Kaco proLOG M User manual

Operator’s Manual
Installation Instructions
KACO-proLOG M / XL

1About this document 3
1.1 Pertaining documents 3
1.2 Attachment and Maintenance of documents 3
1.3 Symbols used in this document 3
1.4 UL Certification 3
1.5 Type Label 3
2Safety Information 3
2.1 Transportation 3
3Notes concerning Installation and Operation 4
3.1 Factory guarantee and liability 4
4Installation 4
4.1 Selecting the appropriate place of installation 4
4.2 Installation of the data logger 4
4.3 Jumper switch 4
4.4 Connections 5
4.4.1 Voltage supply 5
4.4.2 KACO-go 5
4.4.3 Telephone 5
4.4.4 24V external (rear port) 5
4.4.5 Ethernet (for M and XL devices) 5
4.4.6 RS485 connection 5
4.4.7 D0 digital output 6
4.4.8 Analog / digital inputs 6
4.5 Pin allocation 7
5Start-up 7
5.1 Start-up / login of KACO-proLOG via PVI-web 7
5.2 Procedure 7
5.3 KACO-proLOG XL display menu and Status LEDs7
5.3.1 Description of the 4 Status LEDs: 7
5.3.2 Display menu 8
5.3.3 Structure of the display menu 9
5.4 KACO-proLOG M, L LED menu 12
6Connection buildup 13
6.1 Hardware and software requirements 13
6.2 Connection to KACO-proLOG with Ethernet (M and
XL) 13
6.3 Connecting to KACO-proLOG with modem 13
6.3.1 Windows 95/98 14
6.3.2 Windows 2000 16
6.3.3 Windows XP 18
6.4 KACO - Web (Optional) 21
7Menu description 22
7.1 General information 22
7.2 Online values 23
7.2.1 Analog/Digital Inputs 23
7.2.2 Current sensors 24
7.2.3 Inverter Survey 24
7.2.4 Inverter details 24
7.3 Status 24
7.3.1 Plant messages 24
7.3.2 Inverters 25
7.4 Configuration 25
7.4.1 Plant data 25
7.4.2 Standard contact 26
7.4.3 Date / Hour 26
7.5 Admin - Monitoring 27
7.5.1 Network 27
7.5.2 Contact addresses 28
7.5.3 Switching output 29
7.5.4 Plant messages 29
7.5.5 Inverters 29
7.5.7 Status Alarms 30
7.6 Admin Measurement 30
7.6.1 Analog channels 30
7.6.2 Digital channels 31
7.6.3 Current sensors 31
7.6.4 Inverters 31
7.6.5 Energy – digital channels 31
8Sample Configuration 32
8.1 Analog channels 32
8.1.1 Voltage input 32
8.1.2 Current Input 32
8.2 Digital inputs 32
8.3 Alarm criterion 32
8.3.2 Parameterization of the measuring device33
8.4 Programming criteria based on the example of an
inverter comparison 34
9List of Abbreviations 35
10 Technical data 36
KACO SOLAR INC. 2 Operator’s Instructions KACO-proLOG

