KIPI eSTER_x40 Series User manual

CONTROLLER
ecoMAX360P1-C
FOR PELLET FUEL BOILERS
INSTALLATION AND OPERATING MANUAL
ISSUE: 1.1_EN
11-2020
ecoNET300*
ecoNET.apk
ecoNET.app
www.econet24.com
ecoSTER200*
ecoSTER TOUCH*
eSTER_x80*
eSTER_x40*
functions available in the
additional module B
* devices are not the standard equipment of the controller.

ELECTRIC DEVICE UNDER VOLTAGE!
Before any action related to the power supply (cables connection,
device installation etc.) check if the controller is not connected to the
mains!
Installation should be done by a person with appropriate electrical
qualifications. Improper cables connection could result in the controller
damage.
The controller cannot be used in steam condensation conditions and
cannot be exposed to water.

3
TABLE OF CONTENTS
1RECOMMENDATIONS REGARDING SAFETY ........ 4
2GENERAL INFORMATION .................................... 5
3INFORMATION ABOUT DOCUMENTATION......... 5
4STORAGE OF DOCUMENTATION......................... 5
5APPLIED SYMBOLS .............................................. 5
6DIRECTIVE WEEE 2012/19/UE............................. 5
USER SETTINGS ............................................ 7
7USER MENU - STRUCTURE .................................. 8
8THE CONTROLLER SUPPORT ............................... 9
8.1 DESCRIPTION OF THE CONTROLLER SUPPORT.............. 9
8.2 DESCRIPTION OF THE MAIN SCREEN ......................... 9
8.3 THE CONTROLLER START-UP ................................. 10
8.4 PRESET TEMPERATURE SETTING ............................ 10
8.5 FIRING UP MODE............................................. 10
8.6 OPERATION MODE .......................................... 10
8.7 REGULATION MODES .......................................... 11
8.8 SUPERVISION MODE ....................................... 11
8.9 BURNING OFF MODE....................................... 12
8.10 STOP MODE..................................................... 12
8.11 GRATE ........................................................... 12
8.12 BURNER CLEANING............................................. 12
8.13 HUW SETTINGS................................................. 12
8.14 HUW PRESET TEMPERATURE SETTINGS .................. 13
8.15 HYSTERESIS OF HUW......................................... 13
8.16 SUMMER FUNCTION START-UP........................... 13
8.17 HUW CONTAINER DISINFECTION........................... 13
8.18 MIXER CIRCLE SETTINGS ...................................... 13
8.19 WEATHER CONTROL ........................................... 14
8.20 NIGHT DECREASE SETTINGS DESCRIPTION ................ 15
8.21 WORKING ACCORDING TO SCHEDULE ..................... 15
8.22 CIRCULATION PUMP CONTROL .............................. 15
8.23 FUEL LEVEL CONFIGURATION ................................ 16
8.24 FEEDER TEST ..................................................... 16
8.25 INFORMATION................................................... 16
8.26 MANUAL CONTROL ............................................ 16
8.27 COOPERATION WITH THE ROOM THERMOSTAT AND
ROOM PANEL .................................................... 17
8.28 COOPERATION WITH THE INTERNET MODULE........... 17
INSTALLATION AND SERVICE SETTINGS....... 19
9HYDRAULIC SCHEMES ....................................... 20
10 TECHNICAL DATA .............................................. 23
11 CONDITIONS OF STORAGE AND TRANSPORT ... 23
12 THE CONTROLLER INSTALLATION ..................... 23
12.1 ENVIRONMENTAL CONDITIONS ............................. 23
12.2 INSTALLATION REQUIREMENTS.............................. 23
12.3 INSTALLATION OF MODULE................................... 23
12.4 CONNECTING ELECTRICAL SYSTEM ......................... 24
12.5 ELECTRIC SCHEME .............................................. 26
12.6 CONNECTION OF TEMPERATURE SENSORS ............... 28
12.7 CONNECTING WEATHER SENSOR ........................... 28
12.8 TEMPERATURE SENSORS CHECKING........................ 29
12.9 OPTICAL SENSOR CONNECTION..............................29
12.10 MIXERS ROOM TEMPERATURE CONNECTION ............29
12.11 CONNECTION OF RESERVE BOILER ..........................29
12.12 CONNECTION OF ALARM SIGNALING .......................30
12.13 MIXER CONNECTION ...........................................31
12.14 CONNECTING OF CIRCULATION PUMP .....................31
12.15 CONNECTING OF SAFETY TEMPERATURE LIMITER .......31
12.16 THERMAL PROTECTION ........................................32
12.17 CONNECTING OF ROOM THERMOSTAT ....................32
12.18 CONNECTING OF INTERNET MODULE ......................33
13 SERVICE MENU –STRUCTURE ...........................34
14 DESCRIPTION OF SERVICE PARAMETERS...........35
14.1 BURNER ...........................................................35
14.2 BOILER .............................................................36
14.3 CH AND HUW ..................................................36
14.4 BUFFER ............................................................37
14.5 MIXER..............................................................37
14.6 OTHER PARAMETERS ...........................................38
15 ALARMS DESCRIPTIONS.....................................39
15.1 BOILER MAX.TEMP.EXCEEDING ............................39
15.2 BURNER MAX.TEMP.EXCEEDING...........................39
15.3 BOILER TEMP.SENSOR DAMAGE ............................39
15.4 FEEDER TEMP.SENSOR DAMAGE............................39
15.5 OVERHEATING BOILER,STB OPEN CONTACT ............39
15.6 FIRING UP FAILED ATTEMPT ..................................39
16 ADDITIONAL FUNCTIONS...................................39
16.1 POWER STOPPAGE..............................................39
16.2 ANTIFREEZING PROTECTION..................................39
16.3 PREVENTIVE COOLING .........................................40
16.4 PUMP ANTI STANDSTILL FUNCTION.........................40
17 REPLACEMENT OF COMPONENTS.....................40
17.1 FUSE REPLACEMENT............................................40
17.2 SOFTWARE REPLACEMENT....................................40
18 POSSIBLE FAULTS DESCRIPTION ........................41

