KIOUR ALAN-8 User manual

ANALOG ALARM UNIT 8 programmable channels Model ALAN-8
Description
The device ALAN-8 (Multi) has the following characteristics:
1. Temperature sensor type Jfrom -200 oC to +950 oC.
2. Temperature sensor type K from 0 oC to +1350 oC.
3. Temperature sensor type ΡΤ100 with 2 cables from -200 oC to +850 oC.
4. Temperature sensor type ΡΤ100 with 3 cables from -200 oC to +850 oC.
5. Input signal 4 ÷ 20mA with analysis 0÷2000 units and adjustable scale.
6. Input signal 0 ÷ 20mA with analysis 0÷2000 units and adjustable scale.
The new scale can be shifted within the scale of the screen from -99÷2000 units.
7. Detection of cutline or short circuit line in the temperature sensors or 4÷20mA, 0÷20mA (sensor failure) in each channel.
8. Internal relay with one associated auxiliary contact 250VAC 10A for setting up an external alarm circuit in case of main power failure.
9. The input signal J, K, PT100 or mA for every channel can be set through parameters (ChM1÷ChM8). Each channel can be adjusted
independently. Τhe sensors/mA inputs are galvanic isolated from the outputs and power supply.
10. Each channel can be activated or deactivated and set or not to the average group which it will belong. Two groups of averages can be
defined.
11. The OVER FLOW and WRONG CONNECTION alarms activate only the general relay of the device while the LEDs and the display
are flashing. These alarms do not update the alarm’s table. With the parameters OOF1 to OOF8 we drive each line failure to one of
the 11 outputs. In addition, line failure deactivates all the alarms of the corresponding channel. A message OV F for the Over Flow
and WR C for the Wrong Connection of ΡΤ100 are displayed on screen. By pressing [RESET], the general relay is deactivated and
the corresponding LED remains on. If the parameter No.172 OFWC is set to OFF, the general relay is deactivated.
12. The OVER FLOW alarm is activated for: sensor type J over 950 oC, sensor type Kover 1350 oC, sensor type PΤ100 over 850 oC and
below -200 oC, 4÷20mA below 3.9mA and over 20.05mA and 0÷20mA over 20.05mA.
13. The Set Points can function either as alarm or as limit supervisors by adjusting the parameter Νο.171 MoSP.
14. Possibility to invert the commands High and Low of Set Points.
15. Zero adjustment of each indication independently.
16. LCD screen of 2x16 characters.
17. Recording and depicting incoming alarms to screen numbered and in the order they appear.
18. Up to 32 alarms, 4 for each channel.
19. Capability to drive each of the 32 alarms to the outputs 1÷11 independently or in groups.
20. 8 LEDs, one for each channel.
21. Capability to drive the LED operation to the outputs for monitoring.
22. One general internal relay output 250VAC 10A for siren activation.
23. Time-delay for each of the 32 alarms. NOTE: Time-delay for the Average Set Point High and Low alarms is common to each channel
(parameters Tia1 to Tia8), for example time-delay Tia1 for channel 1 applies to AS1H and AS1L.
24. External RESET for connecting an external button.
25. Outputs can drive micro-relays of 30mA consumption. It is recommended to place the micro-relays near the device.
26. Power supply output 24VDC to supply micro-relays and transmitters of 4÷20mA (maximum current 300mA).
27. Screw terminal 0 Volt for supplying transmitters.
28. Power supply: 24VAC ± 10% 50/60Hz or 24VDC +30% / -10%
29. Maximum consumption: 10W
30. Internal power supply fast blow fuse: 1A
31. Internal fast blow fuse in the outputs: 315mA
32. Internal fast blow fuse in the network’s communication: 315mA
Technical specifications
1. By setting the input signal to mA, we adjust the scale channels through the parameters (IN1L/IN1H÷IN8L/IN8H). For example, if the
input signal is 4÷20mA and we want the corresponding scale of channel No.1 to be -50÷+50, we adjust the parameter IN1H to +50
and afterwards we adjust the parameter IN1L to -50. If we try the opposite, that is adjusting first the parameter IN1L to -50, it won’t
be possible because the difference (IN1H –IN1L) can never be greater than 2000 units.
2. Activation / deactivation of a channel. Each channel can be set through parameter (SCh1÷SCh8) with possible values (-1÷2):
“-1” = channel deactivated, “0” = channel activated and doesn’t belong to any average group, “1” = channel activated and belongs to
average group No.1, “2” = channel activated and belongs to average group No.2
3. The Set Points alarms, through the parameter No.171 MoSP, can function either as alarms or as limit supervisors.
A) Operating as alarm: When an alarm appears, the LED, the general relay and the corresponding output (1÷11) are activated. By
pressing [RESET] we deactivate them all. If an alarm still exists, the corresponding LED remains ON and switches to OFF when the
cause of the alarm disappears. B) Operating as limit supervisor: When an alarm appears, the LED, the general relay and the
corresponding output (1÷11) are activated. By pressing [RESET] we deactivate the LED and the general relay but the output (1÷11)
is not deactivated. It will be deactivated only if the cause of the alarm disappears. This operation is suitable for High and High-High
surveillance.
1