1 About this document
The following information will guide you through the
entire operator’s manual. Further documents will be
valid in conjunction with these operating and installation
instructions.
We shall not be liable for any damage caused by
non-adherence to the instructions given in this
manual.
1.1 Pertaining documents
During the installation of the data logger please observe
all assembly and installation instructions for
components and other parts of the system. These
instructions are shipped together with the respective
installation components or supplementary equipment.
1.2 Attachment and Maintenance of documents
Please keep these operating and installation
instructions in a safe place to ensure that they are
available if needed.
1.3 Symbols used in this document
Please observe the safety information provided in this
manual when operating your inverter!
Note!
Useful information and remarks!
Important!
1.4 UL Certification
CE labeling is used to document that the KACO
proLOG data logger indicated on the type label meets
the fundamental requirements according to UL
requirements.
1.5 Type Label
The type label indicating the exact device designation is
located on the right side of the housing.
2 Safety Information
The data logger system for photovoltaic installation
must only be connected by authorized skilled
personnel.
Always make sure that leads and cables do not carry
hazardous live voltages before routing or establishing
connections..
Operators must read this manual carefully and
familiarize themselves with the device prior to putting it
into operation.
All local regulations and provisions must be observed
when operating this device.
Damaged instruments must be made inoperable
immediately and/or checked by authorized skilled
personnel. Manipulating or modifying the
devices/instruments is not permissible.
Opening the device is not permissible.
The safety of the device and operator will no longer be
ensured if the device is not operated according to the
safety instructions stated in this manual.
The proper and safe operation of the device/instrument
requires proper transportation, storage, erection and
assembly, as well as careful operation and
maintenance.
2.1 Transportation
Caution!
Potential hazard for the product
and environment!
The KACO-proLOG data logger is subjected to
extensive testing and inspection in our test field, so as
to ensure the superb quality of our products. Our data
loggers leave our factory in a proper electrical and
mechanical condition. Special packaging ensures that
nothing can happen during the transport to our
customers. Nevertheless, transport damage may not be
ruled out completely. In this case, the forwarding
agent/carrier will be responsible.
Please check the data logger carefully on arrival.
Should you discover any visible signs of damage on the
packaging, which imply that the data logger may be
damaged, or should you find any visible signs of
damage on the data logger itself, please notify your
responsible forwarding agent/carrier immediately.
KACO SOLAR INC. will provide assistance as
necessary. However, INVitten damage reports must be
received by the forwarding agent within six days after
receipt of the goods at the latest.
Use exclusively the original packaging for returning the
data logger – only this material will ensure safe
transportation.
KACO SOLAR INC. 3 Operator’s Instructions KACO-proLOG

3 Notes concerning Installation and
Operation
3.1 Factory guarantee and liability
KACO SOLAR INC. grants a guarantee of two years on
KACO-proLOG, starting from the date of installation.
During this time, KACO SOLAR INC. guarantees the
proper function of the devices and free repair in the
event that a defect should occur, which we are
accountable for.
Should your device show a defect or malfunction during
the guarantee period, please contact your specialist
dealer or, respectively, your installation expert.
Guarantee claims shall be excluded in the following
cases:
-Use of the device for other than the intended use
(normal use)
-Improper use and installation that does not comply
with the required standards
-Improper operation
-Operation of the device with defective protective
equipment
-Manipulation of the device or makeshift repairs
-Influence of foreign objects or Act of God (lightning,
overvoltage, tempest, fire)
-Inadequate ventilation of the device
-Non-adherence to the relevant safety instructions
(VDE (Association of German Engineers), a.o.
-Transport damage
All guarantee claims shall be handled at the premises of
KACO SOLAR INC.. To this end, return transport shall
be effected, as far as possible, in the original or
equivalent packaging. The costs for these services
cannot be borne by KACO SOLAR INC..
Guarantee claims shall only be compensated by KACO
if the damaged device is returned to KACO together
with a copy of the invoice issued to the consumer by the
specialist dealer. The type label on the device must be
fully legible. In the event of noncompliance KACO
reserves the right to deny guarantee services.
4 Installation
4.1 Selecting the appropriate place of installation
The KACO-proLOG data logger should be installed in
the vicinity of a telephone or Ethernet connection and
110V mains connection.
To avoid damage of your KACO-proLOG data logger
or damage of your internal house wiring, please
observe the following rules when selecting the place of
installation:
-
-
-
-
The KACO-proLOG data logger must not be installed
outdoors or in a humid environment.
It must be protected against wetness and direct
sunlight.
The ambient temperature must range between
32°F and +131°F.
Boreholes must be away from other house wiring
connections, e.g. power, gas or water lines.
KACO-proLOG should rest evenly on a flat surface
so as to avoid damage to the enclosure.
4.2 Installation of the data logger
The device is suitable for wall installation. The
boreholes can be marked as shown in the sketch
below. The distance between the screws of the
suspension/support and the wall should be approx. 3
mm.
Place KACO-proLOG over the screw heads and then
carefully pull it down. Subsequently, fasten the lower
part of KACO-proLOG by means of a third screw.
Borehole diagram (inches)
4.3 Jumper switch
The KACO-proLOG board has three jumper switches,
which can be used to set the following operating
modes:
OPTO <-> BEEPER
The jumper can be set to OPTO or BEEPER.
OPTO: Only the D0 output is activated.
BEEPER: The D0 output and the internal beeper are
activated.
The BEEPER should only be activated if
the D0 output is used as an alarm output!
PVI <-> PVI+PVIgo
The jumper can be set to PVI or PVI+PVIgo.
PVI: The RS485 signal is only applied to terminal
“B A RS485“. KACO solar inverters may be connected.
PVI+PVIgo: The RS485 signal is applied to terminal
“B A RS485“ and RJ45 ports “PVI-go On“. Now the
current sensors and solar inverters can be operated
together.
9
6.6 8.8
3.6
4.5
KACO SOLAR INC. 4 Operator’s Instructions KACO-proLOG