4
1Recommendations regarding safety
Requirements concerning safety are
described in detail in individual chapters of
this manual. Apart from them, the following
requirements should in particular be
observed.
•Before starting assembly, repairs or
maintenance, as well as during any
connection works, please make sure
that the mains power supply is
disconnected and that terminals and
electric wires are devoid of voltage.
•After the controller is turned off,
dangerous voltage still can occur on
its terminals.
•The controller cannot be used at
variance with its purpose.
•Additional automatics which protect
the boiler, central heating (CH)
system, and domestic hot water
system against results of malfunction
of the controller, or of errors in its
software, should be applied.
•Choose the value of the programmed
parameters accordingly to the given
type of boiler and fuel, taking into
consideration all the operational
conditions of the system. Incorrect
selection of the parameters can cause
malfunction of the boiler (e.g.
overheating of the boiler, the flame
going back to the fuel feeder, etc.),
•The controller is intended for boiler
manufacturers. Before applying the
controller, a boiler manufacturer
should check if the controller’s mating
with the given boiler type is proper,
and whether it can cause danger.
•The controller is not an intrinsically
safe device, which means that in the
case of malfunction it can be the
source of a spark or high temperature,
which in the presence of flammable
dusts or liquids can cause fire or
explosion. Thus, the controller should
be separated from flammable dusts
and gases, e.g. by means of an
appropriate body.
•The controller must be installed by a
boiler manufacturer in accordance
with the applicable safety standards.
•The programmed parameters should
only be altered by a person
familiarized with this manual.
•The device should only be used in
heating systems in accordance with
the applicable regulations.
•The electric system in which the
controller operates must be protected
by means of a fuse, selected
appropriately to the applied loads.
•The controller cannot be used if its
casing is damaged.
•In no circumstances can the design of
the controller be modified.
•Keep the controller out of reach of
children.