4. Capability of inverting Set Point commands. For example, in channel No.1, the parameter SP1L (Set Point 1 Low) corresponds to
parameter HC1L (Heating Cooling 1 Low). If we set HC1L to Col, the command is executed over the Set Point. If we set HC1L to
Hot, the command is executed below the Set Point. For example, in High and High-High surveillance, the parameters are set as
follows: HC1H = Col and HC1L = Col.
5. The screen depicts 4 temperature channels at the same time. It refreshes automatically to the next set of temperatures and the
two average group temperatures. The refreshing time can be set from the parameter Tisc. By pressing [SET] we manually change
the indication.
6. When an alarm appears, the temperature indication of the channel with the alarm starts flashing on screen, while the corresponding
channel group freezes on screen. Each incoming alarm is recorded and numbered according to the alarm sequence into a table. Up
to 30 alarms are recorded, with the new incoming alarm being placed to the 30th position and the 1st being lost. By pressing [ ] and
[SET] the alarm table appears on screen. To clean the whole table, we press at the same time [ ] and [SET]. The temperature
indications appear on screen by pressing [SET].
7. There are up to 32 alarms where each channel has 4, two Set Point alarms (HIGH, LOW) and two average alarms (HIGH, LOW).
When a channel does not belong to any group, the two average alarms are automatically deactivated.
8. Each alarm is driven to an output (1÷11) by adjusting the proper parameter. The outputs of Set Point alarms are adjusted from
parameters (OS1H/OS1L÷OS8H/OS8L), while the outputs of average alarms are adjusted from parameters
(OA1H/OA1L÷ΟΑ8Η/ΟΑ8L). Alarms can be driven to outputs independently or in groups. If we set “0”, the alarm doesn’t
correspond to any output and if we set from “1÷11”, the alarm corresponds to the selected output.
9. Each channel has one LED, in a total of 8 LEDs. A LED starts flashing when an alarm appears and remains ON until it is
recognized by [RESET]. If the cause of the alarm remains after the RESET, the LED remains steadily ON and turns off when the
cause disappears.
10. Each LED can be driven to an output (1÷11) for monitoring. This adjustment is set from parameters (OLE1÷OLE8). If we set “0”,
the LED will not correspond to any output while if we set from “1÷11”, the LED of the respective channel is driven to the selected
output.
11. General internal relay alarm (250VAC, 10 A resistive loads). When one or more of the 32 alarms appear, the general relay is
activated. If the parameter No.172 OFWC is set to OFF, the OVER FLOW and WRONG CONNECTION alarms do not activate the
general relay.
12. Internal relay with one associated auxiliary contact 250VAC 10A for setting up an external alarm circuit in case of main power
supply failure.
13. Detection of cutline or short circuit line in the temperature sensors or 4÷20 mA, 0÷20 mA (sensor failure) in each channel.
Button’s function Managing the parameters
By pressing [ENTER] we enter the parameter’s menu and
the first parameter is displayed, Code. In order to access
the parameters, we have to set the parameter Code to
“22”.
By pressing [SET] the arrow flashes next to the
parameter’s value and with the arrows [ ], [ ] we can
modify its value.
By pressing [ENTER] we confirm the new value and
the arrow flashes next to the parameter’s name.
By pressing [SET] we cancel the new value and return
to the parameter’s indication while the arrow flashes
next to the parameter’s name.
With the arrows [ ], [ ] we scroll into the parameters
with the order they appear in the parameter’s table.
By pressing [ENTER] we exit parameters menu.
2
button
function
ΕΝΤΕR
- access parameters menu
- confirm the new value of a parameter
SET
1. cancel the new value of a parameter
2. while programming parameters:
By pressing once, an arrow starts flashing next to the parameter
value and its value can be modified with the arrows
By pressing again, the arrow starts flashing next to the parameter
name and we can scroll into the parameters with the arrows
3. when not programming parameters:
- displays the next group of temperatures/mA
- when the alarms appear on screen, by pressing SET we change
the indication to the set of temperatures/mA
- inside parameters menu, we can scroll through the parameters
or change their values
- outside parameters menu, functions as TEST LAMP
- inside parameters menu, we can scroll through the parameters
or change their values
- outside parameters menu, functions as alarm RESET
clears the alarms table (does not reset alarms)
the alarm table appears on screen