Make sure first to connect KACO-go and
then the solar inverters. The RS485 is
internally bridged from the PVI-go port to
the “B A RS485“ terminal. KACO and PVI inverters can
now be operated together.
24V internal <-> 24V external
The jumper can be set to INTERNAL or
EXTERNAL.
This jumper refers to the front port of the “24 V
external” connection.
INTERNAL: KACO-go will be supplied via the internal
power supply of KACO-proLOG.
EXTERNÁL: An external voltage supply for KACO-go
may be connected to the “24V external“ terminal.
4.4 Connections
4.4.1 Voltage supply
KACO-proLOG is connected to 110Vac
and supplied via the integrated power
supply. The 24 VDC output voltage of the
power supply is applied to the terminal
marked “24V external” for external
sensors.
4.4.2 KACO-go Up to 100 current sensors can be
connected at the RJ45 “PVI-go“
ports (Powador-go). The current
sensors can be used , e.g. to
integrate external inverters into
the monitoring system.
Schematic diagram for wiring solar inverters and
current sensors:
4.4.3 Telephone
The data loggers are equipped with an
internal modem (analog or ISDN). The
required cable connection is included in the
scope of delivery.
4.4.4 24V external (rear port)
This port ensures the supply of external
sensors via the internal power supply (max.
230mA). The port is located between the
analog/ISDN modem and Ethernet interface.
4.4.5 Ethernet (for M and XL devices)
In addition to the integrated modem an
Ethernet network connection is
available.
When establishing a direct connection
to a PC/Laptop, make sure to use a
cross-over cable. Connections to a
hub or switch will require a standard
patch cable.
KACO-proLOG can be reached under IP
192.168.100.50 (factory setting); the
k is 255.255.255.0. Detailed instructions
on establishing a connection to an Ethernet device are
given in Section 6.2.
network mas
4.4.6 RS485 connection
KACO- The RS485 Bus is connected to the A/B screw-
type terminals. The data logger uses this
connection to communicate with the external
bus lines (solar inverters or current sensors).
The current sensors are connected to the
provided ports (KACO-go / PVI-go).
proLOG
RS 485
B A
INV 3
KACO-go
(
RJ45
)
INV 2
INV 1
KACO-
g
o 3
KACO-
g
o 2
KACO-
g
o 1
KACO SOLAR INC. 5 Operator’s Instructions KACO-proLOG

Schematic for wiring solar inverters:
The jumper-switch has to be on “PVI-
PVIgo” when the inverter and the current
sensors are connected. In case of inverter
connection only the jumper hast to stay at “PVI”.
4.4.7 D0 digital output
The digital output may be used as an alarm
output to trigger signal transmitters, or as a
pulse output for the connection of a display.
To configure this function you must connect to
KACO-proLOG and make the necessary
adjustments via the browser (Admin Monitoring
-> switch output). The output has been
designed as an optocoupler output (make contact); so
external voltage must be applied as necessary. The
max. load is 50 mA.
Connecting a display to D0
Connecting a signal transmitter to D0
4.4.8 Analog / digital inputs
destroy the sen
The device is equipped with 4 (XL) or,
respectively, 1 (M, L) analog inputs,
which are adjusted for voltage
measurements ranging from 0..10V.
In addition, direct connection of a PT
1000 temperature sensor is enabled. The device has to
be configured accordingly (also please refer to “6.4
PVIweb optional).
KACO-proLOG
RS 485
B A
INV 3
INV 2
INV 1
Voltages greater than 12VDC or reversed poles can
se input!
4 (XL) or, respectively, 1 (M, L) can be
used to pick up digital counter inputs
(max. frequency: 14 Hz). This will
require an interface according to S0
specification.
External voltages greater than 24 VDC
or reversed poles can destroy the
sense input. The 24VDC supply is
available starting from the D0+
terminal.
Connection of an insolation (solar radiation)
sensor and energy meter:
Input AI1 has been pre-configured for the connection of
an insolation sensor. Digital input DI1 has been pre-
configured for the connection of a grid-feeding meter.
KACO-proLOG
24V
+ -
+ -
DI1
+ -
AI1
Signal
GND
24V
+
Mete
r
Insolation
sensor
Si-12TC
Energy
mete
r
D0
+ - + -
KACO-proLOG Display
Pulse input
KACO-proLOG
+ -
D0
+ -
24V
+ -
Signal transmitter
KACO SOLAR INC. 6 Operator’s Instructions KACO-proLOG