5
2General information
The controller ecoMAX360P1-C is a device
designed to control the operation of a boiler
with automatic feeding of solid fuel with a
igniter. Flame detection is performed with
the use of an optical flame brightness sensor.
It can control the work of central heating and
hot water circuits and also control the work
of mixing heating circuits. The required
temperature of heating circuits can be set on
the basis of data obtained from the weather
sensor. The possibility of cooperation with
room thermostats, separate for each heating
circuit is beneficial for maintaining
comfortable temperature in heating rooms.
The controller may operate in connection
with additional wire room thermostat/panel
ecoSTER200, ecoSTER TOUCH and wireless
room thermostat/panel eSTER_x80 or
eSTER_x40 installed in rooms and
ecoNET300 Web module. Additionally it
cooperates with extension B module.
The controller may be used in households
and other similar premises and in light
industry facilities.
3Information about documentation
The controller manual is a supplement for
the boiler manual. In particular, except for
this manual, the boiler manual should also be
observed. The controller manual is divided
into two parts: for user and fitter. Yet, both
parts contain important information,
significant for safety issues, hence the user
should read both parts of the manual.
We are not responsible for any damages
caused by failure to observe these
instructions.
4Storage of documentation
This assembly and operation manual, as well
as any other applicable documentation,
should be stored diligently, so that it was
available at any time. In the case of removal
or sale of the device, the attached
documentation should be handed over to the
new user / owner.
5Applied symbols
In this manual the following graphic symbols
are used:
- useful information and tips,
- important information, failure to
observe these can cause damage of
property, threat for human and
household animal health and life.
Caution: the symbols indicate important
information, in order to make the manual
more lucid. Yet, this does not exempt the
user from the obligation to comply with
requirements which are not marked with a
graphic symbol!
6Directive WEEE 2012/19/UE
Purchased product is designed and made of
materials of highest quality. The product
meets the requirements of the Directive
2012/19/EU of 4 July 2012 on waste
electrical and electronic equipment
(WEEE), according to which it is marked by
the symbol of crossed-out wheeled bin (like
below), meaning that product is subjected to
separate collection.
Responsibilities after finishing a period of
using product:
•dispose of the packaging and product at
the end of their period of use in an
appropriate recycling facility,
•do not dispose of the product with other
unsorted waste,
•do not burn the product.
By adhering obligations of waste electrical
and electronic equipment controlled disposal
mentioned above, you avoid harmful.

6

USER SETTINGS
ecoMAX360P1-C

8
7User menu - structure
Boiler settings
Preset boiler temp.
Weather contr.boiler*
•Heating curve*
•Curve shift*
•Room temp.factor*
Output modulation
•MAX boiler output
•MAX blow-in output
•Average hysteresis H2
•Aver. boiler output
•Average blow-in output
•MIN hysteresis H1
•MIN boiler output
•MIN blow-in output
•Boiler hysteresis
•Min. boiler output FL*
•Max. boiler output FL*
•Blow-in output-grate*
•Feeder:
- Feeder efficiency
- Feeder test
- Fuel dose from test
Boiler oper. mode*
•Pellet, Grate
Regulation mode
•Standard, Fuzzy Logic
Fuel type*
Fuel level
•Alarm level
•Fuel level calibration
Burner cleaning
Cleaning intensity
HUW settings*
Preset HUW temp.
HUW pump mode
•Off, Priority, No priority
HUW cont. hysteresis
HUW disinfection
Night time decrease
Boiler, HUW container, Mixer, Circulation
pump*
•Off
•Reduction value
•Schedule
Sommer/Winter
SUMMER mode
•Summer, Winter, Auto*
Activ. temperature SUMMER
Deactv. temperature SUMMER
Mixer settings 1-2*5
Preset mixer temp.
Mixer room thermostat
Weather control mixer*
Heating curve mixer*
Curve shift*
Room temp. factor*
General settings
Clock
Screen brightness
Screen contrast
Alarms sound
Touch sound
Language
WiFi*
Weather sensor
•Sensor type:
- None, CT6-P, CT4-P
•Sensor correction
* not available if proper sensor or additional
module not connected or the parameter is
hidden.
Main menu
Information
Boiler settings
HUW settings*
Mixer 1-2 settings*
Night time decrease
Summer/Winter
Operation with schedule
•On, Schedule
General settings
Manual control
Alarms
Service settings

9
8The controller support
The following describes the shortened
manual of the controller.
8.1 Description of the controller
support
The controller is operated by pressing
buttons that allow to select items from the
menu and edit parameters.
View of the controller control panel.
Buttons description:
1. Exit from the currently selected menu
level as well as abandoning the set value.
2. Reduce the edited value.
3. Increase the edited value.
4. Enter the MENU and confirm the setting
of the selected parameter.
8.2 Description of the main screen
Main screen view.
Legend:
1. The controller modes: FIRING UP,
OPERATION, SUPERVISION, BURNING
OFF, STOP,
2. boiler preset temperature,
3. boiler measured temperature,
4. functions having influence on preset
boiler temperature:
- preset boiler temperature
decrease due to thermostat
disconnection,
- preset boiler temperature
decrease due to activated time
spans,
- boiler preset temperature during
loading the hot water boiler (HUW),
- boiler preset temperature increase
from mixer circulation,
- activation of weather control for
the boiler circuit,
5. signaling blowing operation,
6. signaling fuel feeder operation,
7. signaling boiler pump (central heating
pump) operation,
8. signaling central heating pump operation
(HUW),
9. measured temperature of hot water tank
(HUW),
10. preset hot water (HUW) tank
temperature,
11. clock and weekday,
12. part of the screen coshared between two
icons:
–symbolizes operating heater, and
the digit next to it stands for a number of
Firing-up attempts;
–symbolizes activating automatics
of furnace cleaning;
13. external (weather) temperature,
14. current boiler power level,
15. signaling activating regulating mode
Individual Fuzzy Logic,
16. signaling disinfection of the hot water
container,
17. signaling burner feeder (stoker)
operation.
Right window on the main screen is
configurable, allows on changing information
displayed there. It is possible to choose a
configuration displaying by pressing the
or button. Note: after connecting the
8
13
14
15
11
10
9
16
18
12
7
6
5
2
4
1
3
FIRE UP
Mon
17

