WARNING!
THE BUILT-IN SPIRIT LEVEL MUST BE USED TO
ALIGN THIS VALVE. FAILURE TO FOLLOW THE
PROCEDURE LISTED BELOW WILL PREVENT THE
VALVE OPERATING CORRECTLY.
INSTALLATION OF VALVES SHOULD BE IN
ACCORDANCE WITH THE WATER SUPPLY (WATER
FITTINGS) REGULATIONS 2010 AND BS 8558:2011.
TANKS AND PIPES SHOULD BE DISINFECTED USING
THE PROCEDURES IN BS EN 806-4:2010 SECTION
6: COMMISSIONING.
tel 0118 921 9920 fax 0118 921 9921 info@keraflo.co.uk www.keraflo.co.uk
10 The float arms should hang vertically
with the built-in spirit level bubbles
exactly between the black lines as
shown in diagram 4.
ENSURE THAT THE FLOAT ARM OPERATING
PINS ENGAGE IN THE HOLES IN THE ACTUATOR
WHEELS AND THAT THE FLOAT MARKED WITH
A RED DOT IS FITTED TO THE VALVE WHICH IS
ALSO MARKED WITH A RED DOT.
11 If the valves are not level, each individual
valve can be rotated at its screwed
connection into the T-outlet. This joint is
sealed by an “o”-ring so can be moved
without fear of a leak.
12 Loosen the locknuts on the valve body
and rotate each valve individually as
necessary so that the float arms are
ABSOLUTELY VERTICAL.
13 Align each valve, tighten the locknut
and re-check the alignment.
EACH BUBBLE MUST BE PRECISELY
BETWEEN THE BLACK LINES.
14 Check that the clearance between
the tank wall and the floats is at least
25mm, when the float arms are
vertical. If it is less than this move
the assembly further into the tank
by adjusting the valve backnuts and
repeating steps 6 to 8.
15 When the clearance and the levels are
correctly set, fully tighten the backnuts
holding the assembly to the tank wall.
16 Using the 4mm Allen key supplied,
remove the two M5x12 screws from the
ends of the float link bar.
17 Place the bar between the lowest holes of
the two Float Arms and attach it using the
M5x12 screws, as shown in Diagram 5.
DIAGRAM 4
SPIRIT LEVEL
AYLESBURY K VALVE p5
SPIRIT LEVEL
DIAGRAM 5
SPIRIT LEVEL
VALVE
BODY
LOCK
NUTS
FLOAT ARMS
FLOAT LINK BAR