manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Kidde
  6. •
  7. Security Sensor
  8. •
  9. Kidde SB4U Assembly instructions

Kidde SB4U Assembly instructions

© 2017 United Technologies Corporation 1 / 3 P/N 3101077-EN • REV 007 • ISS 13JUN17
SB4U Analog Audible Detector
Base Installation Sheet
Operation
The SB4U Analog Audible Detector Base adds an audible output
function to the listed compatible detectors. The base can operate as an
independent local alarm, or as part of a zone or system alarm with
synchronized audible output.
The output of this detector base is field-configurable for output tone
(steady or temporal) and output volume (low dBA or high dBA).
Depending on the system supporting the device loop, the base can:
• Follow the state of the device it supports
• Be controlled and configured for other operating modes through
front panel programming or the configuration utility
The base uses the same address and programming label as the
detector it supports.
Installation
Cautions
• To avoid accidental damage to the control panel, disconnect all
power before wiring the unit.
• Electrical supervision requires the wire run to be broken at each
terminal. Do not loop the signaling circuit field wires around the
terminals.
Note: Always connect the base to a continuous voltage, whether the
output tone is set to steady or temporal.
Sleeping rooms: In sleeping areas, use the high dBA output and
temporal tone settings. However, if the control panel is producing the
three-tone temporal evacuation signal, then the high dBA output and
steady tone settings are permissible.
AB4G-SB: When using the AB4G-SB box, install a reinforcing plate at
every knockout. (Reinforcing plates are included with the box.)
Remove the knockout first and then slide the reinforcing plate into the
plastic housing. After the plate is in place, install the conduit connector
and nut. See Figure 1.
Typically, the base is configured to produce a high dBA temporal tone
and is connected to a notification appliance circuit that outputs a
continuous 24 VDC signal. If the notification appliance circuit outputs a
temporal signal, configure the tone setting on the base for steady.
To install the base:
1. The unit default is for high dBA output. To set the output to low
dBA, cut the circuit board trace as marked on the back of the PC
board. See Figure 3.
2. The unit default is for temporal pattern output. To set the output to
steady tone, cut the circuit board trace as marked on the back of
the PC board. See Figure 3.
3. Select and install a compatible electrical box, and bring the field
wiring into the box.
4. Install the trim ring and secure using screws. The trim ring is
included with the SB4U base. See Figure 2.
5. Make all wiring connections as shown in Figure 3.
6. Attach the base plate to the electrical box using the screws
provided with the electrical box.
7. Attach the trim ring to the base plate. Align the marks on the trim
ring and base plate, press the trim ring onto the base plate, and
then rotate the trim ring until it locks into place.
8. Attach the desired detector to the base. Align the arrows on the
detector and trim ring, press the detector into the base, and then
rotate the detector until it locks into place.
9. Apply power and activate the unit to verify that it is operating
properly.
Figure 1: AB4G-SB box installation
1. Conduit connector
2.
AB4G-SB electrical box
3.
Lock tab
4. Trim rings
5. Screw
6. Nut
7. Reinforcing plate
1
2
3
4
5
6
7
2 / 3 P/N 3101077-EN • REV 007 • ISS 13JUN17
Figure 2: Base installation
1. Detector
2.
Trim ring
3. Screw
4. Base plate
5. Compatible electrical box
Wiring
Wire in accordance with NFPA 72 and CAN/ULC-S524. Be sure to
observe the polarity of the terminals on the terminal block as shown in
the diagram.
Break the wire run at each terminal. Do not loop signaling circuit field
wires around terminals.
Refer to the applicable technical reference manual for application
diagrams.
Note: Shielded wire is required only in environments with very high
electrical noise. When you use shielded cable, follow these
recommendations:
• Shield connection to and from the base must be continuous and
must be insulated from ground. Insulate the shield using tape.
• For Class B wiring, there is no shield connection to ground at the
last device.
Figure 3: Output configuration and wiring diagram
1. AUX-RISER IN (from power supply or previous base)
2.
Volume setting: default is high volume; cut per item 4 for low
volume
3.
Tone setting: default is temporal pattern; cut per item 4 for steady
tone
4.
To configure output volume or tone, cut the circuit board as shown
5.
AUX_RISER OUT To next base or EOL relay
6.
SLC OUT to next intelligent addressable device
7. SLC IN from intelligent addressable controller or previous device
4
SLC +SLC +
AUX_RISER +AUX_RISER +
SLC −
SLC −
AUX_RISER −AUX_RISER −
P/N 3101077-EN • REV 007 • ISS 13JUN17 3 / 3
Table 1: Operating current in mA (RMS)
Voltage
Low dBA High dBA
16 VDC
17 28
24 VDC
24 41
33 VDC
31 52
16 VFWR
41 48
24 VFWR
51 60
33 VFWR
60 66
VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified
Table 2: Sound level output (dBA) per CAN/ULC-S525
Signal
Voltage (VDC)
Low dBA
High dBA
Reverberant room per UL 464 [1]
Temporal
16
71.3
77.2
24
75.0
79.8
33
77.7
81.5
Steady
16
75.8
80.5
24
79.2
84.1
33
82.0
86.0
Reverberant room per UL 268 [2]
Temporal
16
77.3
83.2
24
81.0
85.8
33
83.7
87.5
Steady
16
81.8
86.5
24
85.2
90.1
33
88.0
92.0
[1] For UL 464 applications, low dBA settings are for private mode only
[2] For UL 268 applications, the high setting must be used for
evacuation
Table 3: Audible directional characteristics
Angle
(degrees) Output sound pressure level
90 (reference)
0 dBA
80 and 100
−3 dBA
70 and 110
−6 dBA
Horizontal axis and veritical axis reflect the same pattern
Table 4: Sound pressure level per CAN/ULC-S525
Signal
Voltage High dBA Low dBA
Temporal
Reg. 24 VDC 95 91
Reg. 24
VFWR 99 95
Steady
Reg. 24 VDC 93 89
Reg. 24
VFWR 96 92
Maintenance
Do not change the factory-applied finish.
Specifications
Operating voltage (sounder
power)
24 VDC or 24 VFWR
Current
Operating
Supervisory
See Table 1
DC = 1.46 mA, FWR = 2.15 mA
Default settings
Output volume
Output tone
High dBA
Temporal pattern
Sound level output
UL
ULC
See Table 2
See Table 4
Temporal pattern
0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off,
0.5 s on, 1.5 s off, repeat cycle
Compatible detectors
FX-PD, E-PD, FX-PHD, E-PHD,
FX-HD, E-HD, V-PS, V-PHS, V-
HRD,
and V-HFD
Compatible electrical
boxes AB4G-SB surface box for audible
base
North American 4 in. square x
2-1/2 in. (64 mm) deep box
Standard European 100 mm² box
Wire size
12 to 18 AWG (0.75 to 2.5mm²)
Sizes 16 and 18 AWG are preferred
Base diameter
6.0 in. (152 mm)
Height from box
(including
detector)
2.58 in. (66 mm)
Maximum distance from
ceiling (wall mount)
12 in. (305 mm)
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Storage temperature range
–4 to 140°F (–20 to 60°C)
Regulatory information
UL/ULC rating
Regulated 24 DC or 24 FWR
North American
standards
Meets: UL 268, UL 464, CAN/ULC-S525, and
CAN/ULC-S529
Follow: CSA C22.1 and CAN/ULC-S524.
This device is prohibited from being installed in a
dwelling unit as defined in the National Building
Code of Canada.
Contact information
For contact information, see www.kiddelifesafety.com.