10
expansion module B, the mixer information
windows are activated.
Main screen configuration view.
Right window on the main screen may also
display the fuel level view, providing that this
parameter is set correctly. Tip: Fuel level
may be displayed on room panel.
8.3 The controller start-up
After connecting the power the controller
shows the settings put before connecting the
electricity. If the controller has not operated
before it will start up in „Stand-by” mode. In
this mode the screen is dimmed, actual time
and information “Boiler Off” is displayed.
View of the controller off screen.
In „Stand-by”mode protecting
pumps against going stale function is
in operation. It is executed by
temporary switching them on.
Therefore it is advised to keep the
electrical power to the controller on
when the boiler is not in use.
It is possible to start-up the boiler by
pressing the button and selecting the
activation, or setting its operating
parameters by the or buttons,
without having to turn it on. After making
sure that fuel is in the fuel silo, and the
hatch is closed the boiler can be switched on.
8.4 Preset temperature setting
The preset boiler temperature and preset
circuits temperature can be set in the menu
(possible temperatures are restricted with
range of respective service parameters of the
controller):
Boiler settings →Preset boiler temp.
Mixer settings 1-2 →Preset mixer temp.
The parameter value Preset boiler temp., is
by controller bypassed when the preset
boiler temperature is controlled by weather
sensor. Regardless of that, the preset boiler
temp. is automatically increased to load the
hot user water tank and power heating
circuits of mixers.
8.5 FIRING UP mode
The FIRING UP mode is for automatic firing
up of furnace in boiler. Total time of firing up
process is depends on controller’s settings
and on boiler’s condition before firing up.
Parameters influencing firing up process are
in the menu:
Service settings →
Burner settings →Firing-up
In case of failed attempt of firing up the
furnace another attempts are taken during
which amount of fuel is reduced to 10% of
first attempt’s dose. Firing up attempts are
signaled by the numbers next to the igniter
symbol.
After three failed firing up attempts an alarm
“Failed firing up attempt” is reported. Boiler’s
operation is then stopped. It is not possible
to automatically continue boiler’s operation.
Service intervention is required. After finding
and solving the cause of firing up failure the
boiler should be fired up again.
8.6 OPERATION mode
In the OPERATION modes the burner fan
operates constantly, fuel feeder is engaged
periodically, where period consists of fuel
feeder (stoker) operating time and pause in
fuel feeding time.
Fan and feeder operation cycles.
Boiler Off
Feed time
operat
Feed interval
operat
Feed time
operat
Feed interval
operat