4.5 Pin allocation
Below is a detailed description of the pin allocations of
all interfaces.
RJ45
Links: Pin 1
Rechts: Pin 8
TelephonePIN Analog ISDN
1
2
3 STA / (B2)
4 b= minus SRA / (B1)
5 a= plus SRB / (A1)
6 STB / (A2)
7
8
Ethernet
PIN Name Function
1 TPTX- Transmit Data
2 TPTX+ Transmit Data
3 TPTX+ Transmit Data
4
5
6 TPTX- Transmit Data
7
8
KACO-goPIN Name Function
1 +12V…24V Supply
2 +12V…24V Supply
3 +12V…24V Alarm Output
4 b= plus Data line
5 a= minus Data line
6 GND Alarm output
7 GND Supply
8 GND Supply
5 Start-up
5.1 Start-up / login of KACO-proLOG via PVI-web
On-site configuration of the data logger is
NOT necessary . All you have to do is
ensure that all sensors are connected
properly and the telephone connection is working.
The configuration is carried out via the
remote data connection (DFÜ). Please
fill in the enclosed Application
formsheet after successful installation.
5.2 Procedure
Step 1: Connecting the sensors and inverters
Prior to switching-on the device all sensors must be
completely connected and ready for operation. The
RS485 must also be properly connected.
Step 2: Telephone or Ethernet connection
Prior to start-up the telephone connection should be
tested for proper functionality; then the wiring should be
carried out according to Section “4.1 – Connections.”
Important details on how to establish Ethernet
connections are given under “4.1.4 Ethernet.”
Step 3: Switching-on the KACO-proLOG
Enable supply voltage (the “Power” LED must be
permanently ON after applying supply voltage).
The system needs approx. 2 minutes to
complete the initialization phase. This
process is comparable to the boot phase
of a PC. The end of the boot phase is signaled by the
status LED. This LED is OFF during the boot phase,
and starts flashing when the boot phase has been
completed.
Step 4: Checking the Status LED
On completion of the startup phase the status LED will
provide information on the status of your device:
Status LED OFF ->
System start
Status LED flashes at regular intervals ->
System ready
Optional step: Checking the measured values via
the browser:
If you should have a PC available after startup you will
be able to connect to the data logger via modem or
Ethernet (please refer to Section 6 “Connection
buildup.”
Subsequently, you can check the measured values
directly via the browser. More detailed instructions are
given in Section 7.2, “online data.”
5.3 KACO-proLOG XL display menu and Status
LEDs
5.3.1 Description of the 4 Status LEDs:
“Power” LED
….flashes continuously: This indicates that the device is
supplied with voltage.
… is OFF: voltage supply fault.
“Status” LED
… is OFF. System is starting up; the boot phase is in
progress.
… is flashing: system load successful; normal
operation.
KACO SOLAR INC. 7 Operator’s Instructions KACO-proLOG

“Connect” LED“
…is OFF: Currently no connection via analog modem,
ISDN or GSM.
…flashes: establishing a connection to the desired
number.
…Is permanently ON: connection successful.
“Alarm” LED:
… is OFF: normal operation.
…is permanently ON: the device returns an alarm
signal via alarm output D0 (if configured).
5.3.2 Display menu
The display integrated in the XL version can be used for
such entries as the IP address of the Web log, or for
searching inverter types.
In addition, the current measuring values and stored
energy yields can be retrieved during operation.
Navigating through the display menu:
Enter: Confirm your entry or change to the next
lower menu level or to the next
entry point
Up arrow – select a menu point above the
current row; increase value
Down arrow: Select a menu point below the
current row; reduce value
ESC Escape: Abort your entry or return to the
previous menu level
KACO SOLAR INC. 8 Operator’s Instructions KACO-proLOG