Parameter’s table
No
Parameters description
min
max
default
UOM
1
Code
Entry code in parameters menu = “22”
0
254
0
2
SP1H
Set Point High in Channel 1
-99
2000
100
°C/mA
3
SP1L
Set Point Low in Channel 1
-99
2000
0
°C/mA
…
…
…
…
…
°C/mA
16
SP8H
Set Point High in Channel 8
-99
2000
100
°C/mA
17
SP8L
Set Point Low in Channel 8
-99
2000
0
°C/mA
18
IN1L
4 mA in Channel 1 corresponds to an indication on screen (see Specification 1)
-99
2000
0
19
IN1H
20 mA in Channel 1 corresponds to an indication on screen (see Specification 1)
-99
2000
2000
…
…
…
…
…
32
IN8L
4 mA in Channel 8 corresponds to an indication on screen (see Specification 1)
-99
2000
0
33
IN8H
20 mA in Channel 8 corresponds to an indication on screen (see Specification 1)
-99
2000
2000
34
Tisc
Time for automated refreshing of temperature indications on screen
1
150
6
sec
35
DF1H
Set Point High differential in Channel 1
1
150
2
36
DF1L
Set Point Low differential in Channel 1
1
150
2
…
…
…
…
…
49
DF8H
Set Point High differential in Channel 8
1
150
2
50
DF8L
Set Point Low differential in Channel 8
1
150
2
51
0AJ1
Zero adjustment of temperature sensor in Channel 1
-50
+50
0
°C
…
…
…
…
…
58
0AJ8
Zero adjustment of temperature sensor in Channel 8
-50
+50
0
°C
59
SCh1
Activation/deactivation of Channel 1 with values (-1÷2): “-1” = channel deactivated, “0” =
channel activated and does not belong to any average group, “1” = channel activated and
belongs to average group No.1, “2” = channel activated and belongs to average group No.2
-1
2
1
…
…
…
66
SCh8
Activation/deactivation of Channel 8 with values (-1÷2): “-1” = channel deactivated, “0” =
channel activated and does not belong to any average group, “1” = channel activated and
belongs to average group No.1, “2” = channel activated and belongs to average group No.2
-1
2
1
67
AS1H
Average Set Point High in Channel 1
-99
100
50
°C/mA
68
AS1L
Average Set Point Low in Channel 1
-99
100
-50
°C/mA
…
…
…
…
…
°C/mA
81
AS8H
Average Set Point High in Channel 8
-99
100
50
°C/mA
82
AS8L
Average Set Point Low in Channel 8
-99
100
-50
°C/mA
83
Ti1H
Time-delay of Set Point High Alarm in Channel 1
0
200
0
sec
84
Ti1L
Time-delay of Set Point Low Alarm in Channel 1
0
200
0
sec
…
…
…
…
…
sec
97
Ti8H
Time-delay of Set Point High Alarm in Channel 8
0
200
0
sec
98
Ti8L
Time-delay of Set Point Low Alarm in Channel 8
0
200
0
sec
99
Tia1