11
The Cycle time OPERAT. parameter is located
in the menu:
Service settings →Burner settings →
Operation
Feeder operation time is calculated
automatically depending on the required
current power of the burner, Feed efficiency
and Calorific value of the fuel. Parameters of
blow-in output for different power levels of
the burner are available in the menu:
Boiler settings →Output modulation
8.7 Regulation modes
Can choose between two adjustment modes
responsible for stabilizing the boiler preset
temperature: Standard and Fuzzy Logic. This
mode changes in the menu:
Boiler settings →Regulation mode
•Standard mode operation
If the boiler’s temperature reach preset one
then the controller switches off to the
SUPERVISION mode.
The controller is equipped with boiler’s power
modulation mechanism which allows for
gradual power reduction when approaching
the preset temperature. There are three
power boiler levels: MAX, Average, MIN.
Current power level is displayed on the screen - 3
segmented indicator.
Each level can be allocated with seperate
blow-in output which influence on actual
boiler’s power level. Power levels parameters
are available in the menu:
Boiler settings →Output modulation
The controller regulates burner’s power with
which it operates depending on preset
temperature and defined hysteresis Average
hysteresis H2 and MIN hysteresis H1. It is
possible to configure volumes hysteresis H1
and H2 in such a way that modulation is
done without intermediate position. That
means switching from MAX to MIN with
omission of Aver. power.
Hysteresis of power levels.
•Operation in Fuzzy Logic mode
In Fuzzy Logic mode the controller
automatically regulates burner power to
allow boiler operation in such a way to
maintain its temperature on preset level. The
controller uses power levels defined in
Standard mode. In this mode the parameters
Average hysteresis H2 and MIN hysteresis H1
do not have to be set. The Fuzzy Logic mode
unlike the Standard mode is not faulty in
respect of failing to reach the preset boiler
temperature due to incorrect adjustement of
H2 and H1 hysteresis. It also allows for
quicker reach the preset temperature. In
addition, you can adjust the boiler output in
FL mode by the parameters Min boiler output
FL and Max boiler output FL.
After exceeding the preset temperature by
5ºC the controller switches into
SUPERVISION mode.
8.8 SUPERVISION mode
The SUPERVISION mode is applicable either
in regulation in Standard and Fuzzy Logic
mode. The controller switches into
SUPERVISION mode automatically without
user’s intervention:
•in Standard regulation mode –after
reaching the boiler preset temperature,
•in Fuzzy Logic steering –after exceeding
boiler preset temperature by 5ºC.
In SUPERVISION mode the controller
oversees the furnace, keeping it from
burning off. To do so, the burner operates
with very low power, what together with
properly adjusted parameters do not cause

12
further increase in temperature. Burner’s
power in SUPERVISION mode and other
parameters of Supervision are grouped in the
menu:
Service settings →Burner settings →
Supervision
Parameters of SUPERVISION mode are to be
set in accordance to burner/boiler producer’s
recommendations. They should be so chosen
to prevent the furnace from burning off
during boiler’s pauses (the furnace should
not at the same fire up to too high a
temperature, because it will cause too high a
temperature of the boiler).
The parameters in this mode must
be so chosen as to make the boiler
temperature gradually decreasing.
Incorrect settings can cause boiler
overheating.
Maximum time of boiler’s operating in
supervision mode is defined in service
parameter Supervision time. If after this time
(in Supervision mode) there is no need to
restart the boiler then the controller starts
the process of boiler’s burning off.
For setting Supervision time = 0 the
controller omits SUPERVISION mode
and goes directly to BURNING OFF.
8.9 BURNING OFF mode
In BURNING OFF mode the leftovers of pellet
are burnt and the boiler is prepared to pause
or deactivation. All the parameters
influencing burning off process are grouped
in the menu:
Service settings →
Burner settings →Burning off
The controller stops feeding fuel and makes
periodical blowings to burn off remnants of
fuel. After decrease of flame brightness or
maximum time of burning off expiration the
controller turns into STOP mode.
8.10 STOP mode
In the STOP mode the boiler is being burnt
off and awaits the signal to start operation.
The following can be a signal to start
operation decrease of preset boiler
temperature below preset temperature
diminished by boiler hysteresis (Boiler
hysteresis).
8.11GRATE
Some boilers have an additional grate to
burn other fuels such as wood waste, etc. To
activate the grid, move the parameters
available in the menu:
Boiler settings →Boiler oper. Mode from
Pellet to Grate. In the grate mode fuel feeder
is turned off. The combustion process is
regulated by the blow-in fan. Fan power,
when working with grate, is set in the menu:
Boiler settings →Output modulation →
Blow-in output –grate
The values of parameters such as: Preset
boiler temp., Boiler hysteresis, Fuel detection
time are individually adjusted for the Grate.
This allows to define different properties of
boiler operation for operation modes Grate
and Pellets.
8.12Burner cleaning
The controller is used for cleaning the
furnace of ashes generated in the
combustion process. For this purpose, the
controller uses the work of the blow-in fan
with power set in the Cleaning intensity
parameter, in the menu Boiler settings, set
the time of the burner operation without
cleaning after which the boiler will enter the
BURNING OFF mode, in which the
mechanism for rotary cleaning of the burner
will be started and then firing-up the burner.
Purification of the furnace is made during
FIRING UP and BURNING OFF. Additional
parameters responsible for cleaning are in
the menu:
Service settings →Burner settings →
Cleaning
8.13HUW settings
The controller regulates temperature of the
HUW tank, providing that the temperature
sensor is connected. When the sensor is
disconnected –the information about it is
displayed in the main window. By selecting:
HUW settings →HUW Pump mode the
user is able to:
•deactivate feeding the silo, parameter
Off,
•setting HUW priority, by parameter
Priority –then CH pump is deactivated to
feed the HUW boiler quicker,