5.3.3 Structure of the display menu
KACO SOLAR INC. 9 Operator’s Instructions KACO-proLOG

Description of menu items:
Overview
Provides information about the current IP address of the
Ethernet connection. Also enables retrieval of the field
strength (for GSM devices).
yEthernet
Current IP address: Shows the IP address currently
used within the LAN
yGSM
Field strength: Indicates the field strength.
Settings
The “communications” section can be used to set
various connection parameters, e.g. change IP address
or set the PIN code of the GSM card.
The “data logger” section can be used to start an
inverter scan, depending on which driver is activated.
In addition, the data logger can be reset to factory
settings.
Communication
Ethernet
Boot protocol
None:
No boot protocol is used
DHCP (Dynamic Host Configuration
Protocol) :
A DHCP server assigns an IP address
to KACO-proLOG
BOOTP (Bootstrap protocol):
BOOTP server assigns an IP address
to KACO-proLOG
RARP (Reverse Address Resolution
Protocol):
RARP server assigns an IP address
to KACO-proLOG
Static IP address:
Indicates the IP address used if no boot protcol
has been selected
Network mask:
Indicates the network mask being used;
(unless another mask is assigned by the
BOOTP or DHCP server)
Gateway:
Indicates the gateway being used
(unless another assignment has been made)
Modem/ISDN/GSM
Local IP address:
Defines the IP address of KACO-proLOG
in the WAN.
Remote IP address:
IP address to be assigned to the caller via the
WAN.
Subnet mask:
Defines the subnet mask in the WAN
(only for ISDN); Setting of MSN
PIN Code (only for GSM):
Setting of GSM PIN
Call-Accepted ON (analog only):
Active call-accepted restrictions are deleted.
yData logger
Inverter scan
Allows searching (scanning) for inverters
Set factory settings:
Allows resetting to factory adjustments
ISDN:
Deletes MSN
Analog:
Enables “call accepted” function
Ethernet:
Sets IP address to 192.168.10.90
GSM:
Deletes the GSM PIN
Current values
Shows the current measuring values.
Various data can be retrieved, depending on which
devices are connected:
yAnalog values
Shows analog measuring values
yDigital values
Shows the digital measuring values
yCurrent sensors
Shows the measuring values of the current
sensors
yInverter
Shows the latest output of the individual inverters.
KACO SOLAR INC. 10 Operator’s Instructions KACO-proLOG

Installation/Plant
The “Power/Energy” field shows the total output of
the plant as well as the energy delivered over
various different periods of time.
The “Alarms/Errors” field provides messages about
recognized system errors.
yEnergy DI
If at least one digital channel is selected
to calculate the total output of the installation
the respective measuring data will be displayed in
the following sub-menus:
Latest Output
Daily energy yield
Previous day’s energy yield
Monthly energy yield
Annual energy yield
Total energy yield
yInverter energy
If inverters are selected for the
calculation of installation output and energy yield,
the respective values will be displayed in the
following submenus:
Latest output
Daily energy yield
Previous day’s energy
Monthly energy yield
Yearly energy yield
Total energy yield
yAlarms/errors
Communication:
Error during modem connection buildup
System:
A system error has occurred.
Measuring channels:
Error during the detection of measuring
channels.
Set pasword as 0030 to use a KACO-
web plant.
KACO SOLAR INC. 11 Operator’s Instructions KACO-proLOG

5.4 KACO-proLOG M, L LED menu
Instead of a display, KACO-proLOG M and L use
LEDs to indicate the condition of the device.
How to navigate within this menu is showing below:
Description of LEDs in the “Communications“ submenu
No Dialtone – the device is unable to receive an external
exchange line.
No Carrier – Modem has lost or not recognized its carrier
signal.
No Answer – The called number does not answer.
Busy – The called number is busy.
Sum of error messages. This message will appear if an error
has occurred during initialization or if an unkown error or
general error has occurred.
KACO SOLAR INC. 12 Operator’s Instructions KACO-proLOG

