
10
MANUAL mode
In the MANUAL mode, the burner operates at
minimum power for the time set in the
service parameter Working time with
minimum power, and the exhaust fan,
regulating the air flow through the
exchanger, operates at a constant power set
in the service parameter Fan power. heater
before heating the exchanger until the value
of the service parameter Temp. air to start
the airflow, and then the fan starts to work
with the power set in the parameter Fan set
power or the power set from the fan power
level, which is set with the parameter: Fan
power. gear 1… Fan power - speed 5
corresponding to the selected burner power
point. The parameter is in the menu:
Device settings → Value of fan speeds
heater
3.4 SUPERVISION mode
The SUPERVISION mode occurs both in the
Standard mode and in the Fuzzy Logic mode.
The regulator enters the SUPERVISION mode
without user intervention:
• in the case of the Standard regulation
mode - after reaching the preset airflow
temperature,
• in Fuzzy Logic control - after exceeding the
preset airflow temperature by 5 ° C.
In the SUPERVISION mode, the regulator
supervises the furnace so that it does not go
out. For this purpose, the burner works with
very low power, which, with properly
selected parameters, does not cause any
further temperature increase. Burner power
and other SUPERVISION parameters are
grouped in the menu:
Service settings → Burner settings →
Supervision
The SUPERVISION mode parameters should
be set in accordance with the
recommendations of the burner
manufacturer. They should be selected so
that the furnace does not go out during
downtime. It should not ignite too much at
the same time, as this will increase the
temperature of the burner.
The parameters of the
SUPERVISION mode must be
selected so that the burner
temperature in this mode gradually
drops. Incorrect settings can lead
to overheating.
The maximum burner operation time in the
supervision mode is defined in the
Supervision time parameter. If, after the
expiry of this time, from the moment the
regulator enters the SUPERVISION mode,
there is no need for the burner to work
again, the regulator will start the
extinguishing process.
For the setting Supervision time = 0,
the regulator skips the SUPERVISION
mode and immediately enters the
BURNING OFF mode.
3.5 BURNING OFF mode
In the BURNING OFF mode, the remaining
fuel is burnt and the burner is prepared for a
standstill or shutdown. All parameters
influencing the extinguishing process are
grouped in the menu:
Service settings → Burner settings →
Putting out
The controller stops fuel feeding and
performs cyclical blows in order to burn off
fuel residues. After the flame brightness
decreases or the Maximum Putting Out Time
has expired, the regulator switches to the
STANDSTILL mode.
STANDSTILL mode
In the Standstill mode, the stove is off and
waiting for a signal to start operation. The
signal to start operation may be a drop in
temperature in the room below the preset
airflow temperature minus the value of the
furnace hysteresis. In this mode, the burner
fan runs continuously.
Burner cleaning service
The regulator enables cleaning the furnace
from the ashes generated during the
combustion process. For this purpose, the
controller uses the burner fan operation with
the power set in the Cleaning intensity
parameter. In the Burner cleaning parameter
in the Furnace settings menu, set the
maximum burner operation time without
cleaning, after which the furnace will switch
to the BURNING OFF mode, in which the