  9. Kidde V-PHS Assembly instructions

Kidde V-PHS Assembly instructions

P/N 3101071-EN • REV 05 • ISS 24FEB16 1 / 2
V-PHS Photoelectric and
Fixed-Temperature Heat
Detector Installation Sheet
Description
The V-PHS Photoelectric and Fixed-Temperature Heat Detector uses
an optical sensing chamber to detect smoke and a fixed-temperature
heat sensor to monitor the temperature of the air in its surroundings to
detect heat from fire. The detector analyzes the sensor data to
determine whether to initiate an alarm.
The detector is capable of performing comprehensive self-diagnostics
and storing the results. It continuously monitors changes in sensitivity
due to the environment (e.g., dirt, smoke, temperature, humidity),
notifies the control panel of its condition, and issues a dirty sensor
warning when it reaches its preset limit. This notifies the operator of
the need for service while the detector is still operating.
LED operation
The detector provides a bicolor LED that shows its status.
• Normal: Green LED flashes
• Alarm/active: Red LED flashes
Electronic addressing
The control panel automatically assigns addresses to the detectors.
Use a laptop computer to address custom addresses to the detectors.
No addressing switches are used.
Installation
Install and wire this device in accordance with applicable national and
local codes, ordinances, and regulations.
Refer to Vigilant Detector Application Bulletin (P/N 3101109-EN) for
additional information on detector placement and spacing.
WARNINGS
• Risk of system failure. This detector does not operate without
electrical power. As fires frequently cause power interruption,
discuss further safeguards with your local fire protection specialist.
• Risk of system failure. This detector does not sense fires that start
in areas where heat cannot reach the detector. Heat from fires in
walls, roofs, or on the opposite side of closed doors may not reach
the detector.
Notes
• Photoelectric detectors have a wide range of sensing capabilities,
and are best suited for detecting slow, smoldering fires. The heat
sensor in this device provides a source of supplemental
information to that provided by the photoelectric smoke sensor.
The heat sensor by itself does not provide life safety protection.
• Do not use a detector guard with this detector unless the
combination has been evaluated and found suitable.
• To ensure proper operation, schedule maintenance (regular or
selected) in accordance with the requirements of the authority
having jurisdiction. Refer to NFPA 72 and CAN/ULC-S536.
• To ensure proper operation, store the detector within the
recommended temperature ranges. Allow the detector to stabilize
to room temperature before applying power.
• Keep the dust cover (supplied) on the detector during installation
and remove it prior to commissioning and service. The dust cover
is not a substitute for removing the detector during new
construction or heavy remodeling.
To install the detector:
1. Install and wire the detector base using the installation sheet
supplied with the detector base.
2. Connect the detector to the base by rotating the detector clockwise
until it snaps into the locked position.
To remove the head turn it counterclockwise.
3. If the head must lock to the base, break away the locking tab using
a pair of pliers. See Figure 1.
To remove the detector head after breaking away the locking tab,
insert a small screwdriver into the slot on the side of the base and
press in while simultaneously turning the detector head
counterclockwise.
4. Remove the serial number label from the detector and attach it to
the project documentation.
Figure 1: Locking tab
Maintenance
When cleaning is necessary, the sensing chamber of the detector
easily unsnaps for field cleaning and service.
Note: Only the smoke element of the detector requires cleaning.
To clean the detector:
1. Remove the detector from the base.
2. Insert a screwdriver in the small slot where the detector cap
connects to the detector body. See Figure 2.
3. Pry the detector cap off the detector body.
4. Squeeze the optical block chamber where the two arrows point,
labeled “squeeze here.”
(1)
2 / 2 P/N 3101071-EN • REV 05 • ISS 24FEB16
5. Pull off the optical block chamber.
6. Blow off the optical block base in the detector body using clean
compressed air.
7. Snap a new optical block chamber in place. Make sure you line up
the two arrows on the block chamber with the snaps on the optical
block base.
8. Connect the detector cap to the detector body by rotating the cap
clockwise until it snaps into a locked position.
9. Install the detector onto the base.
Note: To verify the effectiveness of the cleaning, recalibrate the
device and run a device maintenance report. Refer to the technical
reference manual.
10. Test the detector and verify sensitivity.
Figure 2: Detector disassembly
(1) Slot to insert screwdriver
(2) Optical block chamber
(3) Optical block base
(4) Detector body
(5) Detector cap
Testing
NFPA 72 and CAN/ULC-S537 require a calibrated sensitivity test upon
installation and following any modifications or additions to the system.
The detector can perform this test and generate a system sensitivity
report.
Note: Both the smoke element and heat element of the detector must
be tested.
To test the detector:
1. Before initial testing, remove the dust cover from the detector and
notify the proper authorities that the fire alarm system is
undergoing maintenance and will be temporarily out of service.
2. Test the detector’s smoke element using Smoke! In A Can (model
SM-200) canned smoke. Carefully follow directions on the can to
avoid damage to the detector.
3. Test the detector’s heat element using a heat gun while
maintaining a six-inch minimum. Use caution as excess heat can
damage the detector and detector housing.
Specifications
Communication line voltage 20 V peak-to-peak max.
Current
Normal
Alarm
45 µA
45 µA
Smoke sensitivity range
UL
ULC
0.67 to 3.66 %/ft. obscuration
0.87 to 3.70 %/ft. obscuration
UL/ULC fixed-temp alarm rating 135°F (57°C)
Environmental compensation Automatic
Distance from ceiling (wall
mounted)
305 mm (12 po.) max.
Compatible bases
Standard
Relay
Isolator
Audible
B4U, B4U-LP
RB4U
IB4U
SB4U, SB4U-LF
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Storage temperature −4 to 140°F (−20 to 60°C)
Regulatory information
North American
standards
Meets: CAN/ULC-S529, CAN/ULC-S530, UL 268,
UL 521
Follow: CAN/ULC-S524, CAN/ULC-S537,
National Building Code of Canada, National Fire
Code of Canada, and NFPA 72
FCC compliance This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
Industry Canada
compliance
This Class A digital apparatus complies with
Canadian ICES-003.
Contact information
For contact information, see www.kiddelifesafety.com.
© 2016 Walter Kidde Portable Equipment, Inc.
All rights reserved.
(1)
(2)
(5)
XXXXXXXX
(3)
(4)