6 Connection buildup
6.1 Hardware and software requirements
If KACO-proLOG is equipped with an internal analog
modem, an analog modem will be needed for
communication. Similarly, if KACO-proLOG has an
internal ISDN modem the PC must also have an ISDM
modem in order to communicate. A table showing the
possible connections is shown on page 35.
Hardware
Standard PC with modem (analog or ISDN) for KACO-
proLOG with modem, or Ethernet network connection
for KACO-proLOG with Ethernet connection, enabling
email data transfer via the network.
Software
Internet-Browser: starting from Internet Explorer version
5.5 / Netscape 6.1 activated with Java Script.
6.2 Connection to KACO-proLOG with Ethernet (M
and XL)
KACO-proLOG and the PC must be connected to the
same network. IP addresses and the network mask of
KACO-proLOG and, respectively, the PC , must be
stored in the same address memory. If these
requirements are met, KACO-proLOG can be
addressed at its IP address via an Internet browser
(e.g. Mozilla or Internet Explorer).
The IP address can be set via “Network Connections”
via the system control of your PC.
KACO-proLOG must be addressed with
the correct IP address and network mask.
The standard IP address is
192.168.100.50 with a network mask of 255.255.255.0.
This means that KACO-proLOG can be addressed via
a PC having the IP address of 192.168.100.xxx and
network mask of 255.255.255.0. “xxx“ stands for any
number between 1 and 254, whereas number 50 is
already pre-assigned to KACO-proLOG.
Example:
IP address of KACO-proLOG: 192.168.100.50
IP address of network card (PC): 192.168.100.55
The settings of the IP address, network mask and
gateway KACO-proLOG can be changed via “Admin –
monitoring” -> network -> settings. The indicated IP
address may vary depending on the selected setting.
This IP address must then be used instead of the
standard address (as shown above) in the browser.
After modifying, saving the settings and
reset, KACO-proLOG can be reached
via the new parameters.
The IP-adress for returning to factory settings is:
192.168.10.90
6.3 Connecting to KACO-proLOG with modem
A new data transfer line (DFÜ) must be set for a PC to
communicate with KACO-proLOG. This setup may vary
depending on the type of operating system - below
please find instructions for Windows 95/98, Windows
2000 and Windows XP.
KACO SOLAR INC. 13 Operator’s Instructions KACO-proLOG

6.3.1 Windows 95/98
Step 1
Select “START / PROGRAMS / ACCESSORIES /
COMMUNICATION“ to access the menu item “Network
Connections.”
Step 2
Select “Establish new connection” and assign a name
to the new connection to be established. In addition,
enter the modem you wish to use for this connection. (A
suitable modem must be connected to your PC and
installed).
If KACO-proLOG is equipped with an internal analog
modem, an analog modem or ISDN modem with analog
simulation must be used for communication.
If KACO-proLOG is equipped with an internal ISDN
modem, the PC must likewise be equipped with an
internal ISDN modem for communication.
Step 3
Click “NEXT” to set up your connection. Use the
“GENERAL” tab to enter the phone number of the line
you wish to communicate with
KACO-proLOG.
All other settings already exist as defaults and do not
need to be changed.
Please note that an external call prefix may
be necessary when entering the telephone
number. In most cases, this external call
prefix will be assigned a preceding “0”.
KACO SOLAR INC. 14 Operator’s Instructions KACO-proLOG

Step 4
Double-click the new connection to open the “Connect
to” dialog. Click the “Connect” button to initiate the
dialing process. “Admin” must be entered as the
user name and password.
[ w ], [ , ] and blank characters between the
digits of the telephone numbers are
commands for the telephone system (wait
until external call prefix is established).
More detailed information is given in the description of
the telephone system.
Step 5
After establishing the connection the browser is opened
(e.g. Netscape 6.1) and the IP address of the device is
entered. The standard address is: http://192.168.200.1.
Confirm this address to access to the start page of
KACO-proLOG.
KACO SOLAR INC. 15 Operator’s Instructions KACO-proLOG