13
•set simultaneous operation of CH and
HUW pump with the parameter No
priority.
8.14 HUW preset temperature settings
Preset temperature HUW is defined by
parameter:
HUW settings →Preset HUW temp.
8.15 Hysteresis of HUW
Below temperature Preset HUW temp. minus
HUW hysteresis the HUW pump will activate
to feed the HUW tank.
By small hysteresis value HUW
pump will activate faster after HUW
temperature decrease.
8.16 SUMMER function start-up
To activate SUMMER function which allows
feeding the silo during summer, without
necessity to activate CH installation and
mixers periods, it is required to set the
menu:
Summer/Winter → SUMMER mode for
Summer
It is not allowed to activate
function Summer when HUW pump
is disconnected or damaged.
Function SUMMER can be activated
automatically, on the basis of readings from
weather sensor. Use following parameters to
activate this function:
Summer/Winter → SUMMER Mode →
Auto
If the automatic detection of summer mode
is switched on, user can set the parameters:
Activ. temperature SUMMER, so outdoor
temp. above which the summer mode will be
switched on and Deactv. temperature
SUMMER , so outdoor temp. below which the
SUMMER mode will be switched off.
8.17 HUW container disinfection
The controller can automatically, periodically
make HUW container warm up to 70ºC. It is
done to remove bacterial flora.
It is absolutely important to inform
all the inmates about activating the
disinfection function. There is a
danger of scalding with hot water.
Once a week at night, in Monday at 2 a.m.
the controller increases temperature of HUW
container. After 10minutes of keeping the
silo at 70ºC the HUW pump is deactivated
and the silo returns to its normal operation.
It is not advisable to activate disinfection
function while the service of HUW is
deactivated.
8.18 Mixer circle settings
Mixer circuit support is only
available when an additional
expansion module B is connected.
Settings of first mixer circle are in the menu:
Mixer 1 settings
Settings for other mixers are in following
sections of the menu and are identical in
each cycle.
•Mixer settings without weather
sensor
It is required to set manually desired
temperature in mixer’s heating cycle using
parameter Preset mixer temp., e.g. 50ºC.
Such should be a value to provide required
room temperature. After connecting a room
thermostat, value of decline in preset mixer
temperature from thermostat should be set.
(parameters Mixer room thermostat, e.g.
5ºC. This value should be chosen
experimentally. A room thermostat can be a
traditional one or a room panel. After
activating the thermostat, mixer preset
temperature will be reduced. When this value
is reduced correctly then room temperature
increase will be stopped.
•Mixer settings with weather sensor
setting
Set parameter Weather mixer control in
position on. Adjust weather curve according
to point 8.19. Using parameter Curve shift
set required room temperature according to
formula:
Required room temperature = 20°C +
heating curve shift.
Example:
To reach room temperature 25°C value of
heating curve shift must be set for 5°C. To
reach room temperature 18°C value of
heating curve shift must be set for -2°C.

