Date: 8/31/2012
LED indicators are in the Fire system Normal condition when the Power on LED is lit and all other LED
indicators are not lit. LED indicators light continuously or flash when the fire control panel reports Evacuate,
Fire, Alert, Tech Alarm, Security or Fault conditions. The internal buzzer sounds when the fire control panel
reports Evacuate, Fire, Alert, Tech Alarm, Security or Fault conditions.
The internal buzzer is silent when the Taktis Fire Control Panel is in the Fire System Normal condition.
Left LED Indicators
Left LED Indicators
Key LED Colour Description
A Fire Red A fire alarm or fire drill condition exists.
The status condition is provided on the
touch-panel-display. The internal buzzer
sounds intermittently.
Output relays are activated.
!LED Flashing: Sounders are activated
!LED Continuous: Sounders are
silenced
!LED OFF: Fire Control Panel and
Sounders are reset
B General Fault Amber The General Fault LED flashes when fault
conditions exist on the fire control panel.
The flashing General Fault LED
accompanies one or more flashing
amber LEDs that indicate specific fault
conditions.
C System Fault Amber A System Fault exists when this LED is
flashing. Status is provided on the
touch-panel-display and the internal
buzzer sounds continuously. A System
Fault occurs when problems exist with
internal circuits of the Taktis Fire Control
Panel.
Key LED Colour Description
D Power Fault Amber A fault condition exists on the main or
back up power supplies.
E General
Disablement
Amber Parts of the system have been manually
disabled and are inactive.
F Pre-Alarm
Amber One or more fire detectors are close to
their alarm limits and a fire alarm
condition is imminent.