6.3.2 Windows 2000
Step 1
Click “START / PROGRAMS / ACCESSORIES /
COMMUNICATION“ to access the menu item “(Network
and Remote Communication).”Activate this menu item
to open the “DFÜ Network” dialog.
Step 2
Select “Establish new Connection” and assign a name
of your choice to the new connection to be established.
In addition, enter the modem you wish to use for this
connection. (A suitable modem must be connected to
your PC and installed).
If KACO-proLOG is equipped with an internal analog
modem, an analog modem or ISDN modem with analog
simulation must be used for communication.
If KACO-proLOG is equipped with an internal ISDN
modem, the PC must likewise be equipped with an
internal ISDN modem for communication.
Step 3
Click “PROCEED“ or set up your connection. Use the
“GENERAL” tab to enter the phone number of the line
you wish to communicate with
KACO-proLOG.
All other settings already exist as defaults and do not
need to be changed.
KACO SOLAR INC. 16 Operator’s Instructions KACO-proLOG

Please note that an external call prefix may
be necessary when entering the telephone
number. In most cases, this external call
prefix will be assigned a preceding “0”.
Step 4
Double-click the new connection to open the “Connect
to” dialog. Click the “Connect” button to initiate the
dialing process. “Admin” must be entered as the
user name and password.
[ w ], [ , ] and blank characters between the
digits of the telephone numbers are
commands for the telephone system (wait
until externall call prefix is established).
More detailed information is given in the description of
the telephone system
In the dialog “Connect to KACO-proLOG”, click
(Features) to open another window.
Highlight [Internetprotokoll (TCP/IP)] and click
(Features).
In the new dialog (Features of Internet Protocol
TCP/IP), highlight the (Use the following IP address)
and enter the IP address 192.168.200.51. Enter
1.0.0.0. for [DNS-Server].
KACO SOLAR INC. 17 Operator’s Instructions KACO-proLOG

Step 5
After successful buildup of the connection the browser
is opened (e.g. Netscape 6.1) and the IP address of the
device is entered. The standard address is:
http://192.168.200.1.
Confirm this address to access the start page of KACO-
proLOG.
6.3.3 Windows XP
Step 1
Make sure that a suitable modem is connected to your
PC and properly installed.
Click “(START/SYSTEM CONTROL) or, respectively,
(START / SETTINGS / SYSTEM CONTROL)” to access
the menu item “network connections “Now select
Assistant for new connections “.
If KACO-proLOG is equipped with an
internal analog modem, an analog modem
or ISDN modem with analog simulation
must be used for communication.
If KACO-pr OG is equipped with an internal ISDN
tep 2 ssistant for new connections “, followed by
ow select the menu item “Connect to Internet“. In the
transfer modem “.
oL
modem, the PC must likewise be equipped with an
internal ISDN modem for communication.
S
Click “A
“Proceed”.
N
next dialog, select “Establish manual connection”; and
in the next dialog, click “
” Connect to remote data
KACO SOLAR INC. 18 Operator’s Instructions KACO-proLOG

Step 3
Click “Proceed “ to establish your connection. First,
assign a name of your choice to your new connection.
This name will be used to enable your connection again
later. In the next dialog, enter the phone number of
KACO-proLOG. The next dialog can be used to enter a
user name of your choice under
“User “. The “Password” fields may remain blank.
NOTE: The checkboxes 2
(Standardconnection) and 3 (Internet
Connection Firewall) should be
deactivated as these options may inhibit the further
operation.
Now use the following dialog to finally establish your
connection:
KACO SOLAR INC. 19 Operator’s Instructions KACO-proLOG

“Admin” must be entered as the user name and
password.
Please note that an external call prefix may
be necessary when entering the telephone
number. In most cases, this external call
prefix will be assigned a preceding “0”.
Step 4
After successful buildup of the connection the dialog
“Connect to….”will be opened. In this dialog, first press
“Features”. In the next dialog, change to the “Network”
tab and click “Internet Protocol (TCP/IP), followed bei
“Features”.
Now enable the options “Use the following IP address”
and “Use the following DNS server addresses”, and
enter the address “192.168.200.51” in the following
boxes.
KACO SOLAR INC. 20 Operator’s Instructions KACO-proLOG
This manual suits for next models
1
Table of contents
Other Kaco Data Logger manuals