14
In this configuration a thermostat can be
connected. It will level inaccuracy of heating
curve adjustement in case when its value will
be too big. In such case value of decrease of
preset mixer room temperature from
thermostat should be set i.e. for 2°C. After
discontecting thermostat plugs preset mixer
cycle temperature will be reduced. By correct
adjustement of this reduction will stop
temperature increase of temperature in
heated room.
•Mixer settings with weather sensor
and room panel settings
Set parameter Weather mixer control. In
position off. Adjust weather curve according
to point 8.19. Room panel automatically
moves the heating curve depending on
preset room temperature. The controller
relates adjustements to 20ºC, i.e. for preset
room temperature = 22ºC the controller will
move heating curve by 2ºC, for preset room
temperature = 18ºC the controller will move
heating curve by -2ºC. In some cases
described in point 8.19 it can be necessary to
adjust heating curve movement.
In this configuration room thermostat is able
to:
- reduce temperature of heating cycle by a
constant value, when preset temperature in
a room will be reached. Similarly like it was
described in previous point (not
recommended), or
- automatically, constantly correct heating
cycle temperature.
It is not recommended to use both these
possibilities at the same time.
Automatic correction of room temperature is
done according to formula:
Correction = (preset room temperature –
measured room temperature) x room
temperature factor / 10
Example:
Preset temperature in heating room (set in
room panel) = 22ºC. Measured temperature
in room (using room panel) = 20ºC. Room
temperature factor = 15
Preset mixer temperature will be increased
by (22ºC –20ºC) x 15/10 = 3ºC. Correct
value of parameter must be found room
temperature factor. The bigger value of
factor the bigger correction of preset boiler
temperature factor. When set on value “0”
preset mixer temperature is not corrected.
Attention: setting too high value of room
temperature factor may cause cyclic room
temperature fluctuations.
8.19 Weather control
To control the boiler temperature from the
outside temperature, must be weather
control activated. Weather control requires
connecting an outside (weather) temperature
sensor. Weather sensor support should be
enabled in accordance with point 12.7
Depending on measured outside
temperature, automatically controlled can be
either preset boiler temperature and mixer
cycles temperatures. By correct adjustment
of heating curve temperature of heating
circuits is counted automatically depending
on value of external temperature. Thanks to
that by choosing proper heating curve for
given building, room temperature remains
approximately the same –no matter what
outside temperature. Attention: in the
process of experimental adjustement of
proper heating curve it is necessary to
exlude influence of room thermostat on
controller work (irrespectively if room
thermostat is connected or not), by adjusting
parameter:
Service settings → Boiler settings →
Thermostat select on OFF.
In case of connected room panel set
additionally Room temp. factor = 0.
Guidelines for correct heating curve settings:
•Floor heating 0,2 -0,6
•Radiator heating 1,0 - 1,6
•Boiler 1,8 - 4

15
Tips for choosing proper heating curve:
•If by falling outer temperature room
temperature is increasing, then value of
chosen heating curve is too big,
•If by decreasing outer temperature, room
temperature is also decreasing, then
value of chosen heating curve is too low,
•by frosty weather room temperature is
appropriate and in warmer time is too low
–it is recommended to increase
parameter Curve shift and then choose
lower heating curve
•If by frosty weather room temperature is
too low and in warmer time too high –it
is recommended to reduce parameter
Curve shift and choose higher heating
curve.
Buildings which are poorly isolated require
setting heating curve with higher values, and
for better isolated buildings heating curve
will have lower value.
Preset temperature, counted according to
heating curve can be decreased or increased
by controller when it goes beyond scope of
limits of temperatures for given cycle.
8.20 Night decrease settings
description
In the controller it is possible to set time
intervals of preset temperature reduction for
boiler, heating cycles, HUW tank, circulation
pump. Time intervals allow setting
temperature reduction in given time period –
i.e. at night or when user leaves the heated
room. Thanks to it preset temperature can
be reduced automatically, without loss of
heating comfort by reducing fuel
consumption. Decrease of preset
temperature in selected time intervals is
indicated by the symbol on the main
screen.
To activate time intervals, set the parameter
Night time decrease for the given heating
circuit to ON. The parameter Reduction value
set the temperature reduction, one for all
time intervals. Night time decreases can be
defined separately for every day of the week
set Schedule. Select temperature reduction
and beginning and end of respective time
interval. The time intervals for 24 hours are
fixed at 30min.
Time periods.
Above are examples of night-time decrease
the preset temperature lasting from 22:00
till 06:00 and the reduction from 09:00 to
15:00.
Attention, defining time periods
during one day must be started at
00:00!
Time period is omitted by setting
period reduction for value “0” even
if scope of hours is set in it.
8.21Working according to schedule
In the controller is possible to switch on and
switch off the boiler at defined intervals. In
the absence of demand for heat, e.g. in
summer, one can disable the operation of the
boiler at a certain time and thus reduce fuel
consumption. To activate the time intervals
must set the parameter Off,in the menu:
Work acc. schedule →On at YES.
Switching on and off the boiler in the time
interval can be set for all on separate days of
the week in the Schedule.
Work according to the schedule is the same
as that night time decrease, point 8.20
8.22Circulation pump control
Functionality of circular pump is available in
the menu (only after connecting the
additional module B):
Night time decrease →Circular pump.
and

