window after selected.
5.3 Parameter window “Channel x ” (x=1, 2)
5.3.1. Parameter window “Universal IR control setting”
Fig.5.3.1(1) “Universal IR control setting” parameter window
Fig.5.3.1(2) “IR control x” parameter window

KNX/EIB KNX Gateway for IR
13
Parameter “IR control x”(x=1~30)
This parameter is for setting whether to enable IR control, display the relevant window after
selected. Each channel up to support 30 IR controls.
Parameter “Description (max 30char.)”
This parameter is for setting the custom description of IR code, and the description of
corresponding setting window and object name will also change. Up to 30 characters can be input.
Parameter “Object datatype of trigger value”
This parameter is for setting the object datatype for triggering the IR code emit. Options:
1bit [On/Off]
1byte [0..255]
——Parameter “Trigger value”
This parameter is for setting the received value when IR code emission is triggered. The value is
based on the trigger object datatype:
When select 1 bit, options:
1 [On]
0 [Off]
Both 1 and 0
When select 1byte, options: 0..255
Parameter “Assign an IR code NO.[1..300]”
This parameter is for setting the emitted IR code, with a total selection of 300 IR codes. Options:
1..300
Parameter “Delay time for emitting [0..255]*0.1s”
This parameter is for setting the delay time of IR code emission. Options: 0..255
Parameter “Count of emitting [1..100]”
This parameter is for setting the count of IR code emission. Options: 1..100

KNX/EIB KNX Gateway for IR
14
Parameter “Emitting IR code when current status is”
This parameter is visible when the current detection status is selected “Local” or “External”. Set
whether to emit IR code according to the current status. Options:
1 [On]
0 [Off]
Both 1 and 0
1 [On]: if current status is ON, emit IR code, otherwise not.
0 [Off]: if current status is OFF, emit IR code, otherwise not.
Both 1 and 0: both emit when the current status is On or Off.
Parameter “Status response”
This parameter is for setting whether to reply a status value to the bus after the device emitting IR
code, to inform emission is completed. Options:
No
Response value '1'
Response value '0'
According control value
No: no responding;
Response value '1': object “IR Response value” replies the telegram value “1”;
Response value '0': object“IR Response value”replies the telegram value“0”;
According control value: object“IR Response value” the telegram value of response is the same as
trigger value.

KNX/EIB KNX Gateway for IR
15
5.3.2. Parameter window “Air-condition control setting”
Fig.5.3.2(1) “Air-condition control setting” parameter window

KNX/EIB KNX Gateway for IR
16
Fig.5.3.2(2) “Air-condition control setting” parameter window
参数
“Remote model NO.”
This parameter is for setting the remote model number of Air-condition. Options: 0..255
Note: This parameter is a preset parameter. Do not support to input remote model number
currently.
Parameter “Description (max 30char.)”
This parameter is for setting the custom description of Air-condition, and the description of
corresponding object name of Air-condition will also change. Up to 30 characters can be input.
Parameter “Assign IR code NO. for OFF [1..300]”
This parameter is for setting the IR code number when power off Air-condition. Options: 1..300
Parameter “Assign IR code NO. for ON [1..300]”
This parameter is for setting the IR code number when power on Air-condition. Options: 1..300

KNX/EIB KNX Gateway for IR
17
Initial configuration for ON
Note: If the configuration of the initial status is not consistent with the IR code
learned by ON, there will be inconsistencies in the status of the realized control and the
feedback from the device to the bus. The control is controlled by the IR code and the
feedback is fed back according to the configuration of the initial status.
The following parameters are for setting the initial status when power on Air-condition.
——Parameter “Temperature”
This parameter is for setting the temperature of Air-condition when power on. Options:
16°C
17°C
...
30°C
——Parameter “Mode”
This parameter is for setting the control mode of Air-condition when power on. Options:
Heating
Cooling
Dehumidification
Fan
Auto
——Parameter “Fan speed”
This parameter is for setting the fan speed of Air-condition when power on. Options:
Auto
Low
Medium
High
This manual suits for next models
1