Time-delay of Average Set Points High (AS1H) and Low (AS1L ) Alarms in Channel 1
0
200
0
sec
…
…
…
…
…
sec
106
Tia8
Time-delay of Average Set Points High (AS8H) and Low (AS8L) Alarms in Channel 8
0
200
0
sec
107
OOF1
Drive the failure line alarm (OV F, WRC) of Channel 1 to one of the 11 outputs
0
200
0
sec
…
…
…
…
…
…
…
114
OOF8
Drive the failure line alarm (OV F, WRC) of Channel 8 to one of the 11 outputs
0
200
0
sec
115
OS1H
Drive the Set Point High command in Channel 1 to an output
1
11
0
116
OS1L
Drive the Set Point Low command in Channel 1 to an output
1
11
0
…
…
…
…
…
129
OS8H
Drive the Set Point High command in Channel 8 to an output
1
11
0
130
OS8L
Drive the Set Point Low command in Channel 8 to an output
1
11
0
131
OA1H
Drive the Average Set Point High command in Channel 1 to an output
1
11
0
132
OA1L
Drive the Average Set Point Low command in Channel 1 to an output
1
11
0
…
…
…
…
…
145
OA8H
Drive the Average Set Point High command in Channel 8 to an output
1
11
0
146
OA8L
Drive the Average Set Point Low command in Channel 8 to an output
1
11
0
147
OLE1
Drive the LED of Channel 1 to an output
1
11
1
…
…
…
…
…
154
OLE8
Drive the LED of Channel 8 to an output
1
11
8
155
HC1H
Invert Set Point High command in Channel 1 to (Hot) or (Cool)
HoT / Col
CoL
156
HC1L
Invert Set Point Low command in Channel 1 to (Hot) or (Cool)
HoT / Col
HoT
…
…
…
HoT / Col
169
HC8H
Invert Set Point High command in Channel 8 to (Hot) or (Cool)
HoT / Col
CoL
170
HC8L
Invert Set Point Low command in Channel 8 to (Hot) or (Cool)
HoT / Col
HoT
171
MoSP
Set Points alarms (SP1H/SP1L÷SP8H/SP8L) can function either as alarm (OFF) or as limit
supervisor (ON)
ON / OFF
ON
172
OFWC
Over Flow and Wrong Connection alarms activate (ON) or do not activate (OFF) the internal
general relay alarm
ON / OFF
ON
173
rP2H
Not in use
174
rP2L
Not in use
…
…
…
185
rP8H
Not in use
186
rP8L
Not in use
187
rEPE
Not in use
188
V-AD
Device’s address on monitoring network
0
98
0
189
ChM1
Input signal type in Channel 1, values: ”1” for J sensor, “2” for K sensor, “3” for PT100 sensor
with 3 cables, “4” for ΡΤ100 sensor with 2 cables, “5” for 4÷20 mA and “6” for 0÷20 mA
1
5
1
…
…
…
…
…
196
ChM8
Input signal type in Channel 8, values: ”1” for J sensor, “2” for K sensor, “3” for PT100 sensor
with 3 cables, “4” for ΡΤ100 sensor with 2 cables, “5” for 4÷20 mA and “6” for 0÷20 mA
1
5
1
3

