cLr :Accumulated energie can be era ed in thi ection.
The parameter which indicated by the LED at the top of the device, will be
era ed.
▲▼
SET
▲
▼
▲▼
SET
▲
▼
▲▼
SET
▲
▲▼
Exit Menu
CLR
RES ALL PAR
QUIT
CLR ENERGY
YES rES ALL PAr : All parameters are erased and factory settings are restored
increase
decrease
increase
decrease
Operating Voltage (Un) : (Phase-Neutral ) 230Vac
Operating Range : (0,8-1,1) x Un
Operating Frequency : 50/60 Hz
Supply Power Consumption: < 6VA
Power Consumption
of Measurement Inputs: : < 1VA
Vin : 1 – 300 Vac (L-N)
: 2 – 600 Vac (L-L)
Iin : (as the secondary current of
the current transformer)
0,01 - 6 Amp AC
Measurement Class : CAT III
Voltage Transformer Ratio: : 1 ..... 4000
Current Transformer Ratio : 1 ..... 5000 (25000/5A)
Connection Type : 3P&4W , 3P&3W , ARON
emand Time : 1 – 600 min
isplay range : 1,0V - 400,0 kV
: 0,001A ........ 25000 A
: 0 – 999,9 M (W,VAR,VA)
: 0 – 999,9 k (W,VAR,VA)
: 0 – 999.999.999,999 (GWh,GVARh,GVAh)
accuracy
Active Power : 1 class
Reactive Power : 2 class
Apparent Power : 1 class
Pul e Output (2 pcs)
Operating Voltage : 5 – 24Vdc max. 30Vdc
Operating Current : max 50 mA
Min. Switching Time : 100 ms
Technical Specification
evice Protection Class : IP 20
Terminal protection class : IP 00
Ambient temperature : - 5 °C .... + 50 °C
Installation Type : IN rail
imensions : 105x90x59 mm
NOTE: Operating Voltage (Un): ask price and delivery time for 85-256Vac/dc
N
1Σ
N
Pi
i=0
P
=
N
1Σ
N
Qi
i=0
Q
=
S = P 2Q2
+
PF = P
S
Active Power
Reactive Power
Apparent Power
Power Factor
Formula
Current Transformer(Primary) Value : 5 / 5 A
Voltage Transformer Ratio : 1
Pulse Type for 1.Pulse Output : OFF
Pulse Value for 1. Pulse Output (Pd) : 1 KWh
Pulse uration for 1.Pulse Output (Pt) : 100 ms
Pulse OFF Time for 1.Pulse output (Pp) : 200 ms
Pulse Type for 2.Pulse Output : OFF
Pulse Value for 2. Pulse Output (Pd) : 1 KVARh
Pulse uration for 2.Pulse Output (Pt) : 100 ms
Pulse OFF Time for 2.Pulse output (Pp) : 200 ms
Factory Settings
1. Pulse ouputt2. Pulse output
Note :When factory settings
are restored, energies are set to zero.