ADLCU Digital LHD Alarm Distance Locator Installation and Operation Manual 3
Product description
The ADLCU alarm point distance locator allows accurate location of an alarm
point along a length of Linear Heat Detection (LHD) cable.
Location of the alarm point may not always be possible by visual inspection on
low temperature LHD cable due to the cable triggering an alarm before physical
damage has occurred or, on longer lengths of LHD cable, it may be too time
consuming or inconvenient.
The ADLCU is designed exclusively for use with Alarmline II Digital Linear Heat
Detection sensor cables. The ADLCU is designed to interface between a listed
fire alarm control panel, releasing control panel, or addressable module and a
single length of sensor cable.
An important design feature of the ADLCU is the continued correct operation of
the fire alarm control panel, releasing control panel, or addressable module
regardless of faults which may occur in the ADLCU (such as loss of power to the
unit).
Each unit complies with the relevant FM standard and is enclosed in an IP65
rated enclosure.
Features
• Alarm point distance locating device for use with Alarmline II Digital LHD
cables 68°C (154°F), 78°C (172°F), 88°C (190°F), 105°C (221°F), or 185°C
(365°F)
• Alternating metres/feet display of alarm point
• Cable selection
• Leader cable calibration
• Detection of alarm point from 100 to 3000 m (300 to 10000 ft.)
• Installation settings saved in event of power loss
• IP65/IK08 rated enclosure for indoor/outdoor use with 4 sizes of M knockouts
• Simple installation and operation
• Backlit 16x2 character LCD
• Continued correct operation of the fire alarm control panel, releasing control
panel, or addressable module regardless of faults which may occur in the
ADLCU (such as loss of power to the unit)
• FM approved (for indoor use only)
Notes:
• Any fire alarm control unit connected to the ADLCU must be FM approved
• Any power supply used to deliver power to the ADLCU must be ANSI/UL
1481 certified