Dimensions
Connection diagrams –channels
Input connections of channel Technical specifications
for each adjustment
Power supply: 24VAC ±10% 50/60Hz or 24VDC +30% / -10%
Maximum power consumption: 10W
Internal power supply fast blow fuse: 1A
Internal fast blow fuse in the outputs: 315mA
Internal fast blow fuse in the network: 315mA
General internal relay alarm 250VAC 10A resistive loads
Internal relay with one associated auxiliary contact 250VAC 10A for
setting up an external alarm circuit in case of main power failure
Accuracy: 1% ± 1 digit
LCD screen 2x16 characters
Operating temperature: -15÷+70 °C
Storage temperature: -20÷+80 °C
The devise is mounted on a panel hole with dimension 137x137mm
Connection with plug in screw terminals
IP protection rating: IP42 front side. To be installed in an enclosure which
provides protection against solid foreign objects and liquids at least IP42.
Class of equipment: Class II
Internal audible alarm is not included (buzzer)
4

Detection of cutline or short circuit line in the temperature sensors or 4÷20mA, 0÷20mA (sensor failure) in each
channel
ΡΤ100 and 4÷20mA:In case of cutline or short circuit line, the general relay is activated and the corresponding input’s LED is flashing.
Specifically:
1. ΡΤ100 3 cables: a) short circuit line: the general relay is activated, the corresponding input’s LED is flashing and the screen displays
OV F.
b) cutline in the sensor’s cable: the general relay is activated, the corresponding input’s LED is flashing and the screen displays
OV F.
c) cutline in the compensation’s cable: the general relay is activated, the corresponding input’s LED is flashing and the screen
displays WR C.
2. ΡΤ100 2 cables: cutline or short circuit line: the general relay is activated, the corresponding input’s LED is flashing and the screen
displays OV F.
3. 4÷20mA: cutline or short circuit line: the general relay is activated, the corresponding input’s LED is flashing and the screen displays
OV F.
Thermocouple J, K and 0÷20mA:In case of cutline the general relay is activated and the corresponding input’s LED is flashing.
Specifically:
3. Thermocouple J, K: a) cutline: the general relay is activated, the corresponding input’s LED is flashing and the screen displays OV F.
b) short circuit line: short circuit alarm corresponds to 0oC and the reception of the alarm can be adjusted by the parameters.
4. 0÷20mA: a) cutline:the general relay is activated, the corresponding input’s LED is flashing and the screen displays OV F.
b) short circuit line: short circuit alarm corresponds to 0mA and the reception of the alarm can be adjusted by the parameters.
Power failure setup
An internal relay 250VAC 10A with one contact (terminal blocks 34, 35) is available to set up an external alarm circuit in case main power
supply fails. When the device is powered on, the said auxiliary contact will open and when power failure occurs the same contact will
close, therefore an external alarm circuit with a separate power supply will also close and consequently, an audible and/or visual alarm will
be triggered
Internal fuses
Internal power supply fast blow fuse: 1A
Internal fast blow fuse in the outputs: 315mA
Internal fast blow fuse in the network’s communication: 315mA
ATTENTION to prevent electrostatic discharges at the side slots of the device and insertion of sharp objects
ATTENTION: separate the signal cables from the power supply cables to prevent electromagnetic disorders.
Signal cables must never be in the same pipe with the power supply cables.
Read and keep these instructions. The device is under a two years’ good operation guarantee. The guarantee is valid provided the
manual instructions have been applied. Check and service of the device must be performed by an authorized technician. The
guarantee covers only the replacement or the service of the device.
V1.6.220517 preserves the right to adjust its products without further notice www.kiour.com
5
Table of contents
Popular Security System manuals by other brands

BRINKS
BRINKS BHS 2000A Installation & programming manual

GeoVision
GeoVision GV-NVRH V5 user manual

Response
Response RE3000S Installation & operating handbook

ADEMCO
ADEMCO VIA-30PSE installation instructions

HSS Hire
HSS Hire GIANT VOICE TWS-Siren Series Installation, operation and troubleshooting manual

DSC
DSC IMPASSA Quick start installation guide