This manual suits for next models

1

Other Kidde Security Sensor manuals

Kidde DC-9103E-KID User manual

Kidde

Kidde DC-9103E-KID User manual

Kidde V-PHS Assembly instructions

Kidde

Kidde V-PHS Assembly instructions

Kidde AlarmLine II ADLCU User manual

Kidde

Kidde AlarmLine II ADLCU User manual

Kidde GSA-IM Assembly instructions

Kidde

Kidde GSA-IM Assembly instructions

Kidde KI-PHD Assembly instructions

Kidde

Kidde KI-PHD Assembly instructions

Kidde 60WLDR-W User manual

Kidde

Kidde 60WLDR-W User manual

Kidde KIR-HD Assembly instructions

Kidde

Kidde KIR-HD Assembly instructions

Kidde 60WLDR-W-CA User manual

Kidde

Kidde 60WLDR-W-CA User manual

Popular Security Sensor manuals by other brands

Guardian Fall Protection Edge Harness Series instruction manual

Guardian Fall Protection

Guardian Fall Protection Edge Harness Series instruction manual

AVE AF974R-DB manual

AVE

AVE AF974R-DB manual

System Sensor WFDEXP Installation and maintenance instructions

System Sensor

System Sensor WFDEXP Installation and maintenance instructions

Optex Redwall LRP 180QH Installation and setup guide

Optex

Optex Redwall LRP 180QH Installation and setup guide

Texora ULTRA-WIND Instructions for use

Texora

Texora ULTRA-WIND Instructions for use

United Technologies Interlogix DDI602U-F1 Installation sheet

United Technologies

United Technologies Interlogix DDI602U-F1 Installation sheet

F&F DRM-02 quick start guide

F&F

F&F DRM-02 quick start guide

BAPI BA/LDT Termination and Troubleshooting

BAPI

BAPI BA/LDT Termination and Troubleshooting

Haws 7501 Nstallation, operation & maintenance instructions

Haws

Haws 7501 Nstallation, operation & maintenance instructions

Visonic MCT-442 installation instructions

Visonic

Visonic MCT-442 installation instructions

Tractel LCR Operating and maintenance instructions

Tractel

Tractel LCR Operating and maintenance instructions

Compur Statox 501 IR LC Brochure & specs

Compur

Compur Statox 501 IR LC Brochure & specs

ROCK EXOTICA Akimbo Instructions for use

ROCK EXOTICA

ROCK EXOTICA Akimbo Instructions for use

Velleman PIR1300 user manual

Velleman

Velleman PIR1300 user manual

Wenglor P1PY1 Series operating instructions

Wenglor

Wenglor P1PY1 Series operating instructions

Zennio EyeZen TP v2 manual

Zennio

Zennio EyeZen TP v2 manual

Alula RE210P quick start guide

Alula

Alula RE210P quick start guide

Sperian Miller Xenon X00390 User instruction manual

Sperian

Sperian Miller Xenon X00390 User instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.