Other Kidde Security Sensor manuals

Kidde KI-PHD Assembly instructions

Kidde

Kidde KI-PHD Assembly instructions

Kidde SB4U Assembly instructions

Kidde

Kidde SB4U Assembly instructions

Kidde DC-9103E-KID User manual

Kidde

Kidde DC-9103E-KID User manual

Kidde AlarmLine II ADLCU User manual

Kidde

Kidde AlarmLine II ADLCU User manual

Kidde 60WLDR-W-CA User manual

Kidde

Kidde 60WLDR-W-CA User manual

Kidde GSA-IM Assembly instructions

Kidde

Kidde GSA-IM Assembly instructions

Kidde KIR-HD Assembly instructions

Kidde

Kidde KIR-HD Assembly instructions

Kidde 60WLDR-W User manual

Kidde

Kidde 60WLDR-W User manual

Popular Security Sensor manuals by other brands

Waters TQ Detector quick start guide

Waters

Waters TQ Detector quick start guide

PCB Piezotronics ICP J106B/061A60 Installation and operating manual

PCB Piezotronics

PCB Piezotronics ICP J106B/061A60 Installation and operating manual

Emergency Assistance+ SaferinoGo Important Functionality Notes

Emergency Assistance+

Emergency Assistance+ SaferinoGo Important Functionality Notes

Nimbus Water Systems MODUL Q 64 IQ-SENSOR Mounting

Nimbus Water Systems

Nimbus Water Systems MODUL Q 64 IQ-SENSOR Mounting

MSA ExtendAire II Series User instructions

MSA

MSA ExtendAire II Series User instructions

Halma MEMCO Elite 618 manual

Halma

Halma MEMCO Elite 618 manual

KingShield Orion Range OD105 quick start guide

KingShield

KingShield Orion Range OD105 quick start guide

B.E.G. LUXOMAT PD9-M-DALI/DSI-FC Installation and operating instruction

B.E.G.

B.E.G. LUXOMAT PD9-M-DALI/DSI-FC Installation and operating instruction

AJAX vhfBridge user manual

AJAX

AJAX vhfBridge user manual

SECOLink BP2 installation manual

SECOLink

SECOLink BP2 installation manual

Bosch Blue Line Gen2 ISC-BPR2 installation guide

Bosch

Bosch Blue Line Gen2 ISC-BPR2 installation guide

Waeco AirCon Oil Checker R134a Installation and operating manual

Waeco

Waeco AirCon Oil Checker R134a Installation and operating manual

Tatsuta Electric Wire & Cable AD-AS-1BM Operation manual

Tatsuta Electric Wire & Cable

Tatsuta Electric Wire & Cable AD-AS-1BM Operation manual

Epcos B59601 manual

Epcos

Epcos B59601 manual

olympia electronics BSR-6160 quick start guide

olympia electronics

olympia electronics BSR-6160 quick start guide

Det-Tronics X3302 instructions

Det-Tronics

Det-Tronics X3302 instructions

teko Astra-5131 user guide

teko

teko Astra-5131 user guide

ESYLUX MD 180i/16 BASIC CH operating instructions

ESYLUX

ESYLUX MD 180i/16 BASIC CH operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.