16
Service settings →CH and HUW settings
Settings of time control of circular pump are
analogical to settings of night reductions. In
defined time periods circular pump is
deactivated. In omitted periods the circular
pump is switched into position Circulating
operation time, what Circulating standstill
time.
8.23Fuel level configuration
•Fuel level indicator activating
To activate displaying fuel level following
parameters are to be set
Boiler setting →Fuel level →Alarm level
on value bigger than “0”, i.e. 10%.
Pressing or button in the main
window fuel level is displayed in main
window.
•Fuel level indicator service
Each time after filling the fuel silo to the
intended level, press the button for a
longer time - then the prompt "Set fuel level
to 100%" will appear. After accepting on YES
fuel level will be set for 100%.
Tip: Fuel can be refilled anytime, that means
it is not needed to wait till the silo is empty.
However fuel should be filled up to the level
corresponding to 100% and set the controller
level by pressing button.
•Description of activity
The controller measured fuel level on the
basis of its current consumption. Factory
settings will not always correspond to actual
fuel consumption, so to work correctly this
method needs level calibration by controller’s
user. No additional fuel sensors are required.
•Calibration
Fill the fuel silo to the level which
corresponds to full level of fuel, then set
value of parameter:
Boiler settings →Fuel level →Fuel level
calibration →Fuel level 100%
In main window the indicator will be set on
100%. The calibration process is marked
with a pulsating fuel level indicator. The
indicator will pulsate until programming point
referring to minimum fuel level. Decreasing
level of fuel in the silo should be monitored
constantly. When fuel level reaches expected
minimum, parameter value should be set this
way:
Boiler settings →Fuel level →Fuel level
calibration →Fuel level 0%
8.24 Feeder test
The controller allows to test the efficiency of
the burner feeder, which has a significant
impact on the operation of the burner. The
test is started with the Feeder test parameter
in the menu:
Boiler settings →Feeder
Remove the flexible tube from the burner
and direct its end into a plastic bag. Run the
feeder test. After the test, weigh the fuel and
enter the measured value into the Fuel dose
from test parameter in the test.
8.25Information
Menu Information enables view to
measured temperatures and allows to check
which of devices are currently activated.
Switching between following screens is done
by pressing or button.
After connecting extension B module
of mixers information about
auxiliary mixers are displayed.
8.26 Manual control
In the controller it is possible to manual
activate devices like i.e. pumps, feeder
engine, or blower engine. It enables to check
if the device is operating correctly and if it is
connected properly.
Entering manual control menu is
possible only, when boiler is
switched off.

17
Manual control screen view: OFF –the device is turned
off, ON –the device is turned on.
Attention: long lasting activating of
fan, feeder or other device may
cause danger.
8.27 Cooperation with the room
thermostat and room panel
The controller can cooperate with:
•the eSTER_x40 wireless and battery room
thermostat, via two-way ISM
communication,
•the eSTER_x80 wireless room panel with
room thermostat function, via two-way
ISM communication,
•the ecoSTER200 and ecoSTER TOUCH
wired room panel, with room thermostat
function.
The thermostat and room panel
simultaneously provides useful information,
among others, such as: information about
the fuel level, burner operation status,
signals alarms, allows to set the controller
parameters, its modes of operation, also
serves as an additional boiler control panel.
8.28Cooperation with the Internet
module
The controller can work together with
ecoNET300 Web module. It enables online
control and supervision over the controller
for the help of the website
www.econet24.com. You can use the
convenient mobile application ecoNET.apk
and ecoNET.app. Mobile application can be
downloaded free of charge from the website.
ecoNET.apk (Android)
ecoNET.app (iOS)

18

19
INSTALLATION AND SERVICE SETTINGS
ecoMAX360P1-C

20
9Hydraulic schemes
Scheme with a three-way thermostatic actuator to protect the return water temperature
1
: 1 –
boiler, 2 –controller, 3 –boiler temperature sensor, 4 –outside (weather) temperature sensor, 5 –room
thermostat, 6 –boiler pump, 7 - three-way thermostatic valve (manually adjustable), 8 - throttle (poppet)
valve, 9 –HUW pump, 10 - HUW temp. sensor, 11 –HUW tank, 12 –burner feeder (stoker), 13 –burner
fan, 14 –main fuel feeder.
RECOMMENDED SETTINGS:
Parameter
Setting
MENU
Preset boiler temp.
75-80C
Boiler settings
Min. boiler temp.
65C
Service settings→Boiler settings
Boiler inc. by HUW and Mixer
5-20C
Service settings→CH and HUW settings
Boiler room thermostat
eSTER T1
Service settings→Boiler settings
1
The presented hydraulic scheme does not replace central heating engineering design and may be used for
information purposes only!
This manual suits for next models
5
Table of contents
Other KIPI Controllers manuals